background image

Temperature Controllers

 E5CSV

5

1. Sensor Type Specification

Multi-input (Thermocouple/Platinum 

Resistance Thermometer) Models

• Using Thermocouple Sensors, Control Mode Switch 5: OFF

The control range is -20

°

C to +20

°

C of the input temperature 

range.

Note: 1.

The input indication range is the range that can be displayed for 

the control range (-99 to 1999). If the input is within the control 

range but exceeds the display range (-99 to 1999), values below 

-99 will be displayed as “

[[[

“ and values above 1,999 will be 

displayed as “

]]]

.”

2.

If unit is changed to 1 degree when the SP and alarm value for 

the temperature range are displayed in 0.1-units from 0.0 to 

199.9 or 0.0 to 99.9, the values will be multiplied by 10 (e.g., 0.5 

becomes 5). If the unit is changed in the reverse direction, the 

values will be divided by 10. After changing the range, set the 

SP and alarm value again.

• Using Platinum Resistance Thermometers, 

Control Mode Switch 5: ON

The control range is -20

°

C to +20

°

C of the input temperature 

range.

Note: 1.

The input indication range is the range that can be displayed for 

the control range (-99 to 1999). If the input is within the control 

range but exceeds the display range (-99 to 1999), values below 

-99 will be displayed as “

[[[

“ and values above 1,999 will be 

displayed as “

]]]

.”

2.

If unit is changed to 1 degree when the SP and alarm value for 

the temperature range are displayed in 0.1-units from 0.0 to 

199.9 or 0.0 to 99.9, the values will be multiplied by 10 (e.g., 0.5 

becomes 5). If the unit is changed in the reverse direction, the 

values will be divided by 10. After changing the range, set the 

SP and alarm value again.

ST (Self-tuning) Features

Executing AT (Auto-tuning)

Electrical Life Expectancy 
Curve for Relays (Reference 
Values)

Input

K

J

L

T

U

N

R

SP 
range

1,700

1,600

1,500

1,400

1,300

1,200

1,100

1,000

900

800

700

600

500

400

300

200

100

0

-100

1,700

1,300

1,300

850

850

400

400

199.9

199.9

199.9

0.0

0.0

0.0

0

-99

-99

-99

-99

-99

-99

Setting number

0

1

2

3

4

5

6

7

8

9

Input

Pt100

JPt100

SP 
range

1,000

900

800

700

600

500

400

300

200

100

0

-100

850

500

400

400

199.9

200

199.9

200

99

99

0.0

0

0

0.0

0

0

-99

-99

-99

-99

Setting number

0

1

2

3

4

5

6

7

8

9

Mode Key Display Order

If the SP falls outside the temperature 

range when the temperature range is 

changed, the SP will be displayed first. 

The SP will be changed automatically 

either to the minimum value or the 

maximum value, whichever is nearest.

If the alarm value falls outside the 

temperature range when the 

temperature range is changed, the 

alarm value will be displayed first. The 

alarm value will be changed 

automatically to the maximum value in 

the new temperature range.

PV

SP

Alarm value 1

Input shift value

Power ON

Press the       Key.

Press the       Key.

Press the       Key.

Press the       Key.

ST (self-tuning) is a function that finds PID constants by using step 

response tuning (SRT) when Controller operation begins or when 

the set point is changed. Once the PID constants have been 

calculated, ST is not executed when the next control operation is 

started as long as the set point remains unchanged. When the ST 

function is in operation, be sure to turn ON the power supply of the 

load connected to the control output simultaneously with or before 

starting Controller operation.

AT (auto-tuning) is executed by pressing the 

U

 Up and 

D

 Down 

Keys for at least 2 s while the PV is displayed. The deviation 

indicators flash during auto-tuning (AT) execution. AT will be 

cancelled by performing the same operation that AT is executing 

during AT operation. Flashing stops when AT is completed.

Note:

One of the deviation indicators (

▲■▼

) will flash.

AT execution in progress

Press for 

at least 2 s.

Press for 

at least 2 s.

