Analogue Temperature Controller 

E5C2

Specifications

Ratings

Note:

Specify either 100/110/120 VAC or 200/220/240 VAC when ordering.

Input Ranges

Note: 1.

Values in (  ) are the minimum unit.

2.

Values in (  ) are the thermistor resistive value.

Characteristics

Note: 1.

No reset function is incorporated by any E5C2 model with ON/OFF control.

2.

The model number of the special watertight cover conforming to IP66, NEMA4 is Y92A-48B.

Supply voltage

100/110/120 VAC (common), 200/220/240 VAC (common) (See note.) 
50/60 Hz (common)

Operating voltage range

90% to 110% of rated supply voltage

Power consumption

Approx. 2 VA

Input

Thermocouple (with sensor burnout detection circuit), platinum resistance thermometer, or thermistor

Control mode

ON/OFF or P control

Setting method

Analog setting

Indication method

No indication

Control output

Relay output: SPDT, 3 A at 250 VAC, resistive load (switching capacity: 330 VA)

Input

Thermocouple

Platinum resistance 

thermometer

Thermistor (see note 2)

K (CA)

Chromel vs. alumel

L (IC)

Iron vs. constantan

Pt100

THE

Range

°

C

0 to 200 (5),
0 to 300 (10),
0 to 400 (10),
0 to 600 (20),
0 to 800 (20),
0 to 1,000 (25),
0 to 1,200 (25)

0 to 200 (5),
0 to 300 (10),
0 to 400 (10)

–50 to 50 (2),
–20 to 80 (2),
0 to 50 (1),
0 to 100 (2),
0 to 200 (5),
0 to 300 (10),
0 to 400 (10)

–50 to 50 (2) (6 k

 at 0

°

C),

0 to 100 (2) (6 k

 at 0

°

C),

50 to 150 (2) (30 k

 at 0

°

C)

°

F

32 to 392 (10),
32 to 572 (20),
32 to 752 (20),
32 to 1,112 (40),
32 to 1,472 (50),
32 to 1,832 (50),
32 to 2,192 (50)

32 to 392 (10),
32 to 572 (20),
32 to 752 (20)

32 to 212 (5),
32 to 392 (10)

---

Setting accuracy

±

2% FS max.

Hysteresis

Approx. 0.5% FS (fixed)

Proportional band

3% FS (fixed)

Control period

Approx. 20 s

Reset range (see note 1)

±

1% FS min.

Insulation resistance

20 M

 min. (at 500 VDC)

Dielectric strength

2,000 VAC, 50/60 Hz for 1 min between charged terminals and uncharged metallic parts

Vibration resistance

Malfunction: 10 to 55 Hz, 0.15-mm single amplitude for 10 min each in X, Y, and Z directions
Destruction: 16.7 Hz, 2-mm double amplitude for 2 hrs each in X, Y, and Z directions

Shock resistance

Malfunction: 147 m/s

2

, 3 times each in 6 directions

Destruction: 294 m/s

2

, 3 times each in 6 directions

Life expectancy

Electrical:

100,000 operations min. (3 A at 110 VAC, resistive load)

Ambient temperature

Operating: –10

°

C to 55

°

C (with no icing or condensation)

Ambient humidity

Operating: 45% to 85%

Degree of protection

Front panel: IEC standard IP40 (see note 2)
Terminals:

IEC standard IP00

Weight

Approx. 200 g (with flush-mounting adapter)

Summary of Contents for E5C2

Page 1: ...ter PT100 G Thermistor THE 5 Special type Blank Standard type D DIN Special types Ordering Information Temperature Controllers Note When placing an order specify the standard temperature range and supply voltage in addition to the model number e g E5C2 R20K 0 C to 200 C 100 110 VAC Accessories Order Separately 1 2 3 4 5 E5C2 Setting method Indication method Control mode Output Model Thermocouple P...

Page 2: ...to 1 200 25 0 to 200 5 0 to 300 10 0 to 400 10 50 to 50 2 20 to 80 2 0 to 50 1 0 to 100 2 0 to 200 5 0 to 300 10 0 to 400 10 50 to 50 2 6 kΩ at 0 C 0 to 100 2 6 kΩ at 0 C 50 to 150 2 30 kΩ at 0 C F 32 to 392 10 32 to 572 20 32 to 752 20 32 to 1 112 40 32 to 1 472 50 32 to 1 832 50 32 to 2 192 50 32 to 392 10 32 to 572 20 32 to 752 20 32 to 212 5 32 to 392 10 Setting accuracy 2 FS max Hysteresis Ap...

Page 3: ... lit OFF 93 1 0 141 1 0 189 1 0 237 1 0 285 1 0 N 2 3 4 5 6 L 48 x 48 44 8 x 44 8 Panel Cutout Note 1 Recommended panel thickness is 1 to 4 mm 2 Close side by side mounting is possible in a single direction Panel Y92F 30 Flush mounting adapter Tightening screw 96 see note Note 109 mm for US08 Back Connecting Socket Terminal Arrangement Bottom View Dimensions with Flush mounting Adapter Accessory a...

Page 4: ...portional operation add an appropriate external relay to the E5C2 by considering the capacity of the load and the life of the relay Power Supply If a single power supply is used for the E5C2 and the load the supply voltage of the power supply may vary greatly when the load is open or closed if the capacity of the power supply is not large enough Make sure that the capacity of the power supply is l...

Page 5: ... 08 can be wired in the same way as the P2CF 08 Dismounting If flush mounted loosen the screw of the adapter and disengage the hooks for dismounting Temperature Setting Do not turn the temperature setting knob of the E5C2 with excessive force otherwise the stopper of the knob may break Others Do not remove the housing of the E5C2 otherwise the housing may break To clean the surface of the E5C2 use...

Page 6: ...he interest of product improvement specifications are subject to change without notice ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 Cat No H081 E1 02 ...

Reviews: