background image

S8VK-G

5

*1.

Do not use an inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning.

*2.

For a cold start at 25

°

C. Refer to 

Engineering Data

 on page 9 to 11 for details.

*3.

If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +15% of the voltage adjustment range. When adjusting the output voltage, confirm 
the actual output voltage from the Power Supply and be sure that the load is not damaged. 

*4.

A characteristic when the ambient operating temperature is between –25 to 70

°

C.

*5.

Refer to 

Overvoltage Protection

 on page 10 for the time when input voltage shuts off and input turns on again.

*6.

The value is when both rated output voltage and rated output current are satisfied.

*7.

100 to 240 VAC input, in the range of 0 A to the rated output current

*8.

This is the maximum variation in the output voltage when the input voltage is gradually changed within the allowable input voltage range at the rated output voltage and rated output current.

*9.

Refer to 

Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance

 on page 22 for details.

*10.

 Safety Standards for a DC Input
The following safety standards apply to a DC input: UL 60950-1, cUR (CSA C22.2 No. 60950-1), EN 50178, EN 60950-1, and Lloyd’s. 
For a DC input, safety is ensured by an external fuse. 
Select an external fuse that meets the following conditions.
S8VK-G240

@@

: 350 VDC min, 8 A

S8VK-G480

@@

: 350 VDC min, 12 A

*11.

Clamp filter “ZCAT2035-0930” manufactured by TDK Corporation. or equivalent should be installed in the cable connected to the input - output terminals of S8VK-G series. 
Noise filter “FN2080-10-06” manufactured by SCHAFFNER Corporation. or equivalent should be connected to the Input terminals of S8VK-G series.

*12.

At 

40 to 

25°C, time will be required before the rated output voltage is output after the input voltage is input.

Also, the ripple noise value may exceed the value shown in the above table.

Power rating

240 W

480 W

Item

Output voltage

24 V

48 V

24 V

48 V

Efficiency

230 VAC input 

*

6

92% typ.

93% typ.

Input

Voltage range 

*

1

Single-phase, 85 to 264 VAC, 90 to 350 VDC 

*

10 

Frequency 

*

1

50/60 Hz (47 to 63 Hz)

Current 

115 VAC input 

*

6

2.4 A typ. 

4.7 A typ. 

230 VAC input 

*

6

1.3 A typ. 

2.3 A typ. 

Power factor

230 VAC input, 100% load

0.9 min.

0.97 min.

Leakage current 

115 VAC input

0.23 mA typ.

0.3 mA typ.

230 VAC input

0.33 mA typ.

0.49 mA typ.

Inrush current 

*

2 (for a 

cold start at 25

°

C)

115 VAC input

16 A typ. 

16 A typ. 

230 VAC input

32 A typ. 

32 A typ. 

Output

Rated output current

10 A 

5 A 

20 A 

10 A 

Boost current

12 A 

6 A 

24 A 

12 A 

Voltage adjustment range 

*

3

10% to 15% (with V.ADJ) (guaranteed)

Ripple & Noise 
voltage 

*

4

100 to 240 VAC input, 
100% load 

*

6

180 mVp-p max. 
at 20 MHz of bandwidth

350 mVp-p max. 
at 20 MHz of bandwidth

230 mVp-p max. 
at 20 MHz of bandwidth

470 mVp-p max. 
at 20 MHz of bandwidth

Input variation influence 

*

8

0.4% max.

0.4% max.

Load variation influence 

*

7

0.8% max.

0.8% max.

Temperature variation influence 115 to 230 VAC input

0.05%/°C max.

0.05%/°C max.

Start up time 

*

2

115 VAC input 

*

6

250 ms typ. 

290 ms typ. 

380 ms typ. 

230 VAC input 

*

6

250 ms typ. 

290 ms typ. 

260 ms typ. 

Hold time 

*

2

115 VAC input 

*

6

44 ms typ. 

43 ms typ. 

40 ms typ. 

230 VAC input 

*

6

44 ms typ. 

50 ms typ. 

Additional 
functions

Overload protection

Yes, automatic reset

Yes, automatic reset

Overvoltage protection 

*

5

Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and turn on the input again)

Series operation

Yes (For up to two Power Supplies, external diodes are required.)

