H8CA-S

H8CA-S

 

 

Characteristics

 

Note:

 

Operate time of output circuit is included in overall error.

 

Engineering Data

 

 

Electrical Service Life

 

Resistive Load

             Inductive Load 

 

In timer 
function mode

Repeat accuracy

±0.05% ±0.05 s

Setting error

±0.1% ±0.005 s

Variation due to 
voltage change

±0.05% ±0.05 s max.

Variation due to 
temperature change

Insulation resistance

100 m

 

 

 min at 500 VDC

Dielectric Strength

1,500 VAC 50/60 Hz for 1 minute

Vibration

Mechanical durability: 10 to 55 Hz, 0.75 mm (0.030 in) double amplitude
Malfunction durability: 10 to 55 Hz, 0.3 mm (0.012 in) double amplitude

Shock

Mechanical durability: approx. 30 G
Malfunction durability: approx. 10 G

Ambient temperature

Operating: -10° to 55° C (14° to 131° F)
Storage: -25° to 65° C (-13° to 149° F)

Humidity

35 to 85% RH

Service life

Mechanically: 10,000,000 operations min.
Electrically: See “Engineering Data”

Weight

Approx. 130 g (4.59 oz)

30 VDC (p.f. = 1)

250 VAC (p.f. = 1)

Load current (A)

0                      1                      2                     3

Switching oper

ations (x10

3

)

100

500

1000

0

30 VDC (L/R = 7 ms)

250 VAC (p.f. = 0.4)

Load current (A)

0                      1                      2                     3

Switching oper

ations (x10

3

)

100

500

1000

0

Summary of Contents for H8CA-S Series

Page 1: ...input modes and four operating modes are selectable Timer time limit operation integrating operation Four operating modes are selectable Backup power supply for memory protection Provided Approx 10 y...

Page 2: ...60 Hz DC 12 to 120 VDC 20 max permissible ripple Operating voltage range 90 to 110 of rated voltage Power consumption See Note 1 Approx 2 2 VA at 240 VAC 50 Hz Approx 1 W at 120 VDC Max counting spee...

Page 3: ...bration Mechanical durability 10 to 55 Hz 0 75 mm 0 030 in double amplitude Malfunction durability 10 to 55 Hz 0 3 mm 0 012 in double amplitude Shock Mechanical durability approx 30 G Malfunction dura...

Page 4: ...ted if the minimums for A and B are not met In Counter Function Mode In Timer Function Mode Command Input Mode A Individual Input Mode B Phase Difference Input Mode C Count input 1 Count input 2 Digit...

Page 5: ...ne when phase of count input 2 CP2 is delayed with respect to phase of count input 1 CP1 The count value is decreased by one when phase of count input 2 CP2 is ahead with respect to phase of count inp...

Page 6: ...03 13 6 0 54 78 3 07 50 1 97 45 1 77 45 1 77 50 1 97 Note Recommended panel thickness is 1 to 3 2 mm Panel cutout conforms to DIN 43700 70 max 2 76 7 8 0 31 Eleven M3 5 x 7 5 sems 50 max 1 97 3 0 12...

Page 7: ...8 0 31 91 9 3 62 Panel Adapter for panel mounting Y92F 30 P3GA 11 back connecting socket 4 5 0 18 L 15 25 25 25 25 1 0 04 27 0 15 35 0 3 7 3 0 15 10 10 L Length 1 m PFP 100N 50 cm PFP 50N 1 m PFP 100...

Page 8: ...it The function input mode or output mode display will be blinking The Power OFF display will stop blinking when power comes ON Output display Input mode display Output mode display Reset key Advance...

Page 9: ...e N will stop blinking Always disconnect terminals 1 and 3 when finished selecting the function Values cannot be preset if terminals 1 and 3 are con nected 2 Selecting the timer function with sec and...

Page 10: ...r the power supply is ON or OFF Press the key until the desired digit begins blinking Press the key to set the desired value Continue pressing the and keys until the smallest digit has been set To com...

Page 11: ...C voltage is recommended when the counter is installed at a location where the input terminals are easily accessible Note When connecting external signal input contacts and tran sistors use a power su...

Page 12: ...ol output used as shown in the table below Reset Input Connection Voltage Input Type Type of control output Max counting speed of rated time Output delay time Contact output 30 cps Common to hours min...

Page 13: ...nput 2 Counts when turned ON Input 1 Input 2 Counts when turned ON Input 2 Input 1 A count signal is input when turned ON 30 VDC max 30 VDC max Input 1 Input 2 A count signal is input when turned OFF...

Page 14: ...n a signal will be output when the new value is the same as the displayed value The front panel keys operate at a touch Do not press the keys with excessive force or tools such as a screwdriver Press...

Page 15: ...Y92F 30 adapter loosen the two screws of the adapter pry up the top and bottom hooks of the adapter and pull the H8CA S out from the front of the panel Caution The H8CA S has a built in lithium batter...

Reviews: