A. Specifi cations
Frequency
50/60Hz
(
4Hz
Maximum
current
7.4A
17.6A
Phase
Single-phase, two-wire
Input plug shape
NEMAL6-15P
NEMAL6-20P
Input protection
Reset-type overcurrent protection device
Input protection capacity
10A
20A
Output
Allowable connection capacity *1 1000VA/700W
3000VA/2100W
Voltage (effective value) *2
Peak voltage value
200V mode: AC282V
(
6% 220V mode: AC310V
(
6%
(In Commercial Power Mode)
230V mode: AC324V
± 6% 240V mode: AC338V ± 6%
Peak voltage value
200V mode: AC282V ± 6% 220V mode: 6%/-10%
(In Battery Mode)
230V mode: 6%/-10% 240V mode: 6%/-12%
Frequency
50/60Hz
(
1Hz
Phase
Single-phase, two-wire
Output waveform
Sine wave
Waveform distortion rate
200V mode: 6% max. 220V mode: 10% max.
3FDUJmFEMPBEBUSBUFEPVUQVU
7NPEFNBY7NPEFNBY
Number of output receptacles
IEC60320 C13: 3 pcs.
IEC60320 C19: 1 pcs. C13 : 5 pcs.
Terminal block: 2 lines
Terminal block: 2 lines
Power failure switching time
Uninterrupted
Commercial direct shipment (switching time) 4msec.
max.
Backup time *3
Minimum 5 minutes
Battery
Type
Compact sealed lead battery
Sealed lead battery life expectancy
UPZFBST MPOHPQFSBUJOHMJGF"UBNCJFOUUFNQFSBUVSFPG$
Battery capacity (V/Ah) (x Quantity)
12V DC/ 7.2 Ah (x 3)
12V DC/ 9 Ah (x 6)
Charging time
8 hours *4
Environment
Operating ambient temperature
UP$ EVSJOHPQFSBUJPOUP$ EVSJOHTUPSBHF
Operating ambient humidity
25 to 85%RH (during use)/10 to 90%RH (during storage)
Dimensions
(W
×H×Dmm)
145 x 395 x 224 (
(
1) mm *5
213 x 537 x 432 (
(
1) mm *6
Weight of unit
Approx. 15.5 kg
Approx. 35 kg
Internal power
consumption (max.)
50W (100W max.)
55W (155W max.) *7
Noise regulation
(compliance standard)
VCCI Class A
Safety standards /
RoHS directive compliance
UL1778 / CE / RoHS compliance
Noise
50 dB max.
55 dB max.
BU1002SW
BU3002SW
Type
200V mode AC200V
(
3%
220V mode AC220V
(
3%
230V mode AC230V
(
3%
240V mode AC240V
(
3%
Method Operation
method
Full-time inverter supply method
Connectable devices
PC, display, and peripherals
Input
Rated input voltage
200/220/230/240 VAC
Input voltage range
AC145
(
4 to 276
(
4V (with 85% or less connection load)
AC170
(
4 to 276
(
4V (with 85% or more connection load)
*1: Make sure that both the VA value and the W value of the load capacity connected to the UPS are within the range specifi ed here.
*2: Check the operation beforehand if the unit is used in any mode other than “200V AC mode”. In some cases, the maximum voltage
of output in Battery Mode may be lower than the maximum voltage in usual operation (commercial power supply).
*3: The backup times shown here are for when rated load is connected, at 20
°
C, and for initial characteristics.
*4: When an additional battery unit is connected, the charging time is 24 hours.
*5: The height includes the 13mm height of the rubber feet.
*6: The height includes the 56mm height of the casters.
*7: 170W max when and additional battery unit is connected.