A-432

Advanced Photoelectric Sensors

Twin-output models

TEACH

Setting the 
operating mode

Changing the 
operating mode

L ON

D ON

Sensing function

Displayed as "F".

Standard

 (factory-set)

Area

Super-long distance

Super-high speed

Digital incident level display

OFF

 (Factory-set)

Peak

Bottom

Timer function

Displayed as "t".

0

 (Factory-set)

Adjustable in 1-ms units for 0 
to 20 ms and in 5-ms units 
for higher.

200

Flashing setting

Displayed as "L".

OFF

 (Factory-set)

ON

Hold setting

Displayed as "H".

Reversing display

Standard

 (Factory-set)

Reverse

(Factory setting)

L ON

D ON

(Factory setting)

Setting Functions in SET Mode

4

The operating mode for the channel set 
with the channel-selection switch can be 
changed.

SET

CH1

CH2

Changed using the channel-selection switch

Channel 1

Channel 2

2s

MODE

TEACH

TEACH

TEACH

TEACH

TEACH

TEACH

@

 Area Sensing

Area sensing is possible using the threshold values 
for channels 1 and 2.
· If channel 1 is set to L/ON, output turns ON when 

the incident level is between the thresholds.

· If channel 1 is set to D/ON, output turns OFF 

when the incident level is between the thresholds.

The result is output to control output 1.
(Control output 2 is always OFF.)

2s

2s

2s

TEACH

TEACH

TEACH

MODE

MODE

MODE

TEACH

TEACH

TEACH

TEACH

2s

TEACH

TEACH

MODE

Set the mode selector 

to         .

SET

(A)

(B)

(A)

(B)

Display orientation 
setting

There are four different sensitivity settings.

Downloaded from 

Elcodis.com

 

electronic components distributor

 

Summary of Contents for E3X-DA-N series

Page 1: ...vel of LEDs used in sensors is prone to deteriorate with time and as a result detection becomes unstable Using the APC auto power control circuit for the first time as the fiber sensor the E3X DA N se...

Page 2: ...W 1800mW This ECO label is indicated on products that meet the environmental standards established by OMRON Eco mode Setting teaching fine adjustment can be made at the fiber front end The Mobile Cons...

Page 3: ...Connector order separately Control output Model NPN output PNP output Standard models Master E3X CN11 ON OFF output E3X DA6 E3X DA8 Slave E3X CN12 Monitor output models Master E3X CN21 ON OFF output...

Page 4: ...s ac cessories Power supply provid ed by chargeable battery E3X MC11 C1 Mobile Console E3X MC11 H1 Head E39 Z12 1 Cable 1 5 m Straight connector L shaped connector In general amplifier units and conne...

Page 5: ...ively Standard mode Operation reset 1 ms each 2 ms for operation and reset respectively Super long dis tance mode 4 ms for operation and reset respectively 7 ms for operation and reset respectively Se...

Page 6: ...A9 E3X DAB8 E3X DAG8 E3X DAH8 E3X DA44V E3X DA8TW Connection method Connector type M8 connector Connector Weight Packed state Approx 55 g 65 g Approx 55 g Type Standard models Monitor out put models M...

Page 7: ...0 1260 240 1680 1 mm dia 0 01 mm dia E32 ET21R 50 60 80 30 40 50 E32 T16WR 580 690 910 350 450 580 0 3 mm dia 3 3 The digital value is 1000 and the value can be detected in each detection area Refer t...

Page 8: ...mode 270 500 s 1 2 4 10 20 30 50 100 200 ms selectable Both side edge detection mode 570 s 1 2 4 10 20 30 50 100 200 400 ms selectable Func tions Timer function OFF delay timer for L ON ON delay time...

Page 9: ...2 4 3 T Incident light No incident light ON OFF ON OFF Operate Release Operation Indicator orange Between brown and black Output transistor Load relay Incident light No incident light ON OFF ON OFF Op...

Page 10: ...transistor Load relay T Incident light No incident light ON OFF ON OFF Operate Release Operation Indicator orange Between blue and black Output transistor Load relay Main circuit Load Load Monitor out...

Page 11: ...Monitor output Orange E3X DA N 12 to 24 VDC 12 VDC 80 mA K3NX VD2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Use this service power supply for the Sensor with reference to the power consumption of eac...

Page 12: ...ging the Display RUN Mode Manual Tuning Fine Sensitivity Adjustment in ADJ Mode Perform fine sensitivity adjustment after teaching and manual tuning without using the teaching function in the way show...

Page 13: ...pper limit that is lower than the lower limit Setting lower limit for monitoring Alternates between A LO and setting value Factory setting Note It is not possible to set an lower limit that is lower t...

Page 14: ...rating mode for the channel set with the channel selection switch can be changed SET CH1 CH2 Changed using the channel selection switch Channel 1 Channel 2 2s MODE TEACH TEACH TEACH TEACH TEACH TEACH...

Page 15: ...to SET 2 Press the SET button once about 1 s 3 Setting is completed when the red level indicators are turned ON They then return to the digi tal incident level display 4 Set to RUN mode 5 The thresho...

Page 16: ...ration mode and area de tection cannot be set Adjustment Mutual interference prevention function The digital display value may vary due to the light from the other sensor In that case low the sensitiv...

Page 17: ...onnectors without separating them from other amplifier units first Mounting End Plate PFP M Depending on the installation an amplifier unit may move dur ing operation In this case use an end plate Bef...

Page 18: ...t level display Threshold level display With Mounting Blanket Attached Mounting Holes prewired E3X DA11 N E3X DAG11 N E3X DA21 N E3X DAH11 N E3X DAB11 N E3X DAB41 N E3X DA41 N E3X DAG41 N E3X DA51 N E...

Page 19: ...tached Mounting Holes Amplifier units with Cables Twin output Models E3X DA11TW E3X DA41TW 10 64 3 3 8 Two 2 4 dia 10 7 9 9 3 4 38 6 13 3 9 5 1 1 7 4 2 6 2 1 7 36 7 14 31 5 5 5 Hole for optical commun...

Page 20: ...ts M8 Connectors Water resistant Models E3X DA14V E3X DA44V 10 64 3 3 8 Two 2 4 dia 10 7 9 9 3 4 38 6 13 3 9 5 1 1 7 4 2 6 2 1 7 36 7 14 31 5 5 5 Hole for optical communications 1 8 13 05 Incident lev...

Page 21: ...insulated round cable conductor cross sectional area 0 2 mm insulation diameter 1 1 mm is used E3X CN22 A 4 dia 2 conductor vinyl insulated round cable conductor cross sectional area 0 2 mm insulatio...

Page 22: ...use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control systems combustion systems railroad systems a...

Reviews: