• Communications lines and power lines
• DC signals and AC signals
• High-frequency devices (such as Inverters) and signal lines (communications)
l
Wiring
Observe the following points when wiring power supply and signal cables.
• When routing signal cables with differing characteristics through the same duct, always keep
them separated.
• As much as possible, avoid routing multiple power supply lines through the same duct.
If it cannot be avoided, then construct a partition between them in the duct and ground the parti-
tion.
Partitioning Methods for Signal and Power Supply Cables
(a)
(b)
(c)
(d)
Signal cables
Signal cables
Signal cables
Power supply cables
Power
supply
cables
Power supply cables
Partition
Signal
cables
(group A)
Signal
cables
(group B)
Signal
cables
(group C)
• To avoid overheating the conduits when using conduits for wiring, do not place wires for a single
circuit in separate conduits.
Parallel Wiring (Single Phase)
Correct
Correct
Power supply
Incorrect
Power supply
Power supply
Load
Load
Load
Conduits
Conduits
Conduits
OK
OK
NG
• Power cables and signal cables adversely affect each other. Do not wire them in parallel.
5 Installation and Wiring
5-89
NX-series NX1P2 CPU Unit Hardware User’s Manual (W578)
5-5 Control Panel Installation
5
5-5-5
Electrical Environment
Summary of Contents for NX1P2 series
Page 8: ...Manual Structure 6 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Page 52: ...Revision History 50 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Page 82: ...2 System Configuration 2 10 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Page 258: ...Appendices A 10 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Page 259: ...I Index I 1 NX series NX1P2 CPU Unit Hardware User s Manual W578 I...
Page 262: ...Index I 4 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Page 263: ......