background image

E5EK-DRT

E5EK-DRT

4

 Characteristics

Indication accuracy

Thermocouple (see note 1):
(

±

0.3% of indication value or 

±

1

°

C, whichever greater) 

±

1 digit max.

Platinum resistance thermometer (see note 2):
(

±

0.2% of indication value or 

±

0.8

°

C, whichever greater) 

±

1 digit max.

Analog input: 

±

0.2% FS 

±

1 digit max.

Hysteresis

0.01% to 99.99% FS (in units of 0.01% FS)

Proportional band (P)

0.1% to 999.9% FS (in units of 0.1% FS)

Integral (reset) time (I)

0 to 3,999 s (in units of 1 s)

Derivative (rate) time (D)

0 to 3,999 s (in units of 1 s)

Control period

1 to 99 s (in units of 1 s)

Manual reset value

0.0% to 100.0% (in units of 0.1%)

Alarm setting range

–1,999 to 9,999 or –199.9 or 999.9 (decimal point position dependent on input type)

Sampling period (see note 3)

Temperature input: 250 ms
Analog input:

100 ms

Insulation resistance

20 M

 min. (at 500 VDC)

Dielectric strength

2,000 VAC, 50/60 Hz for 1 min between terminals of different polarities

Vibration resistance

Malfunction: 10 to 55 Hz, 10 m/s

2

 (approx. 1G) for 10 min each in X, Y, and Z directions

Destruction: 10 to 55 Hz, 20 m/s

2

 (approx. 2G) for 2 hrs each in X, Y, and Z directions

Shock resistance

Malfunction: 200 m/s

2

 min. (approx. 20G), 3 times each in 6 directions

(100 m/s

2

 (approx. 10G) applied to the relay)

Destruction: 300 m/s

2

 min. (approx. 30G), 3 times each in 6 directions

Ambient temperature

Operating:

–10

°

C to 55

°

C (with no icing)/3-year warranty period: –10

°

C to 50

°

C

Storage:

–25

°

C to 65

°

C (with no icing)

Ambient humidity

Operating: 35% to 85%

Enclosure ratings

Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case:

IEC standard IP20

Terminals:

IEC standard IP00

Memory protection

Non-volatile memory (number of writings: 100,000 operations)

Weight

Approx. 320 g
Mounting bracket: approx. 65 g

EMC

Emission Enclosure:

EN55011 Group 1 class A

Emission AC Mains:

EN55011 Group 1 class A

Immunity ESD:

EN61000-4-2:

4 kV contact discharge (level 2)
8 kV air discharge (level 3)

Immunity RF-interference:

ENV50140:

10 V/m (amplitude modulated, 
80 MHz to 1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)

Immunity Conducted Disturbance:

ENV50141:

10 V (0.15 to 80 MHz) (level 3)

Immunity Burst:

EN61000-4-4:

2 kV power-line (level 3)
2 kV I/O signal-line (level 4)

Approved standards

UL1092, CSA22.2 No. 14, CSA22.2 No. 1010-1
Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC61010-1)
Conforms to VDE0106/part 100 (Finger Protection), when the separately-ordered terminal
cover is mounted.

Note:

1. The indication accuracy of the K, T, and N thermocouples at a temperature of -100

°

C or less is 

±

2

°

±

1 digit maximum.

The indication accuracy of the B thermocouple at a temperature of 400

°

C or less is unrestricted.

The indication accuracy of the R and S thermocouples at a temperature of 200

°

C or less is 

±

3

°

±

1 digit maximum.

The indication accuracy of the W thermocouple at any temperature is (

±

0.3% of the indicated value or 

±

3

°

C, whichever is greater)

±

1 digit maximum.

The indication accuracy of the PL

II

 thermocouple at any temperature is (

±

0.3% or 

±

2

°

C, whichever is greater) 

±

1 digit maximum.

2. The indication accuracy of the Pt at –100.0

°

C to 100.0

°

C is 

±

0.1% FS 

±

1 digit maximum.

3. The sampling period of the standard model with CT and remote SP inputs is 250 ms.

Summary of Contents for E5EK-DRT -

Page 1: ... control outputs heat 2 Be sure to specify the Current Transformer and Output Unit when ordering Description Model Specification Output Unit order separately E53 R Relay E53 S SSR E53 Q Pulse NPN 12 VDC E53 Q3 Pulse NPN 24 VDC E53 Q4 Pulse PNP 24 VDC E53 C3 Linear 4 to 20 mA E53 C3D Linear 0 to 20 mA E53 V34 Linear 0 to 10 V E53 V35 Linear 0 to 5 V Note The Digital Controller uses a dedicated high...

Page 2: ...C 199 9 to 650 0 199 9 to 650 0 100 0 to 100 0 F 199 9 to 999 9 199 9 to 999 9 150 0 to 250 0 Setting 0 1 22 Thermocouple Input switch selectable see note K J T E L U N R S B W PLII Range C 200 to 1 300 0 0 to 500 0 100 to 850 0 0 to 400 0 199 9 to 400 0 0 to 600 100 to 850 0 0 to 400 0 199 9 to 400 0 200 to 1 300 0 to 1 700 0 to 1 700 100 to 1 800 0 to 2 300 0 to 1 300 F 300 to 2 300 0 0 to 900 0...

Page 3: ...g using front panel keys Indication method 7 segment digital display and LEDs Character height PV 14 mm SV 9 5 mm Control output According to Output Unit see Output Unit Ratings and Characteristics Attach an Output Unit that is sold separately Remote SP input Current input 4 to 20 mA Input impedance 150 Ω Current Transformer input Connect an exclusive Current Transformer E54 CT1 or E54 CT3 Other f...

Page 4: ...gs Front panel NEMA4 for indoor use equivalent to IP66 Rear case IEC standard IP20 Terminals IEC standard IP00 Memory protection Non volatile memory number of writings 100 000 operations Weight Approx 320 g Mounting bracket approx 65 g EMC Emission Enclosure EN55011 Group 1 class A Emission AC Mains EN55011 Group 1 class A Immunity ESD EN61000 4 2 4 kV contact discharge level 2 8 kV air discharge ...

Page 5: ...to 250 VAC resistive load Voltage output NPN 40 mA at 12 VDC with short circuit protection NPN 20 mA at 24 VDC with short circuit protection PNP 20 mA at 24 VDC with short circuit protection Linear current output 4 to 20 mA permissible load impedance 600 Ω max resolution approx 2 600 0 to 20 mA permissible load impedance 600 Ω max resolution approx 2 600 Linear voltage output 0 to 10 VDC permissib...

Page 6: ...nection SSR output E53 S Linear voltage output E53 V34 Current output E53 C3 ON OFF voltage output E53 Q Relay output E53 R 0 to 10 V 4 to 20 mA 40 mA at 12 VDC 100 to 240 VAC 50 60 Hz Control output 1 Control output 2 Auxiliary output 1 Auxiliary output 2 Remote SP input 4 to 20 mA CT input 1 to 5 V 0 to 5 V 0 to 10 V 4 to 20 mA 0 to 20 mA Thermo couple Platinum resistance thermometer B 0 to 10 V...

Page 7: ...E5EK DRT E5EK DRT 7 ...

Page 8: ...40 6028 Japan Phone 81 6 949 6035 Fax 81 6 949 6069 ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No H98 E1 1 In the interest of product improvement specifications are subject to change without notice Printed in Japan 0398 1M 0398 a ...