Using Copy Mode

This function can be used only when control is stopped. When copying settings, first finish making settings for the Temperature Controller in the 
normal mode, then upload and download in Copy Mode.

Upload (Temperature Controller to 
Setting Display Unit)

Step 1

Press the 

COPY

 Key for at least 1 s to enter Copy Mode.

Step 2

Use the 

UP

 and 

DOWN

 Keys to select 

up

 on Display No. 2. Press the 

UNIT

 Key to select the unit number for the upload.

Any unit number from 

0

 to 

f

 or "

-

" (all units) can be selected.

Step 3

Press the 

LEVEL

 Key for at least 1 s to start the upload.

Note: 1.

up

 will flash on Display No. 2 during the upload.

2.

The mode will return automatically to the Operation Level 
when the upload has been completed.

Download (Setting Display Unit to 
Temperature Controller)

Step 1

Press the 

COPY

 Key for at least 1 s to enter the copy mode.

Step 2

Use the 

UP

 and 

DOWN

 Keys to select 

down

.

The possible selections are 

up

 and 

down

.

Step 3

Press the 

UNIT

 Key to select the unit number for which data has 

been uploaded. Any unit number from 

0

 to 

f

 can be selected (for 

each Unit). The unit number for any Controllers without uploaded 
data, however, will not be displayed. Also, selection will not be 
possible if the uploaded information in the display was uploaded from 
all Controllers. The UNIT display will be "

-

".

Note:

For example, to download setting data from unit number 1 to 
unit number 2, change the unit number from 2 to 1, and change 
the number of unit number 1 to another unit number or 
disconnect the socket connected to unit number 1. Be sure that 
there is only one Controller with the same unit number on the 
network at any one time.

Step 4

Press the 

LEVEL

 Key for at least 1 s to start the download.

Note: 1.

down

 will flash on Display No. 2 during the download.

2.

The mode will return automatically to the Operation Level 
when the download has been completed.

Supplementary Explanation

To download to all Temperature Controllers, use the same 
configuration as when the data was uploaded. Downloading is not 
possible in the following circumstances. If downloading is not 
possible, 

down

 will flash and then the upload display will be shown.

An E5ZN has been added or deleted since the upload.

The same number of Controllers are connected as when the 
upload was executed, but when the unit numbers are different.

The resistance thermometer/thermocouple type configuration is 
different.

Copying Parameters from an E5ZN 
Master to Other E5ZNs

This section describes how to copy parameters from Unit 1, used as 
the master, to Units 2 and 3, as shown in the following diagram.

Data uploaded to the E5ZN-SDL can be downloaded only to a 
Controller whose unit number has been uploaded. Therefore, after 
copying the Master parameters, change the unit number of the 
Controller where the data is to be downloaded to the unit number 
from which data was uploaded (i.e., the master's unit number), and 
then download the parameter data.

Step 1

Select Copy Mode.
Press the 

COPY

 Key for at least 1 s to enter Copy Mode. 

Step 2

Press the 

UNIT

 Key to select the unit number of the master. In this 

example, the master is unit number 1, so select 1.

Step 3

Upload all the parameters from the Master.
In this example, all the parameters from unit number 1 will be 
uploaded to the E5ZN-SDL. Press the 

LEVEL

 Key for at least one 

second to start the upload. 

up

 will flash on the display during the 

upload. 
The mode will return automatically to Run Mode when the upload 
has been completed.

copy

up

0

copy

down

0

23

0

0

E5ZN-SDL

System Configuration

Master

E5ZN   1

E5ZN   2

E5ZN   3

23

0

0

copy

up

1

copy

up

1

Summary of Contents for E5ZN Series

Page 1: ...is turned ON ERROR Lights when an input error e g memory error or input error for any channel occurs SD RD Send Data Receive Data Light during communications with the host OUT1 OUT2 Control Output 1 C...

Page 2: ...rollers are mounted side by side Mounting Terminal Units Together From 0 to 15 Expansion Terminal Units E5ZN SCT18S can be connected to a standard Terminal Unit E5ZN SCT24S Terminal Units can be mount...

Page 3: ...control panel DIN Track PFP 50N 50 cm PFP 100N 100 cm Install the DIN Track vertically to the ground Mounting the Controller Mounting Procedure Firmly insert the Controller following the guides on th...

Page 4: ...r limit Alarm value 1 20 C Set the deviation in Set point 100 C E5ZN unit number 3 Channel number 1 Power ON Start operation Set the channel number Set the unit number Set the control method Set the a...

Page 5: ...Key Alarm 1 type Press the Key for at least one second Set to pid when PID control is used M M M M Power ON Process value set point To operate Alarm value 1 To stop Operation level M M M PV SP After...

Page 6: ...1 s to start the download Note 1 down will flash on Display No 2 during the download 2 The mode will return automatically to the Operation Level when the download has been completed Supplementary Exp...

Page 7: ...in the download unit number display At initialization there is no upload data so the unit number display is blank Step 7 Press the UNIT Key for at least 1 s to start the download down will flash on th...

Page 8: ...our levels are selected It is possible to enter Copy Mode while control is being performed but copy operations e g upload and download can be used only when control has stopped Mode Level During opera...

Page 9: ...the Operation Level or Adjustment Level The first display flashes after 1 s The Initial Setting Level is for specifying the input type selecting the control method setting the control period setting...

Page 10: ...l h 105 0 1 0 ol l 5 0 1 0 sero off u 0 hbh 0 1 1 0 M ot 2 0 u 0 M amoV 0 u 0 sedu 3 u 0 M istp 0 u 0 cjc on u 0 sprt 0 1 0 M M M M M M M M M M M M M M M M M al3n n o 1 0 alh3 0 2 C 1 0 M M M sub4 17...

Page 11: ...tection Upper limit temperature input shift value Lower limit temperature input shift value Proportional band Integral time Derivative time M wtpt off u 0 M M at off 1 0 ct 0 0 1 0 hb 0 0 1 0 sp 0 0 C...

Page 12: ...0 0 F N 8 200 to1300 C 300 to 2300 F R 9 0 to 1700 C 0 to 3000 F S 10 0 to 1700 C 0 to 3000 F B 11 100 to1800 C 300 to 3200 F ES1A Infrared Tempera ture Sensor K10 to 70 C 12 0 to 90 C 0 to 190 F K60...

Page 13: ...See notes 1 and 6 See note 5 See note 4 6 Upper limit alarm with standby se quence See note 6 7 Lower limit alarm with standby se quence 8 Absolute val ue upper limit 9 Absolute val ue lower limit 10...

Page 14: ...99 999 9 Less than 1999 199 9 More than 9999 999 9 Control continues and operation is normal This message is displayed when the PV or PV SP is displayed Memory Error There is an error in the internal...

Reviews: