K2CM
Dimensions
Note:
All units are in millimeters unless otherwise indicated.
Surface-mounting Models
Operating Procedures
■
Operation, Setting, and Indication
Based on the current value of the motor to be used, perform the setting of each item of the K2CM Motor Protective Relay.
List of Current Settings (when using a 200-VAC motor)
*
The squares (
@
) represent the symbols defined under
Model Number Legend
.
**
Use with more than the number of passes shown above is possible.
Adjust the number of passes according to the rated current of the motor.
*** The rated current is the current at full load.
**** Supply: Low-voltage 3-phase basket type inductive motor, full-load characteristics of 200 VAC, 4-pole, totally-enclosed.
Note:
When using a large-capacity or high-voltage motor whose capacity is 45 kW or more, calculate the rated current/alternating current ratio by
converting with the alternating current ratio of the external current transformer.
Type*
K2CM-
@@
LS
@
K2CM-
@@
L
@
K2CM-
@@
M
@
K2CM-
@@
H
@
Number of passes**
1
1
2
4
8
1
1
Setting
Time scale value
2 to 8
8 to 26
20 to 65
50 to 160
Current setting range (A)
2 to 8
8 to 26 4 to 13 2 to 6.5 1 to 3.25
20 to 65
50 to 160
Motor**** Rated output (kW) Rated current (A)***
0.2
1.8
0.4
2.8
0.75
4.2
1.5
7.3
2.2
10
3.7
16.1
5.5
24
7.5
32
11
45
15
61
18.5
74
22
87
30
117
37
143.0
126
80
6
60
46.5
120
11
33
55
52
11.5
4
48.5
15
Six, M3 terminal screws
33.5
33.5
36
Three, 20-dia. holes
80
±
0.5
52
±
0.5
Four, 6-dia. mounting holes or
four, M5 mounting-screw holes