8
F3SP-T01
Safety Precautions
!
WARNING
Do not operate the product in atmospheres containing
flammable or explosive gas. Arcs or heating of relays
during switching may cause fire or explosion.
Do not use a load that exceeds the contact ratings or
switching capacity. Doing so may cause the product to fail
to perform its specified functions, causing insulation failure,
contact welding, or contact failure. It may also cause
damage to the F3SP-T01 or burning.
The service life will depend on the switching conditions. Be
sure to check the actual operating conditions using the
actual devices, and make sure that the number of switching
operations will not cause performance problems. If you
continue to use the device with deteriorated performance, it may
result in breakdown of insulation between circuits, or cause burning of
the product.
Handle with Care
Do not drop the product or expose it to excessive vibration or shock.
Doing so may prevent it from functioning properly.
Adhesion of Solvent
Do not allow solvents, such as alcohol, thinner, trichloroethane, or
gasoline, to come into contact with the product. Such solvents may
make the markings illegible and cause deterioration of parts.
Installation Location
Do not install or store the product in the following locations. Doing so
may result in product failure or malfunction.
•
Locations subject to direct sunlight
•
Locations subject to temperatures outside the range
−
10 to 55
°
C
•
Locations subject to humidity levels outside the range 35% to 85%
•
Locations subject to condensation due to extreme temperature
changes
•
Locations subject to atmospheric pressures outside the range 86
to 106 kPa
•
Locations subject to corrosive or flammable gases
•
Locations subject to shock or vibration in excess of the product
ratings
•
Locations subject to exposure to water, oil, or chemicals
•
Locations subject to dust (including iron dust) or salts
Take appropriate and sufficient countermeasures when using the
product in the following locations.
•
Locations subject to static electricity or other forms of noise
•
Locations subject to possible exposure to radioactivity
•
Locations close to power supply lines
Installation
•
Do not use products that have been dropped or have its internal
parts disassembled. Specified characteristics may not be
achieved, and may cause damage to the product or burning.
•
If the products are installed side-by-side, the rated current is 1 A.
Do not exceed 1 A.
•
Use the F3SP-T01 in an enclosure that provides at least IP54
degree of protection.
Installation and Wiring
•
Use the following electrical wiring for external I/O devices.
Compatible Ferrules
•
Use ferrules that meet the following standards for length and width.
If the standards are not met, connection may fail, or the ferrules
may not be able to be plugged in and out of the terminals.
•
Ferrule Dimensions (for Power Supply Terminal of F3SP-T01)
•
Recommended Ferrule and Crimping Tool
Precautions for Safe Use
Solid wire
0.2 to 1.3 mm
2
AWG24 to 16
Flexible
wires
1.3 to 2.0 mm
2
, AWG16 to 14
If flexible wires are used, terminate the wires with
insulated ferrules (DIN 46228-4 compatible type)
before connecting them.
Square
Ferrules
Dimension A
1.0 to 2.3
The cross-sectional
area after crimping
must be less than
4.8 mm
2
.
Dimension B
0.8 to 2.65
Cylindrical
Ferrules
Dimension C
0.8 dia. to 2.3 dia.
Type of
ferrule
Manufacturer
Size
Model
Recommended
crimping tool
Square
Ferrules
Phoenix
Contact
AWG24 AI0.25-8YE
UD6
ZA3
AWG22 AI0.34-8TQ
AWG20
AI0.5-10WH
AI0.5-8WH
AWG18
AI0.75-10GY
AI0.75-8GY
AWG16 AI1.5-10BK
AWG14 AI2.5-10BU
Weidmuller
AWG24 H0.25/12
PZ6 roto
AWG22 H0.34/12
AWG20
H0.5/16
H0.5/14
AWG18
H0.75/16
H0.75/14
AWG16 H1.5/16
Cylindrical
Ferrules
Nichifu
AWG22
TGV TC-1.25-11T
TGN TC-1.25-11T
NH11
NH32
NH65
AWG20
AWG18
AWG16
B
C dia.
S
qu
are Ferr
u
les
Cylindrical Ferr
u
les
A