J-44

Three-phase Asymmetry and Phase-sequence Phase-loss Relay 

K8AB-PA

Ordering Information

List of Models

Note: 1. Three-phase 3-wire or 4-wire and the input range are switched using a switch.

2. The power supply is shared with the rated input voltage.

Ratings and Specifications

Ratings

Three-phase Asymmetry and Phase-sequence 

Phase-loss Relay

Rated input (See note 2.)

Model

3-phase 3-wire mode

AC 200, 220, 230, 240

K8AB-PA1

3-phase 4-wire mode

AC 115, 127, 133, 138

3-phase 3-wire mode

AC 380, 400, 415, 480

K8AB-PA2

3-phase 4-wire mode

AC 220, 230, 240, 277

Rated input 
voltage

K8AB-PA1

Three-phase, three-wire mode: 200, 220, 230, 240 VAC
Three-phase, four-wire mode: 115, 127, 133, 138 VAC

K8AB-PA2

Three-phase, three-wire mode: 380, 400, 415, 480 VAC
Three-phase, four-wire mode: 220, 230, 240, 277 VAC

Asymmetry 
operation 
(ASY.)

Operating value setting 
range

Asymmetry rate: 2% to 22%

Operating value

100% operation at set value
Asymmetry operating value = Rated input voltage x Asymmetry set value [%]
The asymmetry operation will function when the difference between the highest and lowest 
voltage phases equals or exceeds the asymmetry operating value. 

Reset (HYS.)

Hysteresis

5% of operating value (fixed)

Resetting method

Automatic reset

Operating 
time (T)

Asymmetry

0.1 s to 30 s (Value when input rapidly changes from 0% to 120%.)

Phase sequence, phase loss 0.1 s max. (Value when input rapidly changes from 0% to 100%.)

Power ON lock (LOCK)

1 s or 5 s (Value when input rapidly changes from 0% to 100%. The operating time is the shortest 
at this point.)

Setting accuracy

±10% of full scale

Time error

±10% of set value (Minimum error: 50 ms)

Input frequency

45 to 65 Hz

Input impedance

100 k

 min.

Indicators

Power (PWR): Green LED, Relay output (RY): Yellow LED, Alarm outputs (ALM1/2): Red LED

Output relays

One SPDT relay (6 A at 250 VAC, resistive load) , normally closed operation (normally ON)

Summary of Contents for K8AB-PA1

Page 1: ...e power supply One SPDT output relay 6 A at 250 VAC resistive load World wide power specifications supported by one Unit switchable Relay warning status easily monitoring using LED indicator Easy wiri...

Page 2: ...g value setting range Asymmetry rate 2 to 22 Operating value 100 operation at set value Asymmetry operating value Rated input voltage x Asymmetry set value The asymmetry operation will function when t...

Page 3: ...and exposed uncharged parts 20 M at 500 V between any charged terminals i e between input output and power supply terminals Degree of protection Terminal section IP20 Rear case IP40 Case color Munsel...

Page 4: ...erating Voltage Asymmetry operation condition Highest voltage Lowest voltage Asymmetry operating voltage Asymmetry operating voltage Rated input voltage V Asymmetry set value Note The rated input volt...

Page 5: ...ng mode OFF ON 3 phase 4 wire power monitoring mode SW3 SW4 Function Default 3 phase 3 wire mode 3 phase 4 wire mode SW3 SW4 OFF OFF Rated input voltage switch K8AB PA1 200 VAC 115 VAC OFF OFF ON OFF...

Page 6: ...of the product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use this product within a board...

Page 7: ...power supplies One SPDT output relay 6 A at 250 VAC resistive load Relay warning status easily monitoring using LED indicator Easy wiring with ferrules 2 2 5 mm2 solid or 2 1 5 mm2 standard ferrules...

Page 8: ...K8AB PH1 Rated input voltage Non isolated 200 to 500 VAC 15 VA Phase sequence phase loss operating time 0 1 s max value when rated operating voltage changes quickly from 0 to 100 Relays are normally O...

Page 9: ...uncharged parts 20 M at 500 V between any charged terminals i e between input output and power supply terminals Degree of protection Terminal section IP20 Rear case IP40 Case color Munsell 5Y8 1 ivory...

Page 10: ...y operative Nomenclature Front Indicators Dimensions L1 L2 L3 L1 L3 L2 L3 L2 L1 L1 L2 L3 Relay Phase Loss Operation Phase Sequence Operation Input Load Alarm Input Output L1 L2 L3 L3 L2 L1 The power s...

Page 11: ...the product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use this product within a board wh...

Page 12: ...istive load Separate outputs possible for overvoltages and undervoltages World wide power specifications supported by one Unit switchable Relay warning status easily monitoring using LED indicator Eas...

Page 13: ...e setting range Overvoltage 30 to 25 of maximum rated input voltage Undervoltage 30 to 25 of maximum rated input voltage Note The rated input voltage is switched with a switch Operating value 100 oper...

Page 14: ...posed uncharged parts 20 M at 500 V between any charged terminals i e between input output and power supply terminals Degree of protection Terminal section IP20 Rear case IP40 Case color Munsell 5Y8 1...

Page 15: ...L1 L2 L3 N L1 L2 L3 The power supply is shared with the rated in put voltage 14 12 11 24 22 21 Over voltage alarm Load Undervoltage alarm phase loss phase se quence alarm Power indicator Relay status...

Page 16: ...itoring mode OFF ON 3 phase 4 wire power monitoring mode SW3 SW4 Function Default 3 phase 3 wire mode 3 phase 4 wire mode SW3 SW4 OFF OFF Rated input voltage switch K8AB PM1 200 VAC 115 VAC OFF OFF ON...

Page 17: ...product 3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use this product within a board whose...

Page 18: ...sible for overvoltages and undervoltages World wide power specifications supported by one Unit switchable Relay warning status easily monitoring using LED indicator Easy wiring with ferrules 2 2 5 mm2...

Page 19: ...d undervoltage Operating value setting range Overvoltage 30 to 25 of maximum rated input voltage Undervoltage 30 to 25 of maximum rated input voltage Note The rated input voltage is switched with a sw...

Page 20: ...harged parts 20 M at 500 V between any charged terminals i e between input output and power supply terminals Degree of protection Terminal section IP20 Rear case IP40 Case color Munsell 5Y8 1 ivory Ca...

Page 21: ...Over voltage alarm Under voltage alarm Load The power supply is shared with the rated in put voltage Power indicator Relay status indicator Overvoltage knob OVER Undervoltage knob UNDER Operating time...

Page 22: ...phase 4 wire power monitoring mode SW3 SW4 Function Default 3 phase 3 wire mode 3 phase 4 wire mode SW3 SW4 OFF OFF Rated input voltage switch K8AB PW1 200 VAC 115 VAC OFF OFF ON OFF 220 VAC 127 VAC...

Page 23: ...3 Do not use thinner or similar solvent for cleaning Use commercial alcohol 4 When discarding properly dispose of the product as industrial waste 5 Only use this product within a board whose structure...