E5EK-DRT
E5EK-DRT
5
Communication Characteristics
Conforms to DeviceNet communications protocol.
For details, refer to the CompoBus/D Operation Manual (W267) and E5EK CompoBus/D-type Digital Controller Operation Manual (H99).
Connection forms
Combination of multi-drop and T-branch connections (see note 1)
Communications baud rate
500 kbps, 250 kbps, or 125 kbps (set using the front panel keys)
Communications media
Special 5-wire cables (2 signal lines, 2 power lines, 1 shield line)
Communications distance
500 kbps
Network length (see note 2): 100 m max. (see note 3)
Drop line length: 6 m max.
Total drop line length: 39 m max.
250 kbps
Network length (see note 2): 250 m max. (see note 3)
Drop line length: 6 m max.
Total drop line length: 78 m max.
125 kbps
Network length (see note 2): 500 m max. (see note 3)
Drop line length: 6 m max.
Total drop line length: 156 m max.
Max. number of nodes
64 nodes (including Master)
Max. number of Slaves
63 Slaves
Error control checks
CRC error check, duplicate node address check
Note:
1. External Terminating Resistor is required.
2. Indicates the maximum distance between nodes.
3. The distance is less than 100 m when thin cables are used for the trunk lines.
Output Unit Ratings and Characteristics
Relay output
5 A at 250 VAC (resistive load)
SSR output
1 A at 75 to 250 VAC (resistive load)
Voltage output
NPN: 40 mA at 12 VDC
(with short-circuit protection)
NPN: 20 mA at 24 VDC
(with short-circuit protection)
PNP: 20 mA at 24 VDC
(with short-circuit protection)
Linear current output
4 to 20 mA, permissible load impedance: 600
Ω
max., resolution: approx. 2,600
0 to 20 mA, permissible load impedance: 600
Ω
max., resolution: approx. 2,600
Linear voltage output
0 to 10 VDC, permissible load impedance: 1 k
Ω
max., resolution: approx. 2,600
0 to 5 VDC, permissible load impedance: 1 k
Ω
max., resolution: approx. 2,600
Current Transformer Ratings
Dielectric strength
1,000 VAC (for 1 min)
Vibration resistance
50 Hz, 98 m/s
2
(10G)
Weight
E54-CT1: approx. 11.5 g; E54-CT3: approx. 50 g
Accessories (E54-CT3 only)
Armature: 2; Plug: 2
Heater Burnout Alarm
Max. heater current
Single-phase 50 A AC (see note 1)
Heater current value display accuracy
±
5% FS
±
1 digit max.
Heater burnout alarm setting range
0.1 to 49.9 A (in units of 0.1 A) (see note 2)
Min. detection ON time
190 ms (see note 3)
Note:
1. Use the K2CU-F
jj
A-
j
GS (with gate input terminals) for the detection of three-phase heater burnout.
2. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A.
3. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less than 190 ms.
This product has been tested by ODVA’s authorized Independent Test Lab and found to comply with
ODVA Conformance Test Software Version 2.0-1.00.