background image

3

H3JA

H3JA

Characteristics

Accuracy of operating time

–

2% max.

Setting error

–

7% max.

Influence of voltage

–

2% max.

Influence of temperature

–

5% max.

Insulation resistance

100 M

W

 min. (at 500 VDC)

Dielectric strength

2,000 VAC, 50/60 Hz for 1 min (between current-carrying and non-current-carrying parts, and be-
tween contact-carrying and control circuit, and between contacts of different poles)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)

Impulse withstand voltage

3 kV (between power terminals)
4.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)

Noise immunity

–

1.5 kV (between power terminals) and 

–

1.5 kV (between output terminals), square-wave noise 

by noise simulator (pulse width: 100 ns/1 

m

s, 1-ns rise)

Static immunity

Destruction: 8 kV
Malfunction: 6 kV

Vibration resistance

Destruction: 10 to 55 Hz with 0.75-mm double amplitude in 3 directions for 1 hour each.
Malfunction: 10 to 55 Hz with 0.5-mm double amplitude in 3 directions for 10 minutes each.

Shock resistance

Destruction: 1,000 m/s

2

Malfunction: 100 m/s

2

Ambient temperature

Operating:

–10

•

C to 55

•

C

Storage:

–25

•

C to 65

•

C

Ambient humidity

Operating: 35% 

to 

85%

Life expectancy

H3JA-8A
Mechanical: 10,000,000 operations min.
Electrical:

60,000 operations min. (7 A resistive load at 250 VAC, 360 operations/h)

H3JA-8C
Mechanical: 10,000,000 operations min.
Electrical:

100,000 operations min. (5 A resistive load at 250 VAC, 360 operations/h)

EMC

(EMI)
Emission Enclosure:

EN55011 Group 1 class A

Emission AC Mains:

EN55011 Group 1 class A

(EMS)
Immunity ESD:

EN61000-4-2: 6 kV contact discharge (level 3)

8 kV air discharge (level 3)

Immunity RF-interference from AM Radio Waves:

EN61000-4-3: 10 V/m (80 MHz to 1 GHz) (level 3)

Immunity Burst:

EN61000-4-4: 2 kV power port and output port (level 3)

1 kV control port with capacitive clamp (level 3)

Immunity Surge:

EN61000-4-5: 2 kV common mode (level 3)

1 kV differential mode (level 3)

Approved standard

UL508, CSA C22.2 No. 14, conforms to EN61812-1

Case color

Light gray (Munsell 5Y7/1)

Degree of protection

IP40 (panel surface)

Weight

H3JA-8A: Approx. 50 g
H3JA-8C: Approx. 60 g

Summary of Contents for H3JA

Page 1: ...G 08 Socket 2 Hold down Clips are sold in sets of two RC Operation resetting system Time limit contact Mounting method Rated time Model Time limit operation self resetting SPDT Surface mounting flush mounting and DIN track mounting 1 s 3 s 5 s 10 s 30 s 60 s 3 min 5 min 10 min 30 min 60 min 3 hrs H3JA 8A DPDT 1 s 3 s 5 s 10 s 30 s 60 s 3 min 5 min 10 min 30 min 60 min 3 hrs H3JA 8C Ex H3JA 8A 100 ...

Page 2: ...20 or 200 to 240 VAC 50 60 Hz 24 VDC Operating voltage range 85 to 110 of rated supply voltage Power consumption H3JA 8A 100 to 120 VAC Approx 3 VA 1 3 W at 120 VAC 200 to 240 VAC Approx 5 VA 1 5 W at 240 VAC 24 VAC Approx 1 2 VA 0 9 W at 24 VAC 24 VDC Approx 0 8 W at 24 VDC H3JA 8C 100 to 120 VAC Approx 3 VA 1 1 W at 120 VAC 200 to 240 VAC Approx 5 VA 1 3 W at 240 VAC 24 VAC Approx 1 3 VA 1 W at ...

Page 3: ...uble amplitude in 3 directions for 10 minutes each Shock resistance Destruction 1 000 m s2 Malfunction 100 m s2 Ambient temperature Operating 10 C to 55 C Storage 25 C to 65 C Ambient humidity Operating 35 to 85 Life expectancy H3JA 8A Mechanical 10 000 000 operations min Electrical 60 000 operations min 7 A resistive load at 250 VAC 360 operations h H3JA 8C Mechanical 10 000 000 operations min El...

Page 4: ...oad 120 VAC inductive load cosf 0 4 30 VDC inductive load L R 7 ms 1 000 500 100 50 0 1 2 3 4 5 6 7 5 000 Switching operations x 10 3 f H3JA 8A H3JA 8C 100 ms min Rt Set time Set time Terminals 2 7 power 6 8 NO 5 8 NC Time UP indicator Orange Power ON indicator Green 100 ms min Rt Set time Set time Terminals 2 7 power 1 3 NO 6 8 1 4 5 8 NC Time UP indicator Orange Power ON indicator Green ...

Page 5: ...ecting socket Panel Cutout Recommended panel thickness 1 to 5 mm 44 46 40 37 4 11 22 91 3 13 15 5 US08 US08 Connecting Socket Track Mounting Front Connecting Socket PF085A Mounting Holes Terminal Arrangement Top View Mounting Height of Timer with Socket Note PF085A can be used as a front connecting socket Eight M3 5 7 sems Two 4 5 dia holes Two M4 or 4 5 dia holes H3JA Hold down Clips Set of Two C...

Page 6: ...minal Cover Conforming to VDE0106 P100 Y92A 48G Attachment for P3G 08 Socket Twelve 6 4 dia holes 34 47 7 x 47 7 48 x 48 47 4 16 5 24 6 27 6 Mounting Track PFP 100N PFP 50N PFP 100N2 4 5 15 25 25 25 25 10 10 7 3 0 15 35 0 3 27 0 15 1 4 5 15 25 25 25 25 15 10 10 35 0 3 27 24 16 29 2 1 1 5 1 000 500 see note 15 5 see note Note The values shown in parentheses are for the PFP 50N 1 000 ...

Page 7: ...7 H3JA H3JA Installation Terminal Arrangement End Plate PFP M Spacer PFP S 50 11 5 M4 x 8 pan head screw 10 6 2 1 8 1 35 5 35 3 1 8 1 3 4 8 5 16 12 44 3 34 8 16 5 10 H3JA 8A H3JA 8C ...

Page 8: ...ERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No L100 E1 1A OMRON Corporation Industrial Automation Company Measuring and Supervisory Controls Department Shiokoji Horikawa Shimogyo ku Kyoto 600 8530 Japan Tel 81 75 344 7108 Fax 81 75 344 7189 Printed in Japan 0401 2M 1100 A ...