Connect the parallel I/O cable (FZ-VP or FZ-VPX (optional)) ensuring minimum bend radius or larger.

FZ-VP (2m, 5m, min. bending radius: 75mm)

FZ-VPX (2m, 5m, min. bending radius: 75mm)

I/O Connector

A1
A2
A3
A4

A5
A6
A7
A8
A9

A10
A11
A12
A13
A14
A15
A16
A17
A18
A19
A20
A21
A22
A23
A24
A25

B1
B2
B3
B4

B5
B6
B7
B8
B9

B10
B11
B12
B13
B14
B15
B16
B17
B18
B19
B20
B21
B22
B23
B24
B25

No.

Wire color Mark (red)

Function

Signal name

No.

COMIN
ENCTRIG_A1 (*2)
ENCTRIG_B1 (*2)
STEP1 (*2)/ 
ENCTRIG_Z1 (*2)
DSA1 (*2)
DI1
DI3
DI5
DI7
STGOUT1
STGOUT3
ERROR
COMOUT1
GATE1 (*2)
OR1 (*2)
READY1 (*2)
COMOUT2
DO1
DO3
DO5
DO7
DO9
DO11
DO13
COMOUT3

Orange
Gray
White
Yellow

Pink
Orange
Gray
White
Yellow
Pink
Orange
Gray
White
Yellow
Pink
Orange
Gray
White
Yellow
Pink
Orange
Gray
White
Yellow
Pink

Wire color Mark (blk)

Function

Signal name

Orange
Gray
White
Yellow

Pink
Orange
Gray
White
Yellow
Pink
Orange
Gray
White
Yellow
Pink
Orange
Gray
White
Yellow
Pink
Orange
Gray
White
Yellow
Pink

RESET

DSA0
DI0
DI2
DI4
DI6
STGOUT0
STGOUT2
RUN/BUSY1 (*2)
BUSY0
GATE0
OR0
READY0
DO0
DO2
DO4
DO6
DO8
DO10
DO12
DO14
DO15

Controller restart

Data send request signal
Command inputs

Strobe trigger output (*1)
Strobe trigger output (*1)
ON while in Run mode/ON during processing
ON during processing
ON for the set output time
Overall judgment result
ON when image input is allowed
Data output

Common for input signals
Encoder trigger input (Phase A)
Encoder trigger input (Phase B) 
Measurement trigger input/ 
Encoder trigger input (Phase Z) 
Data send request signal 
Command inputs

Strobe trigger output (*1)
Strobe trigger output (*1)
ON when there is an error.
Common for control signals
ON for the set output time
Overall judgment result
ON when image input is allowed
Common for output signals
Data output

Common for output signals

Load

Output terminal

COM IN

COM OUT

Input voltage
ON current *1
ON voltage *1
OFF current *2
OFF voltage *2
ON delay
OFF delay
Internal circuit

12 to 24 V DC  ±10 %
5 mA min.
8.8 V min.
0.5 mA max.
1.1V max.
5 ms max.
0.7 ms max.

[Input] signals: STEP0/ENCTRIG_Z0, STEP1/ENCTRIG_Z1,  

 

ENCTRIG_A0 to 1, ENCTRIG_B0 to 1

*1 ON current/ON voltage

  This refers to the current or voltage values needed to shift from the OFF 

 ON state. The ON voltage value is the potential 

difference between each of the input terminals and COM IN.

*2 OFF current/OFF voltage

  This refers to the current or voltage values needed to shift from the ON 

 OFF state. The OFF voltage value is the potential 

difference between each of the input terminals and COM IN.

COM IN

Input terminal

[Output] signals:

Output voltage
Load current
ON residual voltage
OFF leakage current
Internal circuit

12 to 24 V DC  ±10 %
45 mA max.
2 V max.
0.2 mA max.

Input voltage
ON current *1
ON voltage *1
OFF current *2
OFF voltage *2
ON delay
OFF delay
Internal circuit

12 to 24 V DC  ±10 %
5 mA min.
8.8 V min.
0.5 mA max.
0.8 V max.
0.1 ms max.
0.1 ms max.

COM IN

Input terminal

Output voltage
Load current
ON residual voltage
OFF leakage current
Internal circuit

12 to 24 V DC  ±10 %
45 mA max.
2 V max.
0.2 mA max.

Load

COM OUT

Output terminal

•Handling the output common terminals

COMOUT1: STGOUT0 to 3, RUN/BUSY1, ERROR, BUSY0, OR0 to 1, GATE0 to 1   COMOUT2: READY0 to 1, DO0 to 7   COMOUT3: DO8 to 15

*1 This is a signal that is used when the strobe device is connected to the Controller.

*2 This signal is only available in the Random trigger mode.

Internal Specifications

[Input] signals: RESET, DI0 to DI7, DSA0, DSA1

NPN I/O type

Parallel Interface

BUSY0, RUN/BUSY1, OR0 to 1, GATE0 to 1,  

ERROR, DO0 to 15, READY0 to 1

[Output] signals: When STGOUT0-3 are used, 

connect the COM IN terminal.

ENCTRIG_A0
ENCTRIG_B0
STEP0/ 
ENCTRIG_Z0

Encoder trigger input(Phase A)
Encoder trigger input(Phase B)
Measurement trigger input/Encoder 
trigger input(Phase Z)

I/O Connector

No.

Wire color Mark (red)

Function

Signal name

No.

Wire color Mark (blk)

Function

Signal name

Output terminal

COM IN

Input voltage
ON current *1
ON voltage *1
OFF current *2
OFF voltage *2
ON delay
OFF delay
Internal circuit

12 to 24 V DC  ±10 %
5 mA min.
8.8 V min.
0.5 mA max.
1.1V max.
5 ms max.
0.7 ms max.

[Input] signals: STEP0/ENCTRIG_Z0, STEP1/ENCTRIG_Z1, 

 

ENCTRIG_A0 to 1, ENCTRIG_B0 to 1

*1 ON current/ON voltage

  This refers to the current or voltage values needed to shift from the OFF 

 ON state. The ON voltage value is the potential 

difference between each of the input terminals and COM IN.

*2 OFF current/OFF voltage

  This refers to the current or voltage values needed to shift from the ON 

 OFF state. The OFF voltage value is the potential 

difference between each of the input terminals and COM IN.

[Output] signals:

Output voltage
Load current
ON residual voltage
OFF leakage current
Internal circuit

12 to 24 V DC  ±10 %
45 mA max.
2 V max.
0.2 mA max.

Input voltage
ON current *1
ON voltage *1
OFF current *2
OFF voltage *2
ON delay
OFF delay
Internal circuit

12 to 24 V DC  ±10 %
5 mA min.
8.8 V min.
0.5 mA max.
0.8 V max.
0.1 ms max.
0.1 ms max.

Output voltage
Load current
ON residual voltage
OFF leakage current
Internal circuit

12 to 24 V DC  ±10 %
45 mA max.
2 V max.
0.2 mA max.

Internal Specifications

[Input] signals: RESET, DI0 to DI7, DSA0, DSA1

PNP I/O type

Parallel Interface

BUSY0, RUN/BUSY1, OR0 to 1, GATE0 to 1, 

ERROR, DO0 to 15, READY0 to 1

[Output] signals: When STGOUT0-3 are used, 

connect the COM IN terminal.

COM IN

Input terminal

COM OUT

Output terminal

Load

COM IN

Input terminal

COM OUT

Load

I/O Connector wiring is the same as NPN I/O type.

LCD integrated type

Connector

Wire Color

No. mark

LCD integrated type

Pin numbers will depend on the external device being connected. Refer 

to the manual for the personal computer or PLC being connected.

Pin No.

1
2
3
4
5
6
7
8
9

Signal name

SDB(+)

SD/SDA(-)
RD/RDA(-)

RDB(+)

NC
NC
NC
NC

GND

        Function
For RS-422
For RS-232C/RS-422
For RS-232C/RS-422
For RS-422
Not connected
Not connected
Not connected
Not connected
Signal ground

Connector

Connection Method

Wiring

• RS-232C

• RS-422

Controller

Use a shielded cable.

The maximum cable length is 15 m.

Use a compatible connector.

• Recommended items

RS/CS control cannot be used.

Align  the  connector  with  the  socket  and 

press it straight into place, then fix it with 

the screws on both sides of the connector.

Connect the cable ensuring the minimum 

bend radius or larger.

XM3A-0921
XM2S-0911

OMRON Corporation
OMRON Corporation

Signal name

SD
RD

GND

Pin No.

2
3
9

Signal name

SD
RD

GND

Pin No.

*
*
*

External device to be connected

Controller

Use a shielded cable.

Signal name

SDB(+)

SDA(-)
RDA(-)

RDB(+)

Pin No.

1
2
3
4

Pin No.

*
*
*
*

External device to be connected

Signal name

SDA(-)

SDB(+)
RDB(+)

RDA(-)

Plug

Hood

Manufacturer

Model

Serial Interface

Turn OFF the power supply before connecting or 

disconnecting a Cable. Peripheral devices may be 

damaged if the cable is connected or disconnected 

with the power ON.

Make a mount hole on the panel.

Panel thickness range: 1.6 to 4.8 mm

Panel material: Metal (iron, aluminum 

or stainless)

Insert  the  LCD  integrated  controller 

into the hole, from the front panel.

