background image

E5EK-DRT

E5EK-DRT

6

Dimensions

Note:

All units are in millimeters unless otherwise indicated.

 E5EK-DRT

Panel Cutouts

Note:

1. Recommended panel thickness is 1 to 8 mm.

2. Maintain the specified vertical and horizontal

mounting space between each Unit. Units
must not be closely mounted vertically or
horizontally.

120 min.

60 min.

Note:

Rear case width is 44 mm.

Installation

 External Connection

SSR 
output
(E53-S)

Linear 
voltage output
(E53-V34)

Current output
(E53-C3)

ON/OFF voltage
output (E53-Q)

Relay output
(E53-R)

0 to 10 V

4 to 20 mA

40 mA at
12 VDC

100 to 240 VAC,
50/60 Hz

Control output 1

Control output 2

Auxiliary
output 1

Auxiliary
output 2

Remote
SP input

4 to 20 mA

CT input

1 to 5 V, 0 to 5 V,
0 to 10 V

4 to 20 mA,
0 to 20 mA

Thermo-
couple

Platinum 
resistance
thermometer
(B)

0 to 10 V

4 to 20 mA

40 mA at
12 VDC

Precautions

For application precautions, refer to the CompoBus/D Operation Manual (W267) and E5EK CompoBus/D-type Digital Controller Operation
Manual
 (H99).

Summary of Contents for E5EK-DRT -

Page 1: ... control outputs heat 2 Be sure to specify the Current Transformer and Output Unit when ordering Description Model Specification Output Unit order separately E53 R Relay E53 S SSR E53 Q Pulse NPN 12 VDC E53 Q3 Pulse NPN 24 VDC E53 Q4 Pulse PNP 24 VDC E53 C3 Linear 4 to 20 mA E53 C3D Linear 0 to 20 mA E53 V34 Linear 0 to 10 V E53 V35 Linear 0 to 5 V Note The Digital Controller uses a dedicated high...

Page 2: ...C 199 9 to 650 0 199 9 to 650 0 100 0 to 100 0 F 199 9 to 999 9 199 9 to 999 9 150 0 to 250 0 Setting 0 1 22 Thermocouple Input switch selectable see note K J T E L U N R S B W PLII Range C 200 to 1 300 0 0 to 500 0 100 to 850 0 0 to 400 0 199 9 to 400 0 0 to 600 100 to 850 0 0 to 400 0 199 9 to 400 0 200 to 1 300 0 to 1 700 0 to 1 700 100 to 1 800 0 to 2 300 0 to 1 300 F 300 to 2 300 0 0 to 900 0...

Page 3: ...g using front panel keys Indication method 7 segment digital display and LEDs Character height PV 14 mm SV 9 5 mm Control output According to Output Unit see Output Unit Ratings and Characteristics Attach an Output Unit that is sold separately Remote SP input Current input 4 to 20 mA Input impedance 150 Ω Current Transformer input Connect an exclusive Current Transformer E54 CT1 or E54 CT3 Other f...

Page 4: ...gs Front panel NEMA4 for indoor use equivalent to IP66 Rear case IEC standard IP20 Terminals IEC standard IP00 Memory protection Non volatile memory number of writings 100 000 operations Weight Approx 320 g Mounting bracket approx 65 g EMC Emission Enclosure EN55011 Group 1 class A Emission AC Mains EN55011 Group 1 class A Immunity ESD EN61000 4 2 4 kV contact discharge level 2 8 kV air discharge ...

Page 5: ...to 250 VAC resistive load Voltage output NPN 40 mA at 12 VDC with short circuit protection NPN 20 mA at 24 VDC with short circuit protection PNP 20 mA at 24 VDC with short circuit protection Linear current output 4 to 20 mA permissible load impedance 600 Ω max resolution approx 2 600 0 to 20 mA permissible load impedance 600 Ω max resolution approx 2 600 Linear voltage output 0 to 10 VDC permissib...

Page 6: ...nection SSR output E53 S Linear voltage output E53 V34 Current output E53 C3 ON OFF voltage output E53 Q Relay output E53 R 0 to 10 V 4 to 20 mA 40 mA at 12 VDC 100 to 240 VAC 50 60 Hz Control output 1 Control output 2 Auxiliary output 1 Auxiliary output 2 Remote SP input 4 to 20 mA CT input 1 to 5 V 0 to 5 V 0 to 10 V 4 to 20 mA 0 to 20 mA Thermo couple Platinum resistance thermometer B 0 to 10 V...

Page 7: ...E5EK DRT E5EK DRT 7 ...

Page 8: ...40 6028 Japan Phone 81 6 949 6035 Fax 81 6 949 6069 ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No H98 E1 1 In the interest of product improvement specifications are subject to change without notice Printed in Japan 0398 1M 0398 a ...

Reviews: