background image

6

E4PA-N

 

Ultrasonic Displacement Sensor

Safety Precautions

Precautions for Safe Use

Design

Power Supply

If possible, use a power supply without overcurrent detection. This 
Sensor uses a DC-DC converter in the power supply circuit. If the 
power supply has overcurrent detection, the protective circuit may be 
activated by the inrush current.
Recommended power supply: OMRON S82-series Power Supply
(Capacity: 15 W min.)

Wiring

Power Supply Voltage

Do not exceed the operating voltage range. Using a higher voltage 
or using an AC power supply (100 VAC or more) for a DC Sensor 
can cause explosion or burning.

Faulty Wiring

Be careful not to make wiring mistakes such as reversing the power 
supply polarity. Faulty wiring can cause explosion or burning.

Operating Environment

Do not use the Sensor in an environment where inflammable or 
explosive gas is present.

Others

• Do not attempt to disassemble, repair, or modify any Units. Any at-

tempt to do so may result in malfunction, fire, or electric shock.

• Dispose of Sensors as industrial waste.

Precautions for Correct Use

Design

Sensor Ambient Temperature and Humidity

The acoustic velocity generally fluctuates approximately 0.17% with 
each 1

°

C of temperature change. For example, if the ambient tem-

perature increases from 20 to 40

°

C, then the acoustic velocity will 

increase by 3.5%. Moreover, the acoustic velocity will increase by 
2% in dry air compared with air with 100% humidity. Test the environ-
mental conditions where the Sensor will actually be used.

Mutual Interference

The mutual interference prevention function can be used with up to 
five Sensors in close proximity. Separate the Sensors as specified in 
the following table when using two or more Sensors in close proximity 
without using the mutual interference prevention function.

Parallel Arrangement

Note:

The values shown in the following table are examples for ref-
erence only. The actual values will vary depending on the sur-
face conditions of the sensing object, and on the ultrasonic
waves that are reflected. Moreover, if the sensing object is in-
clined, the Y value in the table will be increased further.

Facing Arrangement

Sensing Object

• The sensing object may be solid, liquid, or powder, and the detec-

tion capability of the Sensor will vary depending on the surface con-
ditions of the object. If the surface irregularities are no more than 0.2
mm, then the specified sensing distance will apply. Materials such
as fine powder, felt, cotton, and other materials that absorb sound
should be tested before using the Sensor.

• If the surface temperature of the sensing object is over 100

°

C, there

will be very little ultrasonic reflection. Conduct tests before using the
Sensor.

Influence of Sensing Angle

Ultrasonic Displacement Sensors can detect solid, liquid, or powder 
sensing objects, but the surface of the sensing object will affect the 
measurement. Dented surfaces or sensing objects with an angled 
surface require a tilt angle within 3

°

 max. to achieve accurate sens-

ing.

Installation

Mounting the Sensor

The Sensor must be mounted using the nuts provided, and tightened 
to a torque of 15 N·m max.

If the Sensor malfunctions due to noise, insert insulation between 
the Sensor and the mounting base (metal).

Atmosphere

• To ensure reliability and long service life, do not use the Sensor out-

doors or in places that exceed the rated temperature.

• Ultrasonic sensors use air as the transmission medium, so if there

are local temperature differences there may be malfunctioning due
to reflection and refraction at the boundaries, and the detection dis-
tances change where wind blows. Therefore, the Sensor should not
be used near equipment such as forced-air ventilators.

• Jets from air nozzles include various frequencies, so they can affect

the Sensor and should not be used nearby.

• Water drops on the Sensor surface shorten the sensing distance.

Wiring Considerations

Cable Length

The cable must be no longer than 10 m.

High-voltage Lines

Do not lay power supply cable for the E4PA-N Ultrasonic Displace-
ment Sensor together with high-voltage lines or power lines. Placing 
them in the same conduit or duct may result in interference, damage, 
or malfunction.

Model

Y

E4PA-LS50-M1-N

0.3 m min.

E4PA-LS200-M1-N

1 m min.

E4PA-LS400-M1-N

2 m min.

E4PA-LS600-M1-N

2.5 m min.

Y

E4PA-N

E4PA-N

Sensing object

Sensing object

Model

Y

E4PA-LS50-M1-N

2 m min.

E4PA-LS200-M1-N

8 m min.

E4PA-LS400-M1-N

16 m min.

E4PA-LS600-M1-N

25 m min.

X

E4PA-N

E4PA-N

3

°

3

°

E4PA-N

Sensing object

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Downloaded from

Arrow.com.

Summary of Contents for E4PA-LS200-M1-N

Page 1: ...cu racy of 1 mm or better has been achieved A setting plug with a temperature compensation function makes it easy to set the sensing range The sensing range can be set by the Setting Plug which is inc...

Page 2: ...180 kHz Approx 85 kHz Approx 65 kHz Response time 63 ms max 195 ms max 440 ms max 850 ms max Power supply voltage 10 to 30 VDC ripple p p 10 max Power consumption 1 800 mW max Analog output Current o...

Page 3: ...ance Y mm Distance X m Y X 1 000 800 600 400 200 0 200 400 600 800 1 000 1 2 3 4 5 6 7 Distance Y mm Distance X m 1 4 2 3 5 E4PA N 0 V Ri 500 Rv 1 000 3 1 2 4 5 10 to 30 V 4 to 20 mA 0 to 10 V Mutual...

Page 4: ...ctor for Sensor I O 5 poles Notch on Sensor RUN indicator yellow Power indicator green RUN indicator yellow Error indicator red Position Function A1 Nearest sensing point A1 A2 Farthest sensing point...

Page 5: ...notch on the Sensor with the A2 triangular mark on the Setting Plug The power indicator green and the A2 RUN indicator yellow will flash showing that the far distance has been correctly set 6 Remove...

Page 6: ...etec tion capability of the Sensor will vary depending on the surface con ditions of the object If the surface irregularities are no more than 0 2 mm then the specified sensing distance will apply Mat...

Page 7: ...indicator red 36 See note 2 25 22 25 5 12 128 27 5 40 dia M30 1 5 M12 1 Two clamping nuts Indicator See note Setting Plug Note 1 RUN indicator yellow Power indicator green Error indicator red 2 This...

Page 8: ...t to change without notice ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into ounces multiply by 0 03527 D099 E1 OMRON Corporation Ind...

Page 9: ...not described in this catalog Nuclear energy control systems combustion systems railroad systems aviation systems medical equipment amusement machines vehicles safety equipment and installations subj...

Reviews: