(4) Run the wires to be connected through the hole in the included terminal block cover (with cable
clamp and cable guard tube).
(See Figure 1.)
Connect the ground wire to the G terminal.
Use a Phillips screwdriver to remove the terminal block screws, and connect the wire attached to the
round pressure terminal. (See Figure 2.)
Refer to Table 1 for round pressure terminal sizes.
Figure 1
Table 1
Diameter of screw
M5 Screw
Tightening torque
2 Nm(17.7 lb-in)
(5) Cover the terminal block with terminal block cover (with cable clamp) , and fasten the
previously removed screws to the two locations on the upper side of the cover.
Tighten the cable clamp dial to stabilize the wire. (See Figure 3.)
Figure 2
Figure 3
(2) When using the included UPS monitoring software and the Windows standard UPS service, use a con-
nection cable to connect the unit to the PC.
See also "7. Using the UPS monitoring software and Contact Signal" on page 66.
* If you do not use the UPS monitoring software and Contact Signal, this step is not required.
Make sure to connect the AC input plug of the unit into a wall outlet
(commercial power) with rated input voltage (200 to 240V AC).
●
Connecting to a wall outlet (commercial power) of a different rated input voltage may
result in fi re.
●
The unit may fail.
S’assurer de brancher la fi che d’entrée AC de l’appareil à une prise
murale (alimentation secteur) avec une tension nominale d’entrée (200 à
240V AC).
●
Le branchement à une prise murale (alimentation secteur) d’une tension d’entrée nominale
différente peut entraîner un incendie.
●
L’appareil peut tomber en panne.
Caution
Attention
(3) When the installation and connection is complete, connect the AC Input Plug of the UPS to a wall outlet
(commercial power).