Indicators
•
The operation indicator is lit when the sensing object is near the
sensing distance.
•
The stability indicator is lit when the sensing object position is
less than 95% or more than 107% of the sensing distance. The
stability indicator indicates the range in which each sensing
object is detected smoothly.
Stable non-
sensing area
Operation indicator
(red)
Not lit
Stability indicator
(green)
Stable sensing
area
Lit
Set distance x
approx. 1.07
(see note)
Lit
Lit
Set distance
Set distance x
approx. 0.93
(see note)
Not lit
Note:
Replace the 1.07 value with 1.04 and the 0.93 value with
0.96 for the E2C-X2A.
Sensitivity Adjustment
1. Initial Adjustment
After the E2C Amplifier Unit is turned on, adjust the following Sensor according to the status of each indicator without a sensing object.
•
Status of
Indicators
•
Adjustment
E2C-JC4A Multi-function Model
E2C-A
j
4A Multi-function Model
Lit
Operation
A
B
C
D
Sensitivity
Operation
Sensitivity
Sensitivity
E2C-G
j
4
j
Single-function Model
E2C-WH4A(F) Multi-function Model
No adjustment is required.
Not Lit
Turn the sensitivity adjuster coun-
terclockwise until the operation in-
dicator turns off.
Lit
Lit
Lit
Lit
Not Lit
Not Lit
Not Lit
Not Lit
Indicator
mode
•
Status of Indicators
•
Adjustment
Turn the sensitivity adjuster
counterclockwise so that the op-
eration indicator turns off and the
stability indicator is lit (i.e., the
E2C Amplifier Unit is in mode D).
No adjustment is required.
2. Sensitivity Adjustment
Item
E2C-G
j
4
j
Single-function Model
E2C-WH4A(F) Multi-function Model
Step
1
2
3
1
2
3
Sensing
Sensitivity
adjuster
---
---
---
---
Adjustment
Obtain the
sensing distance
X from the set
distance S
divided by 0.8.
Determine S so
that X will be
less than the
maximum
sensing
distance.
Locate the
Sensor so that
the distance
between the
Sensor and
sensing object is
X. Turn the
sensitivity
adjuster
clockwise until
the operation
indicator is lit.
Return the
Sensor to the
previous position
so that the
distance
between the
Sensor and
sensing object is
S. Secure the
position of the
Sensor to
complete the
sensitivity
adjustment.
Obtain the
sensing distance
X from the set
distance S
divided by 0.8.
Determine S so
that X will be
less than the
maximum
sensing
distance.
Locate the
Sensor so that
the distance
between the
Sensor and
sensing object is
X. Turn the
sensitivity
adjuster
clockwise until
the operation
indicator is lit.
Return the
Sensor to the
previous position
so that the
distance
between the
Sensor and
sensing object is
S. Secure the
position of the
Sensor to
complete the
sensitivity
adjustment.
Note:
If the E2C Amplifier Unit malfunctions due to radical ambient temperature changes, shorten the distance between the Sensor and
sensing object to 80% maximum of the set distance.