Parallel operation

Yes (Refer to 

Safety Precautions

) (For up to two Power Supplies)

Output indicator

Yes (LED: Green), lighting from 80% to 90% or more of rated voltage

Insulation

Withstand voltage

3.0 kVAC for 1 min. (between all input terminals and output terminals), current cutoff 20 mA

2.0 kVAC for 1 min. (between all input terminals and PE terminals), current cutoff 20 mA

1.0 kVAC for 1 min. (between all output terminals and PE terminals), current cutoff 20 mA

Insulation resistance

100 M

Ω

 min. (between all output terminals and all input terminals/PE terminals) at 500 VDC

Environment

Ambient operating temperature

 *1

2

40 to 70 °C (Derating is required according to the temperature. Refer to 

Engineering Data

) (with no condensation or icing)

Storage temperature

40 to 85°C (with no condensation or icing)

Ambient operating humidity

0% to 95% (Storage humidity: 0% to 95%)

Vibration resistance

10 to 55 Hz, 0.375 mm half amplitude for 2 h each in X, Y, and Z directions

Shock resistance

150 m/s

2

, 3 times each in ±X, ±Y, ±Z directions

Reliability

MTBF 

135,000 hrs min.

Life expectancy

 *9

10 years min.

Construction

Weight

900 g max.

1,500 g max.

Cooling fan

No

Degree of protection

IP20 by EN/IEC 60529 

Standards

Harmonic current emissions

Conforms to EN 61000-3-2

EMI

Conducted Emissions

Conforms to EN 61204-3 Class B, EN 55011 Class B

Radiated Emissions

Conforms to EN 61204-3 Class B, EN 55011 Class B

EMS

Conforms to EN 61204-3 high severity levels

Approved Standards

UL Listed: UL 508 (Listing)
UL UR: UL 60950-1 (Recognition)
cUL: CSA C22.2 No.107.1
cUR: CSA C22.2 No.60950-1
EN/VDE: EN 50178, EN 60950-1
ANSI/ISA 12.12.01

Conformed Standards

PELV (EN 60204-1, EN 50178)

EN 61558-2-16

Marine Standards

Lloyd’s register 

*

10 

*

11

SEMI

Conforms to F47-0706 (200 to 240 VAC input)

Summary of Contents for S82Y-VK10S

Page 1: ...Wide operation temperature range 40 to 70 C Power Boost function at 120 Safety standards UL508 60950 1 CSA C22 2 No 107 1 60950 1 EN50178 EN60950 1 Lloyd s standards EN60204 1 PELV Safety of Power Tr...

Page 2: ...3 6 A S8VK G01505 12 V 1 2 A 1 44 A S8VK G01512 24 V 0 65 A 0 78 A S8VK G01524 30 W 5 V 5 A 6 A S8VK G03005 12 V 2 5 A 3 A S8VK G03012 24 V 1 3 A 1 56 A S8VK G03024 60 W 12 V 4 5 A 5 4 A S8VK G06012...

Page 3: ...0 65 A 5 A 2 5 A 1 3 A Boost current 3 6 A 1 44 A 0 78 A 6 A 3 A 1 56 A Voltage adjustment range 3 10 to 15 with V ADJ guaranteed Ripple Noise voltage 4 100 to 240 VAC input 100 load 6 60 mVp p max a...

Page 4: ...32 A typ 32 A typ Output Rated output current 4 5 A 2 5 A 5 A Boost current 5 4 A 3 A 6 A Voltage adjustment range 3 10 to 15 with V ADJ guaranteed Ripple Noise voltage 4 100 to 240 VAC input 100 load...

Page 5: ...2 A typ 32 A typ Output Rated output current 10 A 5 A 20 A 10 A Boost current 12 A 6 A 24 A 12 A Voltage adjustment range 3 10 to 15 with V ADJ guaranteed Ripple Noise voltage 4 100 to 240 VAC input 1...

Page 6: ...hotocoupler Rectifier smoothing circuit AC L INPUT AC N Drive control circuit Fuse 250 VAC 4 0 A HBC Overvoltage detection circuit Noise filter Inrush current protection Rectifier Smoothing circuit Ov...

