BU
75
RW/BU
100
RW/BU
200
RW/BU
300
RW
3
29
●
Connection capacity/battery level meter
In Commercial Power Mode (normal operation), the power consumption of devices connected to the
capacity/battery level meter is displayed as a percentage.
BU75RW: Displayed in 3 levels, with 100% indicating 750VA/600W.
BU100RW: Displayed in 3 levels, with 100% indicating 1000VA/800W.
BU200RW: Displayed in 3 levels, with 100% indicating 2000VA/1600W (when 30A plug or power switchboard
is connected), 1600VA/1280W (when 20A plug is connected), or 1100VA/880W (when 15A plug is
connected).
BU300RW: Displayed in 3 levels, with 100% indicating 3000VA/2400W (when power switchboard is
connected), 2400VA/1920W (when 30A plug is connected), 1600VA/1280W (when 20A plug is
connected), or 1100VA/880W (when 15A plug is connected).
When the connection capacity is 30% or less, the level meter turns OFF.
In Battery Mode, the battery level is displayed as a percentage.
Connection
capacity
Battery level
●
Operation during recovery from a power failure
• The unit automatically resumes output via commercial power if it recovers from a pow er
failure/input power supply error while it is providing power supply output. The spent battery
starts charging.
• If a power failure or abnormal power input is resolved after the battery is discharged completely
and power output is stopped, the UPS restarts automatically and resumes power output. The
expended battery begins to charge.
See also
Setting switch can be used to select whether or not auto restart is performed.
→
Page
35
●
Stop procedure
Operation
Turn ON the power switch of the UPS.
• The power output from the UPS stops.
• Even if you turn off the power switch, if AC is supplied from commercial power, the battery is
automatically charged.
* In Commercial Power Mode (normal operation), the battery level is displayed when the beeper
stop/test switch is pressed.
(Please note that if the button is pressed and held for 5 seconds or more, the beeper begins to
sound and the self-diagnostic test starts.)
Status
indicator
Battery
replacement
Beep
Output
Charging
Description
None
OFF
ON
There is AC input
Power switch "OFF"
In Commercial Power Mode
Connection capacity
Indicator is ON
Indicator is ON In Bat-
tery Mode Battery level
Indicator blinks
90% lamp
60% lamp
30% lamp
All OFF
90% or more
60% or more
30% or more
30% or less
60% or more
30 to 60%
0 to 30%
—