U D

U D

AT execution in progress

AT execution

AT cancelled

500
300

100

50

30

10

5

3

1

0

1

2

3

4

5

6

Switching current (A)

Life (

×

 10

4

 operations)

E5CSV

250 VAC, 30 VDC 

(resistive load)

cos

φ

 = 1

6

Temperature Controllers

E5CSV

2. Operation Settings

Use the control mode switches ( 

 ) to change the 

control mode. (All switches are OFF for the default settings.)

Note:

The previous name Pt100 has been changed to JPt100 in 

accordance with revisions to JIS. The previous name J-DIN has 

been changed to L in accordance with revisions to DIN 

standards.

3. Alarm Modes

Select the number of the alarm mode switch 

 when changing 

the alarm mode. (The default is 2).

Note: 1.

No alarm. The alarm value (alarm operation display) will not 

be displayed when the setting is 0 or 9 even if the selection 

key is pressed. 

Alarm Setting Range 

X: 0 to FS (full scale); Y: Within temperature range

The value of X is the deviation setting for the SP (set point).

2.

Standby Sequence Function (The standby sequence 

operates when the power is turned ON.)

For details on the position of the temperature range switch, control mode switches, and alarm mode switch, refer to page 4. 

Function selection

1

2

3

4

5

6

ON/OFF 

PID

PID control

ON

ON/OFF control

OFF

Control 

period

2 s

ON

20 s

OFF

Direct/

reverse 

opera-

tion

Direct operation 

(cooling)

ON

Reverse operation 

(heating)

OFF

Input 

shift

display

Enabled

ON

Disabled

OFF

Tempera-

ture 

Sensor 

selection

Platinum 

resistance thermometer 

input

ON

Thermocouple 

input

OFF

Temper-

ature 

unit

°

F

ON

°

C

OFF

6

5

4

3

2

1

ON

6

5

4

3

2

1

ON

Set

value

Alarm type

Alarm output operation

0, 9

Alarm function OFF

OFF

1

Upper- and lower-

limit

2

Upper-limit

3

Lower-limit

4

Upper- and lower-

limit range

5

Upper- and lower-

limit with standby 

sequence (See note 

2.)

6

Upper-limit with 

standby sequence 

(See note 2.)

7

Lower-limit with 

standby sequence 

(See note 2.)

8

Absolute-value 

upper-limit

0 1

2

3

45

6

7

8

9

X

SP

X

ON

OFF

SP

X

ON

OFF

X

SP

ON

OFF

X

SP

X

ON

OFF

X

SP

X

ON

OFF

X

SP

ON

OFF

X

SP

ON

OFF

0

Y

ON

OFF

Upper-limit

alarm

SP

Lower-limit

alarm
Alarm

output

ON

OFF

Upper-limit

alarm

SP

Lower-limit

alarm

Alarm

output

ON

OFF

Rising Temperature

Dropping Temperature

Note:

Turn OFF the power before changing the DIP switch settings on the E5CSV. Each of the switch settings will be enabled after the power is 

turned ON.

8

Temperature Controllers E5CSV

Summary of Contents for E5CSV -

Page 1: ...Advanced Industrial Automation Perfect control Enhanced functionality Easy setting up E5CSV temperature controller Ready set g o ...

Page 2: ...mperature control in 4 simple steps The E5CSV temperature controller series is the enhanced successor to our E5CS series the most widely sold temperature controller that has established itself throughout the world as the ideal choice for simple cost effective temperature control P SV protection SW1 ON OFF PID control SW2 fast or slow process SW3 Heat or Cool SW4 Input shift ON OFF SW5 Thermocouple...

Page 3: ...e control requirements with only 4 models No expert knowledge needed to optimise performance because of Self and Auto Tuning functions Reduced chance of malfunction thanks to set value protection End user friendly since the menu only has 3 parameters Excellent legibility with a large 13 5 mm single line 3 5 digit 7 segment LED display Clear status overview thanks to PV SV deviation indicator outpu...