Page 7: ...t Harmonic current suppression circuit Power factor improvement Drive control circuit Rectifier smoothing circuit Voltage detection circuit Overvoltage detection circuit V V V V V DC OUTPUT Overcurren...

Page 8: ...K G015 S8VK G030 S8VK G060 120 W Models 240 W Models 480 W Models S8VK G12024 S8VK G240 S8VK G480 No Name Function 1 Input terminals L N Connect the input lines to these terminals 1 2 Protective Earth...

Page 9: ...s than 90 VAC the derating is 2 5 V 2 For a DC power input reduce the load given in the above derating curve by multiplying the following coefficients S8VK G12024 0 9 3 This is the guaranteed value fo...

Page 10: ...excessive voltage even if the feedback circuit in the Power Supply fails If an excessive voltage that is approximately 130 of the rated voltage or more is output the output voltage is shut OFF Reset t...

Page 11: ...rcuit breaker should be connected on N input line like the following Reference Value Reliability MTBF Value Single phase model 15 W 600 000 hrs 30 W 580 000 hrs 60 W 590 000 hrs 120 W 450 000 hrs 240...

Page 12: ...22 5 1 Rail Stopper 86 75 4 90 1 4 7 Sliding 10 max 90 1 S8VK G015 15 W 5 1 3 5 7 62 16 32 1 Rail Stopper 86 75 4 90 1 4 7 Sliding 10 max 90 1 S8VK G030 30 W 110 1 106 5 7 62 16 32 1 Rail Stopper 75 4...

Page 13: ...8 Rail Stopper 4 7 Sliding 7 5 max S8VK G12024 120 W 1 140 145 6 10 4 6 35 6 35 19 8 Rail Stopper 150 1 4 7 Sliding 7 5max 104 6 60 1 125 1 S8VK G240 240 W 10 4 140 145 6 1 6 35 6 35 30 25 19 8 Rail...

Page 14: ...f there is a possibility that the Unit will be subject to vibration or shock use a steel DIN Rail Otherwise metallic filings may result from aluminum abrasion 4 5 15 25 25 10 10 1 000 500 25 25 15 5 3...

Page 15: ...r 30 and 60 W models S82Y VS10S Side mounting bracket for 120 W models S82Y VK10S Side mounting bracket for 240 W models S82Y VK20S Type Model Dimensions Appearance Front mounting bracket For 15 30 an...

Page 16: ...bracket For 120 W models S82Y VK10S Side mounting bracket For 240 W models S82Y VK20S 35 64 t 2 0 80 60 0 1 55 0 1 13 4 5 dia 0 1 Left side mounting Right side mounting 140 0 1 50 0 1 15 5 0 1 150 12...

Page 17: ...r Do not allow any pieces of metal or conductors or any clippings or cuttings resulting from installation work to enter the Product CAUTION Indicates a potentially hazardous situation which if not avo...

Page 18: ...0 5 to 2 5 mm2 AWG14 to 12 2 5 to 4 mm2 2 5 to 4 mm2 8 to 10 mm S8VK G01512 AWG22 to 12 0 35 to 4 mm2 0 35 to 2 5 mm2 S8VK G01524 AWG24 to 12 0 25 to 4 mm2 0 25 to 2 5 mm2 S8VK G03005 AWG24 to 12 0 2...

Page 19: ...ng horizontally always place the side with the label facing upward DIN Rail Mounting To mount the Block on a DIN Rail hook portion A of the Block onto the rail and press the Block in direction B To di...

Page 20: ...5 to 40 C 2 Up to two of the same model can be connected in parallel 3 Adjust the output voltage difference of each Power Supply to 50 mV or less using the output voltage adjuster V ADJ 4 There is no...

Page 21: ...unt of surge voltage such as a lightening surge occurs while turning ON the power supply In case there is no output voltage please check the following points before contacting us Checking overload pro...

Page 22: ...nents to achieve the original product functions and performance However the influence of the ambient temperature on aluminum electrolytic capacitors is large and the service life is reduced by half fo...

Page 23: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 24: ...omron com Kyoto JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 65 6835 2711 OMRON CHINA CO LTD Room 2211 Bank of Ch...