E2K-L

 

Liquid Level Sensor

Characteristics

*

  In the following cases, stable detection may not be possible and so be sure to confirm correct operation in the actual installation before use.

1.  If the dielectric constant or conductivity of the liquid is low.

2.  If the capacity of the liquid is small, or if the pipe diameter is so small or the walls of the pipe are so thick that the amount by which the

capacity changes in proportion to the level of the liquid is small.

3.  If there are a lot of bubbles or a highly viscous liquid film residue on the inside walls of the pipe, or if there is a build up of dirt on the inner or

outer walls of the pipe.

Output Circuit Diagrams

Item

Model number

E2K-L13MC1

E2K-L26MC1

Applicable 
pipes

Material

Non-metal

Size

External 
diameter

8 to 11 mm-dia.

12 to 26 mm-dia.

Wall 
thickness

1 mm max.

1.5 mm max.

Sensing object

Liquid 

*

Repeat accuracy

±

0.2 mm max.

Hysteresis (reference value only; 
varies with pipe size and solution) 

0.6 to 5 mm

0.3 to 3 mm

Supply voltage 
(operating voltage range)

12 to 24 VDC, 10% max. ripple (10.8 to 30 VDC)

Current consumption

12 mA max.

Control 
output

Switching capacity

100 mA max.

Residual voltage

1 V max. (for load current of 100 mA cable length of 2 m)

Detection position of liquid 
surface

Notch position (For details, refer to Sensitivity Adjustment on page 6.)

Indicator

Operation indicator (orange)

Ambient temperature

Operating: 0 to 55

°

C; Storage: 

-

10 to 65

°

C (with no icing or condensation)

Ambient humidity

Operating/storage: 25% to 85% (with no condensation)

Temperature influence

In the range 0 to 55

°

C: Detection level at 23

°

±

4 mm

 (with distilled water or 20% concentration salt water)

(

±

6 mm with E2K-L13MC1 for distilled water in pipe of diameter 8 mm)

Voltage influence

At the rated power supply voltage 

±

10%: Detection level at rated power supply voltage 

±

0.5 mm

Insulation resistance

50 M

W

 min. (at 500 VDC) between charged parts and case

Dielectric strength

500 VAC, 50/60 Hz for 1 minute between charged parts and case

Vibration resistance (destruction)

10 to 55 Hz with a 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions

Shock resistance (destruction)

500 m/s

2

 for 3 times each in X, Y, and Z directions

Enclosure rating

IEC60529 IP66

Connection method

Pre-wired (standard cable length: 2 m)

Weight (packed state)

Approx. 70 g

Material

Case, cover

Heat-resistant ABS resin

Cable clamp

NBR

Accessories

2 binding bands, 4 slip-prevention tubes, instruction manual

Output 

format

Model number

Timing chart

Output circuit

NO

E2K-L13MC1
E2K-L26MC1

Yes

No

Operates

Releases

ON

OFF

Load 
(brown-black)

Operation indicator 
(orange)

Liquid surface

brown

+V

0V

black

100 mA max. (load current)

blue

Main circuit

Load

Summary of Contents for E2K-L

Page 1: ...4 7107 Regional Headquarters OMRON EUROPE B V Sensor Business Unit Carl Benz Str 4 D 71154 Nufringen Germany Tel 49 7032 811 0 Fax 49 7032 811 199 OMRON ELECTRONICS LLC 1 East Commerce Drive Schaumburg IL 60173 U S A Tel 1 847 843 7900 Fax 1 847 843 8568 OMRON ASIA PACIFIC PTE LTD 83 Clemenceau Avenue 11 01 UE Square 239920 Singapore Tel 65 835 3011 Fax 65 835 2711 OMRON CHINA CO LTD BEIJING OFFIC...

Page 2: ...ers allowing reductions in stock requirements Binding band Slip prevention tube 12 step sensitivity adjuster Operation indicator 20mm 24mm 33mm Little influence from bubbles Not influenced by the color of the pipe or liquid Use for pipes with diameters in the range 8 to 11 mm or 12 to 26 mm Conforms to CE standards Conforms to CE standards an indispensable requirement for semiconductor manufacturi...

Page 3: ... pipe or liquid Available in 8 to 11 mm dia and 12 to 26 mm dia models to enable sensing for a wide range of pipe diameters Space saved with built in amplifier Sensing method Applicable pipe diameters Appearance Output format Model number Electrostatic capacity method 8 to 11 mm dia NPN open collector output NO E2K L13MC1 12 to 26 mm dia E2K L26MC1 Liquid surface level detection ...

Page 4: ...on of liquid surface Notch position For details refer to Sensitivity Adjustment on page 6 Indicator Operation indicator orange Ambient temperature Operating 0 to 55 C Storage 10 to 65 C with no icing or condensation Ambient humidity Operating storage 25 to 85 with no condensation Temperature influence In the range 0 to 55 C Detection level at 23 C 4 mm with distilled water or 20 concentration salt...

Page 5: ...ence of Surrounding Objects Units mm Mutual Interference When installing 2 or more Sensors in series in parallel or facing each other be sure that they are separated by at least the distances shown below Mutual Interference Units mm The detection level for the top Sensor may change when the detection level for the bottom Sensor is set Be sure to set the detection level for the bottom Sensor first ...

Page 6: ...el to be detected After the Sensor is mounted adjust the detecting sensitivity using the 12 step sensitivity adjuster in the way shown below Note 1 While adjusting the sensitivity do not put your hand on the Sensor and make sure that the cable is properly secured Failure to observe these points may affect the detection level Note 2 When using more than one Sensor e g to detect for upper and lower ...

Page 7: ...s in temperature because this will shorten the service life Miscellaneous Drift may occur when the power supply is turned ON If the dielectric constant of the liquid is low the detection level of the liquid may be 2 to 3 mm higher than the set level for approximately 20 minutes after power is turned ON Dimensions Units mm Correct Use 20 5 43 41 33 R6 5 24 11 5 1 5 6 5 1 3 5 6 6 Sensitivity adjuste...

Reviews: