![background image](http://html1.mh-extra.com/html/omron/e5gc-600/e5gc-600_manual_742653021.webp)
21
Press and hold the
L
Level key for three seconds. This will get the unit back to the Initial Setting level.
1.
The first parameter in the initial setting level is the (
in-t
). This is the input type parameter use
the
instruction sheet or user manual to determine the correct setting based on the input type is
applied to
the unit for the application. Use the Up/Down arrow keys to adjust the value.
2.
Tap on the
M
Mode key once to get to the next parameter (
d-u
). Select the units to be displayed
ether °C or °F. Use the Up/Down arrow keys to adjust the value.
3.
Tap on the
M
Mode key once to get to the next parameter (
sl-h
). This is used to determine the
upper set point limit. Use the Up/Down arrow keys to adjust the value. The value set here will be
the
highest value of the set point in the operation level.
4.
Tap on the
M
Mode key once to get to the next parameter (
sl-l
). This is used to determine the
lower set point limit. Use the Up/Down arrow keys to adjust the value. The value set here will be
the
lowest value of the set point in the operation level.
5.
Tap on the
M
Mode key several times to get to the (
alt1
) parameter. This is used to determine if
the
unit is set up for High Limit control (Heating) or Low Limit control (Cooling). Use the Up/Down
arrow
keys to adjust the value. A selection of (
2
) will set the unit for High Limit control and a
selection
of (
3
)
will set the unit for Low Limit control.
6.
Note:
I
f the unit is equipped with more than 1 alarm and these are not being used by the
application
setting additional alarms (
alt2
) and (
alt3
) to a value of (
0
) will disable these output
indications on
the front display. To disable these tap on the
M
Mode key until (
alt2
) and (
alt3
)
appear and adjust
them using the Up/Down arrow keys to a value of (
0
).
7.
Note:
I
f the Event
I
nput will be used to reset the alarm condition set this next parameter:
Tap on the
M
Mode key several times to get to the (
ev-1
) parameter. This needs to be changed
from
(
msp0
) to (
lat
). Use the Up/Down arrow keys to adjust the value. This will reassign the
Event
I
nput
to Alarm Latch Cancel.
Press and hold the
L
Level key for three seconds. This will get the unit back to the Operation Setting
level.
At this point the controller is set up for commissioning:
1.
Verify that the Process Value is reading correctly.
2.
Tap on the
M
Mode key to get to (
a l-1
) this must be set to a value of (
0
). If this is not
set to
(
0
) the controller will add this value to the set value and may cause damage to the
system.
3.
Tap on the
M
Mode key until the controller is reading the process value and set point.
High Limit Control testing:
If the set point is adjusted below the actual process value the SUB1 LED should be ON and the system
should not run. Raise the set point using the Up arrow key and set the high limit for the application. Verify
that the SUB1 LED is still ON and that the system cannot be started. Apply a reset to the Limit controller
via event input or PF key. The SUB1 LED should go off and the system should be able to be started.
E5GC-600