![background image](http://html1.mh-extra.com/html/omron/s8ea-series/s8ea-series_manual_743692003.webp)
S8EA
3
Ratings, Characteristics, and Functions
*1.
Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal
temperature of the Power Supply may result in ignition or burning.
*2.
For details, refer to
Output Voltage Adjuster (V. ADJ)
on page 16.
*3.
Specified for the rated input voltage (100 VAC) and a 100% load.
The measurement method is based on JEITA standard RC-9131B.
For details, refer to
Ripple Noise Voltage
on page 17.
*4.
To reset the protection, turn OFF the input power for three minutes or longer and then turn it back ON.
*5.
The weight is for an open-frame model.
*6.
The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 120 VAC (85 to 132 VAC).
*7.
Class B compliance was met with an aluminum plate placed under the Power Supply.
*8.
Excluding models with low leakage current.
Power rating
50 W
75 W
Item
Output voltage
5 V
12 V
24 V
5 V
12 V
24 V
Efficiency (Typ.)
100 VAC input
78%
84%
85%
83%
85%
88%
Input
Voltage
*
1
100 to 120 VAC (allowable voltage: 85 to 132 VAC, 120 to 175 VDC
*
6)
Frequency
*
1
50/60 Hz (47 to 63 Hz)
Current (Typ.)
100 VAC input
1.3 A
1.4 A
1.6 A
Power factor
---
Harmonic current emissions
---
Leakage current
100 VAC input
0.5 mA max. (model with low leakage current: 0.1 mA max.)
Inrush current
100 VAC input
17.5 A max.
Output
Voltage adjustment range
*
2
±10% (with V. ADJ)
Ripple
*
3
150 mV max.
240 mV max.
480 mV max.
150 mV max.
240 mV max.
480 mV max.
Input variation influence
±1% max. (with 100 VAC input at 100% load)
±1% max. (with 100 VAC input at 100% load)
Load variation influence
2% max.
1.5% max.
2% max.
1.5% max.
Temperature variation influence
0.05%/°C max.
Startup time (Typ.)
100 VAC input
400 ms
550 ms
Hold time (Typ.)
100 VAC input
20 ms
25 ms
Additional
functions
Overload protection
105% to 160% of rated load current, voltage drop, intermittent, automatic reset
Overvoltage protection
*
4
Yes (at 130% or higher of rated output)
Series operation
Yes (For up to two Power Supplies; external diodes required.)
Parallel operation
No
Other
Ambient operating temperature
−
10 to 60°C (Derating is required according to the temperature.) (with no icing or condensation)
Storage temperature
−
25 to 75°C
Ambient operating humidity
25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 kVAC for 1 min. (between all inputs and outputs; Cutoff current: 10 mA)
2.0 kVAC for 1 min. (between all inputs and PE; Cutoff current: 10 mA)
1.0 kVAC for 1 min. (between all outputs and PE; Cutoff current: 20 mA)
Insulation resistance
100 M
Ω
min. (between all outputs and all inputs/PE)
Vibration resistance
10 to 55 Hz, 19.6 m/s
2
(2 G) for 1 h each in X, Y, and Z directions
Shock resistance
196.1 m/s
2
, 3 times each in ±X, ±Y, ±Z directions
Conducted emissions
Conforms to EN 55011 Group 1 Class B
*
7
*
8
Radiated emissions
Conforms to EN 55011 Group 1 Class B
*
7
*
8
Approved standards
UL UR: UL 60950-1 (Recognition)
cUR: CSA C22.2 No. 60950-1
EN: EN 50178 and EN 60950-1
SEMI
---
Weight
*
5
140 g max. (without chassis and cover)
190 g max. (without chassis and cover)