Model Number Structure
■
Model Number Legend
Models with Terminal Blocks
1. Output type
R: Relay
Q: Voltage for driving SSR
2. Number of alarms
1:
1 alarm
3. Input type
T:
Thermocouple/platinum resistance
thermometer (multi-input)
4. Power supply voltage
Blank: 100 to 240 VAC
D:
24 VAC/VDC
5. Terminal cover
500:
Finger protection cover
Ordering Information
■
List of Models
■
Accessories (Order Separately)
Protective Front Cover
1 2 3 4
5
E5CSV-
@
1 T
@
-5
00
Size
Power supply
voltage
Number of
alarm points
Control output
TC/Pt multi-input
Incl. terminal cover
1/16 DIN
48 x 48 x 78 mm
(W x H x D)
100 to 240 VAC
1
Relay
E5CSV-R1T-500
Voltage (for driving SSR)
E5CSV-Q1T-500
24 VAC/VDC
1
Relay
E5CSV-R1TD-500
Voltage (for driving SSR)
E5CSV-Q1TD-500
Type
Model
Hard Protective Cover
Y92A-48B
2
Temperature Controllers
E5CSV
Specifications
■
Ratings
■
Characteristics
Note: 1.
The following exceptions apply to thermocouples.
•
U, L: ±2
°
C ±1 digit max.
•
R: ±3
°
C ±1 digit max. at 200
°
C or less
2.
The following exceptions apply to platinum resistance
thermometers.
Input set values 0, 1, 2, 3 for E5CSV: 0.5% FS ±1 digit max.
Input set value 1 for E5CSV: 0.5% FS ±1 digit max.
Supply voltage
100 to 240 VAC, 50/60 Hz
24 VAC/VDC, 50/60 Hz
Operating voltage range
85% to 110% of rated supply voltage
Power consumption
5 VA
3 VA/2 W
Sensor input
Multi-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100
Control
output
Relay output
SPST-NO, 250 VAC, 3A (resistive load)
Voltage output (for driving the SSR)
12 VDC, 21 mA (with short-circuit protection circuit)
Control method
ON/OFF or 2-PID (with auto-tuning)
Alarm output
SPST-NO, 250 VAC, 1A (resistive load)
Setting method
Digital setting using front panel keys (functionality set-up with DIP switch)
Indication method
3.5 digit, 7-segment digital display (character height: 13.5 mm) and deviation indicators
Other functions
•
Setting change prohibit (key protection)
•
Input shift
•
Temperature unit change (
°
C/
°
F)
•
Direct/reverse operation
•
Control period switching
•
8-mode alarm output
•
Sensor error detection
Ambient temperature
-10 to 55
°
C (with no condensation or icing)
Ambient humidity
25% to 85%
Storage temperature
-25 to 65
°
C (with no condensation or icing)
Setting accuracy
Thermocouple (See note 1.):
(±0.5% of indication value or ±1
°
C, whichever is greater) ±1 digit max.
Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1
°
C, whichever is greater) ±1 digit max.
Indication accuracy
(ambient temperature of 23
°
C)
Influence of temperature
R thermocouple inputs:
(±1% of PV or ±10
°
C, whichever is greater) ±1 digit max.
Other thermocouple inputs:
(±1% of PV or ±4
°
C, whichever is greater) ±1 digit max.
Platinum resistance thermometer inputs: (±1% of PV or ±2
°
C, whichever is greater) ±1 digit max.
Influence of voltage
Hysteresis (for ON/OFF control)
0.1% FS
Proportional band (P)
1 to 999
°
C (automatic adjustment using auto-tuning/self-tuning)
Integral time (I)
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning
Derivative time (D)
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)
Alarm output range
Absolute-value alarm: Same as the control range
Other:
0% to 100% FS
Alarm hysteresis:
0.2
°
C or
°
F (fixed)
Control period
2/20 s
Sampling period
500 ms
Insulation resistance
20 M
Ω
min. (at 500 VDC)
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity
Vibration
resistance
Malfunction
10 to 55 Hz, 20 m/s
2
for 10 min each in X, Y, and Z directions
Destruction
10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions
Shock resistance
Malfunction
100 m/s
2
min., 3 times each in 6 directions
Destruction
300 m/s
2
min., 3 times each in 6 directions
Life expectancy
Electrical
100,000 operations min. (relay output models)
Weight
Approx. 120 g (Controller only)
Degree of protection
Front panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00
Memory protection
EEPROM (non-volatile memory) (number of writes: 1,000,000)
EMC
EMI Radiated:
EN 55011 Group 1 Class A
EMI Conducted:
EN 55011 Group 1 Class A
ESD Immunity:
EN 61000-4-2: 4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Radiated Electromagnetic Field Immunity:
EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)
10 V/m (900 MHz pulse modulated)
Conducted Disturbance Immunity:
EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)
Noise Immunity (First Transient Burst Noise): EN 61000-4-4
Burst Immunity:
2 kV power-line (level 3), 1 kV I/O signal-line (level 3)
Surge Immunity:
EN 61000-4-5: Power line:
Normal mode 1 kV; Common mode 2 kV
Output line (relay output): Normal mode 1 kV; Common mode 2 kV
Voltage Dip/Interrupting Immunity:
EN 61000-4-11 0.5 cycle, 100% (rated voltage)
Approved standards
UL 61010C-1 (listing), CSA C22.2 No.1010-1
Conformed standards
EN 61326, EN 61010-1, IEC 61010-1, VDE 0106 Part 100 (finger protection), when the terminal cover is mounted.