B-88
Solid-state Timer
H3YN
■
Life-test Curve (Reference Value)
5,000
1,000
500
200
5,000
1,000
500
200
5,000
1,000
500
200
5,000
1,000
500
200
5,000
1,000
500
100
60
H3YN-2/-21
H3YN-4/-41
H3YN-4-Z/-41-Z
Switching oper
ations (x 10
3
)
Load current (A)
Switching oper
ations (x 10
3
)
Load current (A)
Switching oper
ations (x 10
3
)
Load current (A)
Switching oper
ations (x 10
3
)
Load current (A)
Switching oper
ations (x 10
3
)
Load current (A)
250 VAC, resistive load
250 VAC, cos
φ
= 1
24 VDC, cos
φ
= 1
Reference: A maximum current of 0.6 A can be switched at 125 VDC (cos
φ
= 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases,
a life of 100,000 operations can be expected.
The minimum applicable load is 1 mA at 5 VDC (P reference value).
250 VAC, cos
φ
= 0.4
24 VDC, L/R = 7 ms
250 VAC, cos
φ
= 1
24 VDC, cos
φ
= 1
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cos
φ
= 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases,
a life of 100,000 operations can be expected.
The minimum applicable load is 1 mA at 1 VDC (P reference value).
250 VAC, cos
φ
= 0.4
24 VDC, L/R = 7 ms
24 VDC, re-
sistive load
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cos
φ
= 1).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases,
a life of 100,000 operations can be expected.
The minimum applicable load is 0.1 mA at 1 VDC (P reference value).