53
4.
Settings needed to measure electricity
4.2 Circuit settings (continued)
3
Set the CT primary current for the circuits enabled from B to D
(Ex.: set the CT primary current for circuit C to 50A)
1
From the circuit C setting item, press the [
][
] keys to move to "CT primary current (MENU C4)".
2
Press the [ENTER] key to enter the setting mode.
3
Press the [
][
] keys to change the value to "50".
– Press the [MODE• ] key to move one place to the left.
– If you press the [MODE• ] key on the end at the left, the cursor moves to the right end.
4
Press the [ENTER] key to confirm your selection.
4
Set pulse output ON or OFF (MENU C6) (Ex.: set circuit C to ON)
1
From the circuit C setting item, press the [
][
] keys to move to "Pulse output ON/OFF (MENU C6)".
2
Press the [ENTER] key to enter the setting mode.
3
Press the [
][
] keys to select "ON".
4
Press the [ENTER] key to confirm your selection.
The menu numbers to assign the pulse output terminals of circuits B-D are B6 for circuit B, C6 for circuit C, and D6 for
circuit D.
Caution
• The phase and wire type is set in circuit A. The phase and wire type set for circuit A is shown in the circuit B to D
setting items (MENU B1, C1, and D1) and cannot be changed.
• Depending on the phase and wire type set for circuit A, there will be circuits that are unavailable for use.
The setting items for circuits unavailable for use will not be displayed.
• You need to set the current for the CT secondary side and CT primary side for each circuit.Confirm the rated values for the CT
you are using and set correctly.
1
2
3
4
1
2
3
4