![background image](http://html.mh-extra.com/html/omron/h3de/h3de_manual_744462026.webp)
B-76
Solid-state Power OFF-delay Timer
H3DE-H
Specifications
■
General
Note:
Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm.
■
Time Ranges
Note:
The Timer will not operate if the specified power-on time is not kept. Be sure to supply power for at least the period specified.
■
Ratings
Note:
The ripple in DC power supply must be 20% max. A single-phase, full-wave rectifying power supply can be connected if the ripple output of
the power supply is a maximum of 20% of the whole output.
Item
H3DE-H
Operating mode
Power OFF-delay
Operating/Reset method
Instantaneous operation/Time-limit reset
Terminal block
Clamps Two 2.5 mm
2
max. bar terminals without sleeves
Terminal screw tightening torque
0.98 N·m max. {approx. 10 kgf·cm max.}
Output type
Relay: SPDT
Mounting method
DIN track mounting (see note)
Attachment
Nameplate
Approved standards
UL508, CSA 22.2 No.14
Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100
Output category according to IEC60947-5-1 (AC-13; 250 V 5A/AC-15; 250 V 3 A/DC-13; 30 V 0.1 A)
Time scale display
Time ranges
Min. power ON time
S series
x 0.1 s
0.1 to 1.2 s
0.1 s minimum
x 1 s
1 to 12 s
L series
x 1 s
1 to 12 s
0.3 s minimum
x 10 s
10 to 120 s
Rated supply voltage (see note)
100 to 120 VAC (50/60 Hz)
200 to 230 VAC (50/60 Hz)
24 VAC/VDC (50/60 Hz)
48 VAC/VDC (50/60 Hz)
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
24 VAC/VDC Type
AC: Approx. 0.3 VA (0.2 W) at 24 VAC
DC: Approx. 0.2 W at 24 VDC
48 VAC/VDC Type
AC: Approx. 0.5 VA (0.5 W) at 48 VAC
DC: Approx. 0.5 W at 48 VDC
100 to 120 VAC Type
AC: Approx. 0.8 VA (0.7 W) at 120 VAC
200 to 230 VAC Type
AC: Approx. 1.6 VA (1.0 W) at 230 VAC
Control output
Contact output: 5 A at 250 VAC with resistive load (cos
φ
= 1)
5 A at 30 VDC with resistive load (cos
φ
= 1)
Ambient temperature
Operating:
−
10
°
C to 55
°
C (with no icing)
Storage:
−
25
°
C to 65
°
C (with no icing)
Ambient humidity
Operating: 35% to 85%
Summary of Contents for H3DE