Model KM1/KE1 combination list
A-13
Appendix
Setting item
Initial value
Setting range
PMU1A
(Electric
power)
PMU2A
(Power
two-system)
EMU8A
(Pulse/
temperature)
CTD8E
(CT
expansion)
Over voltage alarm threshold for measuring
block 2
528.0 V
0.0~12100.0 V
×
c
× ×
Over voltage alarm hysteresis for measuring
block 2
24.0 V
0.0~2200.0 V
×
c
× ×
Over voltage alarm on-delay for measuring
block 2
0.1 s
0.1~10.0 s
×
c
× ×
Under voltage alarm threshold for measuring
block 2
85.0 V
0.0~12100.0 V
×
c
× ×
Under voltage alarm hysteresis for measuring
block 2
24.0 V
0.0~2200.0 V
×
c
× ×
Under voltage alarm on-delay for measuring
block 2
0.1 s
0.1~10.0 s
×
c
× ×
Power factor alarm threshold for measuring
block 1
0.00
-1.00~1.00
c
c
×
c
Power factor alarm hysteresis for measuring
block 1
0.05 0.00~1.00
c
c
×
c
Power factor alarm on-delay for measuring
block 1
0.5 s
0.5~10.0 s
c
c
×
c
Power factor alarm threshold for measuring
block 2
0.00 -1.00~1.00
×
c
×
c
Power factor alarm hysteresis for measuring
block 2
0.05 0.00~1.00
×
c
×
c
Power factor alarm on-delay for measuring
block 2
0.5 s
0.5~10.0 s
×
c
×
c
Reactive power upper limit alarm threshold
for measuring block 1
1000 var
-120000000~120000000 var
c
c
×
c
Reactive power upper limit alarm hysteresis
for measuring block 1
100 var
0.0~24000000 var
c
c
×
c
Reactive power upper limit alarm on-delay for
measuring block 1
0.5 s
0.5~10.0 s
c
c
×
c
Reactive power lower limit alarm threshold for
measuring block 1
300 var
-120000000~20000000 var
c
c
×
c
Reactive power lower limit alarm hysteresis
for measuring block 1
100 var
0.0~24000000 var
c
c
×
c
Reactive power lower limit alarm on-delay for
measuring block 1
0.5 s
0.5~10.0 s
c
c
×
c
Reactive power upper limit alarm threshold
for measuring block 2
1000 var
-120000000~120000000 var
×
c
×
c
Reactive power upper limit alarm hysteresis
for measuring block 2
100 var
0~24000000 var
×
c
×
c
Reactive power upper limit alarm on-delay for
measuring block 2
0.5 s
0.5~10.0 s
×
c
×
c
Reactive power lower limit alarm threshold for
measuring block 2
300 var
-120000000~120000000 var
×
c
×
c
Reactive power lower limit alarm hysteresis
for measuring block 2
100 var
0~24000000 var
×
c
×
c
Reactive power lower limit alarm on-delay for
measuring block 2
0.5 s
0.5~10.0 s
×
c
×
c
Upper-limit temperature alarm threshold
80.0
-50.0~100.0
×
×
○
×
Upper-limit temperature alarm hysteresis
5.0
0.0~10.0
×
×
○
×
Upper-limit temperature alarm on-delay
0.5 s
0.5~10.0 s
×
×
○
×
Lower-limit temperature alarm threshold
0.0
-50.0~100.0
×
×
○
×
Lower-limit temperature alarm hysteresis
5.0
0.0~10.0
×
×
○
×
Lower-limit temperature alarm on-delay
0.5 s
0.5~10.0 s
×
×
○
×
Active input setting
H’000000FF
0bit: Input 1
1bit: Input 2
2bit: Input 3
3bit: Input 4
4bit: Input 5
5bit: Input 6
6bit: Input 7
7bit: Input 8
c
c
c
c
Unit no.
01
0~99
c
c
c
c
Communication speed
0: 9.6 kbps
0: 9.6 kbps
1: 19.2 kbps
2: 38.4 kbps
c
c
c
×
Data bit length
0: 7 bits
0: 7 bits
1: 8 bits
c
c
c
×
Stop bit length
1: 2 bits
0: 1 bit
1: 2 bits
c
c
c
×
Vertical parity
1: Even
0: No
1: Even
2: Odd
c
c
c
×
Transmission wait time
20 ms
0 to 99 ms
c
c
c
×
Connection configuration
H’00000000
(Not
connected)
0 bit: Slave ID 1 connected/not
connected
1 bit: Slave ID 2 connected/not
connected
2 bit: Slave ID 3 connected/not
connected
3 bit: Slave ID 4 connected/not
connected
4 bit: Slave ID 5 connected/not
connected
5 bit: Slave ID 6 connected/not
connected
c
c
× ×