![Omron E5EZ-PRR Series Manual Download Page 12](http://html1.mh-extra.com/html/omron/e5ez-prr-series/e5ez-prr-series_manual_742652012.webp)
40
Digital Position-Proportional Controllers
E5EZ-PRR
■
Setting the Type of Input
Types of input include thermocouple, platinum resistance thermometer, infrared temperature sensor,
and analog inputs. Please set your input type in accordance with the sensor to be used. Product spec-
ifications also include multi input types, such as thermocouples/ plastic resistance thermometers, and
analog input types, resulting in differences between set values. Please confirm the model that you are
using.
Table of Input Types
•
Initial value of
"
5
"
•
Initial value of
"
0
"
Input
Type
Name
Set
value
Set
Range
of
Temperature
Input
Platinum
Resistance
Thermometer
Pt100
0
-200 to 850 (°C)
/ -300 to 1500 (°F)
1
-199.9 to 500.0 (°C)
/ -199.9 to 900.0 (°F)
2
0.0 to 100.0 (°C)
/ 0.0 to 210.0 (°F)
JPt100
3
-199.9 to 500.0 (°C)
/ -199.9 to 900.0 (°F)
4
0.0 to 100.0 (°C)
/ 0.0 to 210.0 (°F)
Thermocouple
K
5
-200 to 1300 (°C)
/ -300 to 2300 (°F)
6
-20.0 to 500.0 (°C)
/ 0.0 to 900.0 (°F)
J
7
-100 to 850 (°C)
/ -100 to 1500 (°F)
8
-20.0 to 400.0 (°C)
/ 0.0 to 750.0 (°F)
T
9
-200 to 400 (°C)
/ -300 to 700 (°F)
22
-199.9 to 500.0 (°C)
/ -199.9 to 700.0 (°F)
E
10
0 to 600 (°C)
/ 0 to 1100 (°F)
L
11
-100 to 850 (°C)
/ -100 to 1500 (°F)
U
12
-200 to 400 (°C)
/ -300 to 700 (°F)
23
-199.9 to 500.0 (°C)
/ -199.9 to 700 (°F)
N
13
-200 to 1300 (°C)
/ -300 to 2300 (°F)
R
14
0 to 1700 (°C)
/ 0 to 3000 (°F)
S
15
0 to 1700 (°C)
/ 0 to 3000 (°F)
B
16
100 to 1800 (°C)
/ 300 to 3200 (°F)
Infrared
temperature
sensor,
ES1B
10°C to 70°C
17
0 to 90 (°C)
/ 0 to 190 (°F)
60°C to 120°C
18
0 to 120 (°C)
/ 0 to 240 (°F)
115°C to
165°C
19
0 to 165 (°C)
/ 0 to 320 (°F)
140°C to
260°C
20
0 to 260 (°C)
/ 0 to 500 (°F)
Analog Input
0 to 50 mV
21
The scaling usage range is either
-1999 to 9999 or -199.9 to 999.9
Input Type
Specifica-
tions
Set
value
Set Range of Input
A
nalog I
nput
T
y
pe
Current
Input
4 to 20mA
0
Use the following scales based on the
range of measurements:
-19999 to 9999
-199.9 to 999.9
-19.99 to 99.99
-1.999 to 9.999
0 to 20mA
1
Voltage
Input
1 to 5V
2
0 to 5V
3
0 to 10V
4
in-t
5
l.ini
Input Types
5