background image

I-10

Analogue Temperature Controller 

E5C2

Accessories (Order Separately)

Protective Cover Y92A-48

The protective cover protects the front panel, particularly the setting
section, against dust, dirt, and water drip. It also prevents the set val-
ues from being altered due to accidental contact with the setting
keys.

Installation

Connections

Input

Connect a thermocouple, the E52-THE

@

 Thermistor or platinum

resistance thermometer to the E5C2 as shown in the following illus-
tration.

Output

If the load circuit is a heating control system, be sure to connect the
load to terminals 4 and 5. If the load circuit is a cooling control sys-
tem, be sure to connect the load to terminals 4 and 6. If the heating
control system is connected to terminals 4 and 6 or the cooling con-
trol system is connected to terminals 4 and 5, the temperature of the
heating control system or cooling control system will be abnormal
and a serious accident may result.

If the E5C2 is in frequent operation, such as proportional operation,
add an appropriate external relay to the E5C2 by considering the
capacity of the load and the life of the relay.

Power Supply

If a single power supply is used for the E5C2 and the load, the supply
voltage of the power supply may vary greatly when the load is open
or closed if the capacity of the power supply is not large enough.
Make sure that the capacity of the power supply is large enough so
that the supply voltage range will be always from 90% to 110% of the
rated supply voltage.

The E5C2 operates at either 50 or 60 Hz.

P2CF-08 Front Connecting Socket

Mounting Holes

70 max.

Eight, M3.5 x 7.5 sems

50 max.

20 max.

Two, 4.5 dia. or Two, M4

P3G-08 Back Connecting Socket (for Flush Mounting)

27 dia.

Two, 
4.5-dia. 
holes

Terminal Arrangement/ 
Internal Connections 
(Top View)

Note: 

Can also be

 

mounted to a 
DIN track.

Terminal Arrangement/ 
Internal Connections 
(Bottom View)

Note:

 A finger-protection model (P2CF-08-E) is also available.

Note:

 A Protective Cover for finger protection (Y92A-48G) is also available.

Appearance

Model

Y92A-48B

Thermocouple input

Relay output

Thermistor input

Platinum resistance 
thermometer input

Power supply 
100/110, 200/220, 
110/120, 220/240 VAC 
50/60 Hz

Summary of Contents for E5C2

Page 1: ...ter PT100 G Thermistor THE 5 Special type Blank Standard type D DIN Special types Ordering Information Temperature Controllers Note When placing an order specify the standard temperature range and supply voltage in addition to the model number e g E5C2 R20K 0 C to 200 C 100 110 VAC Accessories Order Separately 1 2 3 4 5 E5C2 Setting method Indication method Control mode Output Model Thermocouple P...

Page 2: ...to 1 200 25 0 to 200 5 0 to 300 10 0 to 400 10 50 to 50 2 20 to 80 2 0 to 50 1 0 to 100 2 0 to 200 5 0 to 300 10 0 to 400 10 50 to 50 2 6 kΩ at 0 C 0 to 100 2 6 kΩ at 0 C 50 to 150 2 30 kΩ at 0 C F 32 to 392 10 32 to 572 20 32 to 752 20 32 to 1 112 40 32 to 1 472 50 32 to 1 832 50 32 to 2 192 50 32 to 392 10 32 to 572 20 32 to 752 20 32 to 212 5 32 to 392 10 Setting accuracy 2 FS max Hysteresis Ap...

Page 3: ... lit OFF 93 1 0 141 1 0 189 1 0 237 1 0 285 1 0 N 2 3 4 5 6 L 48 x 48 44 8 x 44 8 Panel Cutout Note 1 Recommended panel thickness is 1 to 4 mm 2 Close side by side mounting is possible in a single direction Panel Y92F 30 Flush mounting adapter Tightening screw 96 see note Note 109 mm for US08 Back Connecting Socket Terminal Arrangement Bottom View Dimensions with Flush mounting Adapter Accessory a...

Page 4: ...portional operation add an appropriate external relay to the E5C2 by considering the capacity of the load and the life of the relay Power Supply If a single power supply is used for the E5C2 and the load the supply voltage of the power supply may vary greatly when the load is open or closed if the capacity of the power supply is not large enough Make sure that the capacity of the power supply is l...

Page 5: ... 08 can be wired in the same way as the P2CF 08 Dismounting If flush mounted loosen the screw of the adapter and disengage the hooks for dismounting Temperature Setting Do not turn the temperature setting knob of the E5C2 with excessive force otherwise the stopper of the knob may break Others Do not remove the housing of the E5C2 otherwise the housing may break To clean the surface of the E5C2 use...

Page 6: ...he interest of product improvement specifications are subject to change without notice ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No H081 E1 02 ...