Page 4: ...er of alarms 1 1 alarm 3 Input type T Thermocouple platinum resistance thermometer multi input 4 Power supply voltage Blank 100 to 240 VAC D 24 VAC VDC 5 Terminal cover 500 Finger protection cover Ordering Information List of Models Accessories Order Separately Protective Front Cover 1 2 3 4 5 E5CSV 1T 500 Size Power supply voltage Number of alarm points Control output TC Pt multi input Incl termi...

Page 5: ...uence of voltage Hysteresis for ON OFF control 0 1 FS Proportional band P 1 to 999 C automatic adjustment using auto tuning self tuning Integral time I 1 to 1 999 s automatic adjustment using auto tuning self tuning Derivative time D 1 to 1 999 s automatic adjustment using auto tuning self tuning Alarm output range Absolute value alarm Same as the control range Other 0 to 100 FS Alarm hysteresis 0...

Page 6: ...ause measurement errors 2 Models with 100 to 240 VAC and 24 VAC VDC are separate Models using 24 VDC have no polarity Panel Cutout Dimensions 44 8 44 8 84 78 6 48 48 60 min L 48 N 2 5 1 0 Mounting side by side group mounting of N Controllers 45 0 6 0 45 0 6 0 45 0 6 0 L Tightening screws 48 76 5 7 5 Adapter for flush mounting Panel Y92F 30 Adapter for flush mounting 58 E5CSV Note 1 The recommended...

Page 7: ...d The ALM indicator lights when the alarm value 1 is being displayed PV SP Alarm Value Input Shift Display Alarm indicators ALM1 Alarm 1 Lights when the alarm 1 output is ON ALM2 Alarm 2 For future use Up Key Pressing the Up Key increases the SP alarm value display Keeping the Up Key pressed continues to increase the display value When the internal protect switch is ON press the Up Key while holdi...

Page 8: ...100 0 100 1 700 1 300 1 300 850 850 400 400 199 9 199 9 199 9 0 0 0 0 0 0 0 99 99 99 99 99 99 Setting number 0 1 2 3 4 5 6 7 8 9 Input Pt100 JPt100 SP range 1 000 900 800 700 600 500 400 300 200 100 0 100 850 500 400 400 199 9 200 199 9 200 99 99 0 0 0 0 0 0 0 0 99 99 99 99 Setting number 0 1 2 3 4 5 6 7 8 9 Mode Key Display Order If the SP falls outside the temperature range when the temperature ...

Page 9: ... ON OFF PID PID control ON ON OFF control OFF Control period 2 s ON 20 s OFF Direct reverse opera tion Direct operation cooling ON Reverse operation heating OFF Input shift display Enabled ON Disabled OFF Tempera ture Sensor selection Platinum resistance thermometer input ON Thermocouple input OFF Temper ature unit F ON C OFF 6 5 4 3 2 1 ON 6 5 4 3 2 1 ON Set value Alarm type Alarm output operatio...

Page 10: ...or Switch 2 OFF control period 20 s Quick Control Response Using an SSR Switch 2 ON control period 2 s 2 Set direct reverse operation for the output Performing Heating Control for Heaters Switch 3 OFF Performing Cooling Control for Freezers Switch 3 ON 6 5 4 3 2 1 ON Switch 1 OFF ON OFF control OFF ON Control output SP 6 5 4 3 2 1 ON OFF ON Control output SP 6 5 4 3 2 1 ON Switch 1 ON PID control ...

Page 11: ...input shift set the input shift value to h0 The shift range depends on the setting unit 5 Protect Switch When the protect switch is ON Up Key and Down Key operations are prohibited to prevent setting mistakes 6 5 4 3 2 1 ON Multi input Thermocouple Platinum Resistance Thermometer Control mode switch 5 OFF Multi input Thermocouple Platinum Resistance Thermometer Control mode switch 5 ON Set ting F ...

Page 12: ...ystems Programmable logic controllers Human machine interfaces Remote I O Motion Drives Motion controllers Servo systems Inverters Control Components Temperature controllers Power supplies Timers Counters Programmable relays Digital panel indicators Electromechanical relays Monitoring products Solid state relays Limit switches Pushbutton switches Low voltage switch gear Sensing Safety Photoelectri...

Reviews: