I-10

Motor Protection Circuit Breaker 

J7MN

Descriptions

Releases

Circuit-breakers J7MN are equipped with bimetallic-based, inverse-
time delayed overload releases and with instantaneous overcurrent 
releases (electromagnetic short-circuit releases). The overload 
releases can be set in accordance with the load current. The over-
current releases are permanently set to a value 13 times the rated 
current and thus enable trouble-free start-up of motors. The scale 
cover can be sealed to prevent unauthorized adjustments to the set 
current.

Operating mechanisms

Circuit-breakers J7MN-3P are actuated via a rocker operating mech-
anism and circuit-breakers J7MN-3R, J7MN-6R and J7MN-9R via a 
rotary operating mechanism. An electrical signal can be output, at all 
Circuit-breakers, via a signalling switch to indicate that the Circuit-
breaker has tripped. All operating mechanisms can be locked in the 
0 position with a padlock (shackle diameter 3.5 to 4.5 mm). The 
J7MN Circuit-breakers fulfil the isolation characteristics specified in 
IEC 60947-2.

Operating conditions

Circuit-breakers J7MN are suitable for use in any climate. They are 
designed for operation in enclosed rooms under normal conditions 
(e. g. no dust, corrosive vapours or harmful gases). Suitable enclo-
sures must be provided for installation in dusty or damp rooms. Cir-
cuit-breakers J7MN can also be fed from below. In order to prevent 

premature tripping due to phase failure sensitivity, the three conduct-
ing paths must always be uniformly loaded. The conducting paths 
must be connected in series in the case of single-phase loads.

Short-circuit protection

The short-circuit releases of J7MN circuit-breakers disconnect the 
faulty load feeder from the system in the event of a short circuit and 
thus prevent any further damage from being caused. Circuit-break-
ers with a short-circuit breaking capacity of 50 kA or 100 kA at a volt-
age of 400 V AC are practically short-circuit-proof at this voltage, as 
higher short-circuit currents are not usually encountered at the instal-
lation point. Back-up fuses are only necessary if the short-circuit cur-
rent at the installation point exceeds the rated ultimate short-circuit 
breaking capacity of the circuit-breakers.

Motor protection

The tripping characteristics of J7MN circuit-breakers are designed 
mainly to protect three-phase induction motors. The circuit-breakers 
are therefore also referred to as Manual Motor Starters. The current 
of the motor to be protected is set with the aid of the scale.

Line protection

J7MN Circuit-breakers for motor protection are also suitable for line 
protection. The J7MN Circuit-breakers fulfil the isolation conditions of 
IEC 60 947-3 as well as the additional test conditions for circuit-
breakers with isolation characteristics specified in IEC 60947-2. Tak-
ing IEC 60 204-1 into consideration, they can thus be implemented 
as main and EMERGENCY STOP switches. Door-coupling rotary 
operating mechanism do not fulfil the isolation characteristics.

Wiring diagrams

J7MN-6R

J7MN-9R + J77MN-TB100

Rated operational current 

Ie

26

32

40

50

63

63

75

90

100

A

Max. short-circuit current

240 V

100

100

100

100

100

100

100

100

100 kA

480 V

50

50

50

50

50

40

40

40

40 kA

600 V

10

10

10

10

10

10

10

10

10 kA

Motor load
1-phase

115  V

2

3

3

5

5

5

7

1

/

2

10

10 HP

230 V

5

5

7

1

/

2

10

15

15

15

20

20 HP

Motor load
3-phase

230 V

10

10

15

15

20

25

25

30

40 HP

460V  

20

25

30

40

50

50

60

75

75 HP

600V

25

30

40

50

60

60

75

100

100 HP

Max. rated fuse or breaker

600

600

600

600

600 1,000 1,000 1,000 1,000 A

Combination Motor Controller Type E

Ratings of auxiliary switches and 
alarm switches

Lateral auxiliary switch with 
J77MN-xxS and signalling 
switch J77MN-T

Transversal auxiliary switch 
with J77MN-xxF

Breaking capacity

A600

A300

AC

Q300

R300

DC

Circuit breakers

Traverse Aux. Contact blocks

Aux. Contact Block (side mounted)

J7MN

J77MN-11F

J77MN-20F

J77MN-02F

J77MN-11S

J77MN-20S

J77MN-02S

Alarm Switch

Undervoltage Release

Shunt Release

J77MN-T-11S

J77MN-TA-11S

J77MN-U-...

J77MN-S-...

Summary of Contents for J7MN -

Page 1: ...lease Shunt release Three phase busbar system Moulded plastic enclosures Door coupling rotary mechanisms Insulated Link modules Ordering Information Model Number Legend 1 Motor Protection Circuit Brea...

Page 2: ...4 22 286 15 J7MN 3P 22 26 11 18 26 338 15 J7MN 3P 26 32 15 22 32 416 15 J7MN 3P 32 0 16 0 10 0 16 2 1 100 J7MN 3R E16 0 25 0 06 0 16 0 25 3 3 100 J7MN 3R E25 0 4 0 09 0 25 0 4 5 2 100 J7MN 3R E4 0 63...

Page 3: ...24 V 50 Hz 28 V 60 Hz J77MN S 24 110 127 V 50 Hz 120 V 60 Hz J77MN S 110 220 230 V 50 Hz 240 260 V 60 Hz J77MN S 230 240 V 50 Hz 277 V 60 Hz J77MN S 240 380 400 V 50 Hz 440 460 V 60 Hz J77MN S 400 41...

Page 4: ...mm In 64 A 1 1 The sum of all added currents per module must not exeed the above mentioned nominal currents for 2 units J7MN 3P J7MN 3R 1 J75 CPM 2 45 6 for 3 units 1 J75 CPM 3 45 6 for 4 units 1 J75...

Page 5: ...3 7 5 J7KN 18 J77MN VKN 3 Not Needed J7MN 3P J7MN 3R J7KN 18 xx VKN3 Included J7KNG 18 xx D J77MN VKG 3 11 J7KN 22 J77MN VKN 3 Not Needed J7MN 3P J7MN 3R J7KN 22 xx VKN3 Included J7KNG 22 xx D J77MN...

Page 6: ...100 100 100 100 100 100 100 1 100 100 100 100 100 100 100 100 100 100 1 6 100 100 100 100 100 100 100 100 3 3 20 2 5 100 100 100 100 100 100 50 100 3 3 35 4 100 100 100 100 100 38 50 15 38 50 3 3 40 6...

Page 7: ...R per conducting path P I 3 In 26 up to 63 A 12 6 W In up to 63 A W 11 9 W In 75 up to 100 A 15 W Shock resistance acc to IEC 68 Part 2 27 25 g Degree of protection acc to IEC 60 529 IP 20 Shock hazar...

Page 8: ...ty 3 VA 1 2 W Response voltage trip 0 7 to 1 1 Us V Short circuit protection for auxiliary and control circuits Fuse gL gG 10 A Miniature circuit breaker C characteristic 6 A Conductor cross sections...

Page 9: ...0 10 10 10 10 10 10 10 kA Motor load 1 phase 115 V 1 8 1 4 1 3 1 2 1 2 1 11 2 2 2 HP 230 V 1 10 1 6 1 3 1 2 1 11 2 2 3 3 5 5 HP Motor load 3 phase 200 V 1 2 3 4 1 2 2 3 3 5 71 2 71 2 HP 230 V 1 3 1 2...

Page 10: ...AC are practically short circuit proof at this voltage as higher short circuit currents are not usually encountered at the instal lation point Back up fuses are only necessary if the short circuit cu...

Page 11: ...690 mm 30 30 30 30 50 inch 1 18 1 2 1 18 1 18 2 Height of arcing spaces clearance from earthed parts at Ue V 240 415 460 525 690 mm 50 50 50 50 50 inch 2 2 2 2 2 Height of arcing spaces clearance fro...

Page 12: ...77MN DC 1 Max for shackle diameter for padlock 8 mm In the interest of product improvement specifications are subject to change without notice ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millim...

Reviews: