E5ZN Operation
CSM_E5ZN_operation_TG_E_2_2
1
Nomenclature
E5ZN (Orders for the E5ZN series will not be accepted after March 31, 2019.)
•
The E5ZN is a Temperature Controller that features the ability to be built into equipment.
•
The E5ZN is equipped with RS-485 communications, so process values can be monitored and parameters can be read or written from the host
system.
•
The Terminal Unit can be separated from the Controller, so maintenance can be performed on the Controller without changing the wiring.
•
If two or more Controllers are connected to the same host system, use an expansion Terminal Unit and close mounting to safe space and
reduce wiring.
Using Setting Switches
Controller
Front panel
Terminal Unit
Standard Model
Expansion Model
Baud Rate
Operation Indicators
Unit Number Switch
Set the baud rate of the Controller to match the baud rate of the host system.
•
POWER
Lights when power is turned ON.
•
ERROR
Lights when an input error (e.g., memory error or input error for any channel) occurs.
•
SD/RD (Send Data/Receive Data)
Light during communications with the host.
•
OUT1, OUT2 (Control Output 1, Control Output 2)
Light when the control output 1 or the control output 2 functions are ON.
•
SUB1, SUB2 (Auxiliary Output 1, Auxiliary Output 2)
Light when the auxiliary output 1 or the auxiliary output 2 functions are ON.
Front Panel
Set the unit number to identify the Controller connected to the host system and to the Setting Display Unit
(E5ZN-SDL).
The unit number is hexadecimal.
Switch settings 0 to F correspond to unit numbers 00 to 15.
Set a different unit number for each E5ZN if more than one is connected using RS-485 communications.
Communications cannot be performed if the same unit number is used more than once on the same line.
Setting
0
00
1
01
Default setting
Default setting
2
02
3
03
4
04
5
05
6
06
7
07
8
08
9
09
A
10
B
11
C
12
D
13
E
14
F
15
Unit number
Setting
0
4800
1
9600
2
19200
3
38400
4
5
6
Do not set.
7
8
9
Baud rate (bps)
0
1
2 3 4
5
9
8
7
6
01
23
4 5 6
7
F E D C B A
9
8