background image

K8DT-AS

6

Operation Methods

Setting Ranges and Wiring Connections

Connections

Input

Connect the input between the I1-COM, I2-COM, or I3-COM terminals, according to the input 
current. Malfunctions may occur if the input is connected to unused terminals and the Unit will not 
operate correctly.
For the K8DT-AS3, the I1 terminal is not used. For the K8DT-AS2, the I3 terminal is not used.
If using the OMRON K8AC-CT200L CT, connect to terminals k and l on the K8AC-CT200L. 
(Terminals kt and lt are not used.)

Power Supply

Connect the power supply to terminals A1 and A2.

Outputs

For a relay output, the 

SPDT

 contacts are output on terminals 11, 12, and 14. For a transistor output, 

the NPN output is on terminals 11 and 14.
Do not use the transistor output for control applications. It is designed only to output a signal when 
an error is detected.

DIP Switch Settings

The reset method, drive output method, and operating mode are set using the DIP switch located on 
the front of the Unit.
For the K8DT-AS

@

, SW1 is not used.

Note:

Open the DIP switch cover to set the DIP switch.
Keep the DIP switch cover closed while the power supply to the Relay is ON.

Model

Setting range

Input type

Wiring 

connections

K8DT-AS1

2 to 20 mA AC/DC

Direct input

I1-COM

10 to 100 mA AC/DC

Direct input

I2-COM

50 to 500 mA AC/DC

Direct input

I3-COM

K8DT-AS2

0.1 to 1 A AC/DC

Direct input or 
commercially available 
CT

I1-COM

0.5 to 5 A AC/DC

I2-COM

K8DT-AS3

10 to 100 A AC 

*

OMRON CT

I2-COM

20 to 200 A AC 

*

OMRON CT

I3-COM

Note:

The DC input terminals have no polarity.

*

The K8DT-AS3 is designed to be used in 
combination with the OMRON K8AC-CT200L 
Current Transformer (CT). (Direct input is not 
possible.)

Single-phase power

K8DT-AS3

K8AC-
CT200L

Current input

or

C (COM)

A1

A2

I1

I2

I3

Load

Power supply

voltage

11

14

11

14

l

k

12

Contact output

Transistor output

<For K8DT-AS3>

O

N

1

2

3

4

SW3

DIP switch pins

SW2
SW1

SW4

DIP Switch Functions

Note:

All pins are set to OFF by default.

Pin

ON 

OFF 

Resetting 
method

Automatic reset

Not used.

---

---

Manual reset

---

---

Output drive 
method

Normally closed

---

---

Normally open

---

---

Operating mode

Undercurrent

---

---

Overcurrent

---

---

1

ON

OFF

2

3

4

Summary of Contents for K8DT-AS Seriesl

Page 1: ...K8DT AS2 Options Order Separately Front Cover Refer to Safety Precautions on page 10 Refer to page 9 for commonly asked questions For the most recent information on models that have been certified for...

Page 2: ...DC Approx 5 Direct input Continuous input at 120 of maximum input 1 s at 150 100 mA AC DC I2 COM 10 to 100 mA AC DC Approx 1 Direct input 500 mA AC DC I3 COM 50 to 500 mA AC DC Approx 0 2 Direct input...

Page 3: ...rules Applicable wire size 0 25 to 1 5 mm2 AWG24 to AWG16 Wire insertion force 8 N max for AWG20 wire Screwdriver insertion force 15 N max Wire stripping length 8 mm Ferrule length 8 mm Current capaci...

Page 4: ...copper wires with a rating of 75 C or an equivalent rating Inside Inside 1 Current Input AS1 2 Output C Relay Output T Transistor Output 3 Power Supply Voltage A 100 to 240 VAC D 24 VAC DC No polarit...

Page 5: ...ge Contacts 11 12 Set value Alarm indicator Lit Contacts 11 14 or transistor output Input Delay time 250 ms reference value Terminal block See note Terminal block See note Current knob SV Hysteresis k...

Page 6: ...front of the Unit For the K8DT AS SW1 is not used Note Open the DIP switch cover to set the DIP switch Keep the DIP switch cover closed while the power supply to the Relay is ON Model Setting range I...

Page 7: ...et Value SV of 50 and Overcurrent Operation Operation will be at 100 A and resetting at 90 A when the hysteresis HYS is set to 10 Operating Time The operating time is set using the operating time knob...

Page 8: ...3 1 7 1 7 9 3 76 Two M5 screw holes or two 5 5 dia holes OMRON CT K8AC CT200L Mounting Hole Dimensions Note The OMRON Current Transformer CT is designed to be used with the K8DT AS3 Use terminals k an...

Page 9: ...ely 30 A The startup current will exceed the overload capacity rating 150 for 1 s of the K8DT AS1 and K8DT AS2 and result in failure of the Relay To monitor the motor load use the K8DT AS3 Overload ca...

Page 10: ...ails monitoring and alarm outputs may fail to operate This may result in physical damage to the facilities equipment or other devices that are connected to it To reduce this risk inspect the Relay reg...

Page 11: ...pply power to the product 22 Do not install the product immediately next to heat sources 23 Perform periodic maintenance 24 Do not wire anything to the release holes 25 When you insert a flat blade sc...

Page 12: ...rom the release hole Checking Connections After the insertion pull gently on the wire to make sure that it will not come off and the wire is securely fastened to the terminal block To prevent short ci...

Page 13: ...re is basic insulation between the power supply terminals and input terminals There is basic insulation between the power supply terminals and output terminals There is basic insulation between the in...

Page 14: ...MEMO 14...

Page 15: ...CONNECTED WITH THE PRODUCTS WHETHER SUCH CLAIM IS BASED IN CONTRACT WARRANTY NEGLIGENCE OR STRICT LIABILITY Further in no event shall liability of Omron Companies exceed the individual price of the Pr...

Page 16: ...IL 60169 U S A Tel 1 847 843 7900 Fax 1 847 843 7787 Regional Headquarters OMRON EUROPE B V Wegalaan 67 69 2132 JD Hoofddorp The Netherlands Tel 31 2356 81 300 Fax 31 2356 81 388 Contact www ia omron...