Terminal Block Wiring
l
Wire and Ferrule
Attach a ferrule to a wire, or use a solid wire.
Do not connect bare stranded wires directly to terminals.
The recommended solid wire specification and ferrule are given below.
Recommended solid wire
Wire type
Wire size
Solid Wire
0.2 mm
2
to 0.5 mm
2
(AWG24 to AWG20)
Recommended ferrule
Manufacturer
Model
Applicable wire
Phoenix Contact
AI0,25-12
0.2 mm
2
(AWG24)
l
Terminal Wiring
Release button
2-conductor shielded
twisted-pair cable
• To make the connection, insert the ferrule into the terminal hole on the terminal block. Insert the
ferrule until it is locked inside.
• To disconnect the wiring, press the release button in with a small flat-blade screwdriver and pull
the line out while the lock is released.
The screwdriver shown below is recommended for wiring.
Recommended screwdriver model
Model
Manufacturer
SZS 0,4×2,5
SZF 0-0,4×2,5
Phoenix Contact
ESD 0.40×2.5
Wera
0,4×2,5×75 302
Wiha
AEF.2,5×75
Facom
210-719
Wago
SDI 0.4×2.5×75
Weidmuller
*1.
You can purchase the SZF 0-0,4×2,5 screwdriver (manufactured by Phoenix Contact) from OMRON by specifying the
OMRON's model number (XW4Z-00B).
5 Installation and Wiring
5-79
NX-series NX1P2 CPU Unit Hardware User’s Manual (W578)
5-4 W
iring
5
5-4-12
Wiring the Analog I/O Option Board
Summary of Contents for NX1P2 series
Page 8: ...Manual Structure 6 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Page 52: ...Revision History 50 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Page 82: ...2 System Configuration 2 10 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Page 258: ...Appendices A 10 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Page 259: ...I Index I 1 NX series NX1P2 CPU Unit Hardware User s Manual W578 I...
Page 262: ...Index I 4 NX series NX1P2 CPU Unit Hardware User s Manual W578...
Page 263: ......