![Omron NYM12W-C100 User Manual Download Page 90](http://html1.mh-extra.com/html/omron/nym12w-c100/nym12w-c100_user-manual_743128090.webp)
Hardware Arrangement
The coils and contacts in electromagnetic contacts and relays in an external circuit are sources of
noise. Do not install them close to the Monitor. Locate them at least 100 mm away from the Monitor.
Example of Arrangement in Panel
AC I/O
device
Terminal block
DC I/O
device
OMRON
product
Wire Layout for the Power Supply
Observe the following points when wiring the power supply system.
• Separate the Monitor power supply from the I/O device power supply and install a noise filter near
the Monitor power supply feed section.
• Use an isolating transformer to significantly reduce noise between the Monitor and the ground. In-
stall the isolating transformer between the Monitor power supply and the noise filter, and do not
ground the secondary coil of the transformer.
• Keep the wiring between the transformer and the Monitor as short as possible, twist the wires well,
and keep the wiring separate from high-voltage and power lines.
Unit power supply for Omron product
I/O power supply for Omron product
Power Supply System Diagram
Power circuits
Power supply for general operations circuits
Outlet (for peripheral devices)
I/O power supply for Omron product
Noise
filter
5 Installation
5 - 10
NY-series Industrial Monitor User's Manual (W554)
Summary of Contents for NYM12W-C100
Page 7: ...Index CONTENTS 5 NY series Industrial Monitor User s Manual W554 ...
Page 8: ...CONTENTS 6 NY series Industrial Monitor User s Manual W554 ...
Page 28: ...Revision History 26 NY series Industrial Monitor User s Manual W554 ...
Page 30: ...Sections in this Manual 28 NY series Industrial Monitor User s Manual W554 ...
Page 38: ...1 Overview 1 8 NY series Industrial Monitor User s Manual W554 ...
Page 52: ...2 Hardware 2 14 NY series Industrial Monitor User s Manual W554 ...
Page 114: ...6 Operating Procedures 6 6 NY series Industrial Monitor User s Manual W554 ...
Page 127: ...I Index I 1 NY series Industrial Monitor User s Manual W554 I ...
Page 129: ......