J-70
Solid State Relays
G3R-I/O
■
Characteristics
Input Module
Output Module
Item
G3R-IAZR1SN-UTU
G3R-IDZR1SN-UTU
G3R-IDZR1SN-1-UTU
Operate time
20 ms max.
0.1 ms max.
15 ms max.
Release time
20 ms max.
0.1 ms max.
15 ms max.
Response frequency
10 Hz
1 kHz
10 Hz
Output ON voltage drop
1.6 V max.
Leakage current
5
µ
A max.
Insulation resistance
100 M
Ω
min. between input and output
Dielectric strength
4,000 VAC, 50/60 Hz for 1 min between input and output
Vibration resistance
10 to 55 to 10 Hz, 0.75-mm single amplitude
Shock resistance
1,000 m/s
2
Ambient temperature
Operating: –30
°
C to 80
°
C (with no icing)
Storage:
–30
°
C to 100
°
C (with no icing)
Certified standards
UL508 File No. E64562
CSA C22.2 (No. 14, No. 950) File No. LR35535
TÜV File No. R9650094 (EN60950)
Ambient humidity
Operating: 45% to 85%
Weight
Approx. 18 g
Item
G3R-OA202SZN-UTU
G3R-OA202SLN-UTU
G3R-ODX02SN-UTU
G3R-OD201SN-UTU
Operate time
1/2 of load power source
cycle + 1 ms max.
1 ms max.
1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
2 ms max.
Response frequency
20 Hz
100 Hz
Output ON voltage drop
1.6 V max.
2.5 V max.
Leakage current
1.5 mA max.
1 mA max.
Insulation resistance
100 M
Ω
min. between input and output
Dielectric strength
4,000 VAC, 50/60 Hz for 1 min between input and output
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude
Shock resistance
Destruction: 1,000 m/s
2
Ambient temperature
Operating: –30
°
C to 80
°
C (with no icing)
Storage:
–30
°
C to 100
°
C (with no icing)
Certified standards
UL508 File No. E64562
CSA C22.2 (No. 14, No. 950) File No. LR35535
TÜV File No. R9650094 (EN60950)
Ambient humidity
Operating: 45% to 85%
Weight
Approx. 18 g