I-8

Motor Protection Circuit Breaker 

J7MN

Auxiliary switches

Time/Current characteristic

J7MN-3P & J7MN-3R

J7MN-6R & J7MN-9R

Aux. Type 

Switching capacity

 Control voltage

J77MN-11F / 20F / 02F & J7MN-T(A)

Front transverse auxiliary switch with 1 
NO + 1 NC, 2 NO, 2 NC

Rated operational voltage 

Ue

24 VAC

240 VAC

Rated operational current

Ie/AC-15

3 A

2 A

Ie/AC-12 Ith

5 A

5 A

Rated operational voltage

Ue  L/R 200 ms

24 VDC

220 VDC

Rated operational current 

Ie/DC-13

1 A

0.1 A

J77MN-11S / 20S / 02S

Lateral auxiliary switch  with 1 NO + 1 
NC, 2 NO, 2 NC  & two signalling 
switches with 1 NO + 1 NC

Rated operational voltage

Ue

24 VAC

240 VAC

Rated operational current

Ie/AC-15

6 A

4 A

Ie/AC-12 Ith

10 A

Rated operational voltage

Ue  L/R 200 ms

24 VDC

220 VDC

Rated operational current

Ie/DC-13

2 A

0.25 A

J77MN-U

Undervoltage release

Power consumption

during pick-up

8.5 VA / 6 W

uninterrupted duty

3  VA / 1.2 W

Response voltage 

trip

 0.7 to 0.35  × Us (V)

pick-up

 0.85 to 1.1   × Us (V)

J77MN-S

Shunt release 

Power consumption 

during pick-up

8.5 VA / 6 W

uninterrupted duty

3 VA / 1.2 W

Response voltage 

trip

0.7 to 1.1 × Us (V)

Short-circuit protection for auxiliary and control circuits Fuse gL/gG

10 A

Miniature circuit breaker C-characteristic

6 A

Conductor cross-sections for auxiliary and control circuits 

Screw-type Pz2

solid

1 x (0.5 to 2.5) / 2x (0.5 to 2.5) mm²

flexible

1 x (0.5 to 4) / 2 x (0.75 to 2.5) mm²

solid AWG

1 x (20 to 14) / 2 x (20 to 14) AWG

flexible AWG

1 x (20 to 10) / 2 x (18 to 14) AWG

Oper

ation time

Oper

ation time

Multiple of set current × Ie

Multiple of set current × Ie

Hour

Min

ute

Second

Time

Hour

Min

ute

Second

Time

Ir=10.4, ..., 15.6 X In

Reflex tripping:
t

5 ms

Ir=10.4, ..., 15.6 X In

Reflex tripping:
t

5 ms

I

The curve shows the mean operating current at an ambient temperature of 20°C starting from cold.

II

The tripping characteristic of electromagnetic overcurrent releases (short-circuit releases)

The tripping characteristic of the inverse-time delayed overload releases apply for DC and AC with a frequency of 0 to 400 Hz.
At operating temperature, the tripping times of the thermal releases are reduced to approximately 25 %.
The characteristic shown here is a schematic representation of circuit-breakers for all ranges.
Current limiting characteristics and I²t characteristics are available on request.

Summary of Contents for J7MN -

Page 1: ...lease Shunt release Three phase busbar system Moulded plastic enclosures Door coupling rotary mechanisms Insulated Link modules Ordering Information Model Number Legend 1 Motor Protection Circuit Brea...

Page 2: ...4 22 286 15 J7MN 3P 22 26 11 18 26 338 15 J7MN 3P 26 32 15 22 32 416 15 J7MN 3P 32 0 16 0 10 0 16 2 1 100 J7MN 3R E16 0 25 0 06 0 16 0 25 3 3 100 J7MN 3R E25 0 4 0 09 0 25 0 4 5 2 100 J7MN 3R E4 0 63...

Page 3: ...24 V 50 Hz 28 V 60 Hz J77MN S 24 110 127 V 50 Hz 120 V 60 Hz J77MN S 110 220 230 V 50 Hz 240 260 V 60 Hz J77MN S 230 240 V 50 Hz 277 V 60 Hz J77MN S 240 380 400 V 50 Hz 440 460 V 60 Hz J77MN S 400 41...

Page 4: ...mm In 64 A 1 1 The sum of all added currents per module must not exeed the above mentioned nominal currents for 2 units J7MN 3P J7MN 3R 1 J75 CPM 2 45 6 for 3 units 1 J75 CPM 3 45 6 for 4 units 1 J75...

Page 5: ...3 7 5 J7KN 18 J77MN VKN 3 Not Needed J7MN 3P J7MN 3R J7KN 18 xx VKN3 Included J7KNG 18 xx D J77MN VKG 3 11 J7KN 22 J77MN VKN 3 Not Needed J7MN 3P J7MN 3R J7KN 22 xx VKN3 Included J7KNG 22 xx D J77MN...

Page 6: ...100 100 100 100 100 100 100 1 100 100 100 100 100 100 100 100 100 100 1 6 100 100 100 100 100 100 100 100 3 3 20 2 5 100 100 100 100 100 100 50 100 3 3 35 4 100 100 100 100 100 38 50 15 38 50 3 3 40 6...

Page 7: ...R per conducting path P I 3 In 26 up to 63 A 12 6 W In up to 63 A W 11 9 W In 75 up to 100 A 15 W Shock resistance acc to IEC 68 Part 2 27 25 g Degree of protection acc to IEC 60 529 IP 20 Shock hazar...

Page 8: ...ty 3 VA 1 2 W Response voltage trip 0 7 to 1 1 Us V Short circuit protection for auxiliary and control circuits Fuse gL gG 10 A Miniature circuit breaker C characteristic 6 A Conductor cross sections...

Page 9: ...0 10 10 10 10 10 10 10 kA Motor load 1 phase 115 V 1 8 1 4 1 3 1 2 1 2 1 11 2 2 2 HP 230 V 1 10 1 6 1 3 1 2 1 11 2 2 3 3 5 5 HP Motor load 3 phase 200 V 1 2 3 4 1 2 2 3 3 5 71 2 71 2 HP 230 V 1 3 1 2...

Page 10: ...AC are practically short circuit proof at this voltage as higher short circuit currents are not usually encountered at the instal lation point Back up fuses are only necessary if the short circuit cu...

Page 11: ...690 mm 30 30 30 30 50 inch 1 18 1 2 1 18 1 18 2 Height of arcing spaces clearance from earthed parts at Ue V 240 415 460 525 690 mm 50 50 50 50 50 inch 2 2 2 2 2 Height of arcing spaces clearance fro...

Page 12: ...77MN DC 1 Max for shackle diameter for padlock 8 mm In the interest of product improvement specifications are subject to change without notice ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millim...

Reviews: