94
Low Voltage Switch Gear
Appendix
Permissible ratings of devices approved for North America
hp-rating = Power rating in in horse power (maximum motor rating)
FLA = Full Load Amps / Motor full load current
Icu complies with „short circuit breaking capacity“ to UL
Approvals
and
R
-Guide- and File-No.
These data are important for UL-inspecting
Ratings Icu complies with „short
circuit breaking breaking ca-
pacity“
Manual Motor Starter
Manual Motor Controller
Suitable for Tap
Conductor Protection in
Group Installations
Combination Motor Controller Type E
Circuit breaker
Type
Rated
current
IN
A
up to AC
240 V
up to AC
480 V
up to AC
600 V
up to AC
240 V
up to AC
480 V
up to AC
240 V
up to AC
240 V
up to AC
480 V
up to AC
600 V
UL
kA
CSA
kA
UL
kA
CSA
kA
UL
kA
CSA
kA
UL
kA
UL
kA
UL
kA
UL
kA
CSA
kA
UL
kA
CSA
kA
UL
kA
CSA
kA
J7MN-12
0,11... 3,2 65
50
65
50
30
10
65
65
-
-
-
-
-
-
-
4
65
50
65
50
30
10
65
65
-
-
-
-
-
-
-
5
65
50
65
50
30
10
65
65
-
-
-
-
-
-
-
6,3
65
50
65
50
30
10
65
65
-
-
-
-
-
-
-
8
65
50
65
50
30
10
65
65
-
-
-
-
-
-
-
10
50
50
10
-
-
-
-
-
-
-
-
-
-
-
-
12
50
50
10
-
-
-
-
-
-
-
-
-
-
-
-
J7MN-25
(+J74MN-TB25)
0,11 ... 3,2 65
50
65
50
30
30
65
65
30
65
50
65
30
50
30
4
65
50
65
50
30
30
65
65
30
65
50
65
30
50
30
5
65
50
65
50
30
30
65
65
30
65
50
65
30
50
30
6,3
65
50
65
50
30
30
65
65
30
65
50
65
30
50
30
8
65
50
65
50
30
30
65
65
30
65
50
65
30
50
30
10
65
50
65
50
30
30
65
65
30
65
50
65
30
50
30
12,5
65
50
65
50
30
30
65
65
30
65
50
65
30
50
30
16
65
50
65
50
30
30
65
65
-
65
50
65
30
-
-
20
65
50
65
50
30
30
65
65
-
65
50
65
30
-
-
22
65
50
65
50
30
30
65
65
-
65
50
65
30
-
-
25
65
50
65
50
30
30
-
-
-
-
-
-
-
-
-
J7MN-50
25
65
50
65
50
25
25
65
65
25
65
50
65
50
25
25
32
65
50
65
50
25
25
65
65
25
65
50
65
50
25
25
40
65
50
65
50
25
25
65
65
25
65
50
65
50
25
25
45
65
50
65
50
25
25
65
65
25
65
50
65
50
25
25
50
65
50
65
50
25
25
65
65
25
65
50
65
50
25
25
J7MN-100
(+J74MN-TB100)
50
65
50
65
50
30
30
65
65
30
65
50
65
30
50
30
63
65
50
65
50
30
30
65
65
30
65
50
65
30
50
30
75
65
50
65
50
30
30
65
65
30
65
50
65
30
50
30
90
65
50
65
50
30
30
65
65
-
65
50
65
30
-
-
100(99)
65
50
65
50
30
30
65
65
-
65
50
65
30
-
-
Country
USA
Canada
USA
Canada
Europe
MANUAL MOTOR
CONTROLLER
COMBINATION
MOTOR
CONTROLLER
UL
UL
UL
UL
Type
J7MN-12
o
o
-
-
o
J7MN-25
o
o
o
*1
*1
in use with J74MN-TB25
o
*1
o
J7MN-50
o
o
o
o
o
J7MN-100
o
o
o
*2
*2
un use with J74MN-TB100
o
In standard version approved
-
Not provided for test till now
o
*2
o
J73MN-11F
o
o
-
-
o
J73MN-N
o
o
-
-
o
J73MN-S
o
o
-
-
o
J73MN-T-11S
o
o
-
-
o
J73MN-L
o
-
-
-
o
J74MN-TB25
o
o
-
-
o
J74MN-TB100 o
o
-
-
o
Devices
Guide-No.
File-No.
Canada
USA
Circuit Breakers J7MN
as Manual Motor Controller
NLRV7
NLRV
E129916
Circuit Breakers J7MN
as Combination Motor Controller
NKJH7
NKJH
E197641
J74MN busbar system
NLRV7
NLRV
E129916
J74MN accessories
NKCR7