Separate Power Supplies for Time Switch and Load
●
Common Power Supply for Time Switch and Load
Direct control with
the Time Switch
Direct control with
the Time Switch
Using with an electromagnetic relay or contactor
If using the Switch beyond its ratings is unavoidable,
use it together with an electromagnetic switch or contactor
Single phase
Three phase
Single phase
Three phase
■
Applicable wire : 600V vinyl-insulated wire (solid wire or stranded wire, copper)
14 to 24 AWG
Up to two wires of the same size and type can be inserted
into a single terminal. Strip length : 11
±
1 mm.
■
Applicable tightening torque : 8.67 to 10.4 in.lb. (0.98 to 1.17 N·m)
■
Recommended fuse : T2A AC250V T2A, 250 VAC, time delay, low breaking
capacity