50
4.
Settings needed to measure electricity
4.2 Circuit settings (continued)
3
Setting up the communication address (Ex.: set to 15)
1
On the setup items of circuit A, press [
] or [
] key to move to the "Communication address (MENU A2)."
2
Press the [ENTER] key to enter the setup mode. The ones place of the main display blinks.
3
Press the [
] or [
] key to change the numerical value to "15."
– By pressing the [MODE• ] key, the cursor moves left by one digit.
– By pressing the [MODE• ] key at the leftmost digit, the cursor moves to the rightmost digit.
4
Press the [ENTER] key to determine the settings.
*1. The communication address settings are assigned to circuit A. When multi-address is used, the values on the table
below are assigned automatically.
*2. The communication addresses of circuits B-D cannot be set up individually.
4
Set the CT secondary side current (Ex.: set to 1A)
1
From the circuit A setting item, press the [
][
] keys to move to "CT secondary current (MENU A3)".
2
Press the [ENTER] key to enter the setting mode. The setting value in the main display flashes.
3
Press the [
][
] keys to select "1A".
4
Press the [ENTER] key to confirm your selection.
5
Set the CT primary side current (Ex.: set to 50A)
1
From the circuit A setting item, press the [
][
] keys to move to "CT primary current (MENU A4)".
2
Press the [ENTER] key to enter the setting mode.
3
Press the [
][
] keys to change the value to "50".
– Press the [MODE• ] key to move one place to the left.
– If you press the [MODE• ] key on the end at the left, the cursor moves to the right end.
4
Press the [ENTER] key to confirm your change.
1
2
3
4
1
2
3
4
1
2
3
4