• Panel mounting

* No burr allowed

Use the bracket (supplied with the 

product)  to  secure  the  controller 

and the panel.

 

Tightening torque: 0.5 to 0.6 Nm

297

+1

0

247

(Unit: mm)

Top face

Bottom face

+1 0

Mounting

1

2

3

 Mounting the controller to the optional 

desktop stand.

The controller can be placed on 

a desk by attaching the optional 

desktop stand (FZ-DS) to the 

rear of the controller.

* For details, refer to the instruction 

manual of the desktop stand.

 Mounting the controller to the optional 

VESA attachment unit.

VESA-compatible mounting of 

the controller is possible by 

attaching the optional VESA 

attachment unit (FZ-VESA) to 

the rear of the controller.

* For details, refer to the instruction 

manual of the VESA attachment 

Summary of Contents for FZ5-110

Page 1: ... 出力信号の負荷電流は適切か 配線に誤りは無いか 接地について コントローラの電源回路は内部回路と絶縁されていません 24VDC電源のプラス 端子を接地する場合は コントローラの FG端子 PLCのFG端子を接地しないでください パソコンの外郭とSG 0V がパソコン内部で接続されていますの で 下図のような経路で電流が流れ焼損の原因になります パソコンんのようなSG 0V とFGが短絡短絡する経路が無い場合 には コントローラのFG端子を接地しても問題ありません PLCに ついては ご使用のPLCの仕様をご確認の上 配線してください コントローラに接続するカメラは 必ず台座を使用して取り付けて ください カメラ本体の外郭はSG 0V ですので 台座が 無い場合には SG 0V とFGが短絡する恐れがあります プラス 端子を接地する場合は SG 0V 例 カメラ本体 電源端子 を指等で触れ...

Page 2: ... 7ms RESET DI0 DI7 DSA0 BUSY0 RUN BUSY1 OR0 1 GATE0 1 ERROR DO0 15 READY0 1 STEP0 ENCTRIG_Z0 STEP1 ENCTRIG_Z1 ENCTRIG_A0 1 ENCTRIG_B0 1 1 ON ON OFF ON ON COM IN 2 OFF OFF ON OFF OFF COM IN STGOUT0 3 STGOUT0 3 ON OFF DC12 24V 10 45mA 2V 0 2mA ON 1 ON 1 OFF 2 OFF 2 ON OFF DC12 24V 10 5mA 8 8V 0 5mA 0 8V 0 1ms 0 1ms ON OFF DC12 24V 10 45mA 2V 0 2mA COM IN COM OUT COM IN COM OUT COM IN No パラレル I O ケーブ...

Page 3: ...制に従う設備 c 人命や財産に危険が及びう る システム 機械 装置 d ガス 水道 電気の供給システムや24時間連続運転システムな どの 高い信頼性が必要な設備 e その他 上記 a d に準ずる 高度な安全性が必要と さ れる用途 上記は適合用途の条件の一部です 当社のベス ト 総合カタログ データ シー ト等最新版 のカタログ マニュアルに記載の保証 免責事項の内容を よ く 読んでご使用く だ さ い r 2012年8月 A その他のお問い合わせ 納期 価格 サンプル 仕様書は貴社のお取引先 または貴社 担当オムロン販売員にご相談ください オムロン制御機器販売店やオムロン販売拠点は Webページで ご案内しています 製品に関するお問い合わせ先 クイック オムロン 0120 919 066 営業時間 8 00 21 00 営業日 365日 FAXやWebページでもお問い合わせいただけ...

Page 4: ...tions Indicates the possibility of laser radiation Indicates the possibility of injury by high temperature under specific conditions CAUTION Symbols and the meanings for safety precautions described in this manual In order for the product to be used safely the following indications are used in this book to draw your attention to the cautions The cautions with the indications describe the important...

Page 5: ... Phase A Encoder trigger input Phase B Measurement trigger input Encoder trigger input Phase Z I O Connector No Wire color Mark red Function Signal name No Wire color Mark blk Function Signal name Output terminal COM IN Input voltage ON current 1 ON voltage 1 OFF current 2 OFF voltage 2 ON delay OFF delay Internal circuit 12 to 24 V DC 10 5 mA min 8 8 V min 0 5 mA max 1 1V max 5 ms max 0 7 ms max ...

Page 6: ...prox 3 4 kg for 4 camera type Approx 3 2 kg for 2 camera type Operation Serial communications Network communications EtherNet IP communication Exclude FZD Parallel I O Monitor interface USB interface Power supply voltage Current consumption At Power supply voltage 24 V DC Insulation resistance Dielectric strength Leakage current Noise resistance Vibration resistance Shock resistance Ambient temper...

Reviews: