D5C

Safety Precautions

Refer to 

Safety Precautions for All Limit Switches

.

Make sure that the antenna does not come into contact 
with the human body, otherwise an electric shock may 
be received.

Mounting

Do not tighten the nuts with excessive force. 
The maximum permissible tightening force of 
each nut with a washer is 29.4 N

·

m.

Grounding of Antenna and Sensing 

Object

<Size of Sensing Object>

Grounded Object

If the sensing object is the following grounded conductor, its size 
will not affect the operation of the D5C. Check for the presence of 
insulators sticking to the sensing object or the corrosion of the 
sensing object, however, so that the ground resistance will not 
exceed 3 k

Ω.

Contact with Grounded Conductor
The sensing object is equivalently grounded through
ground resistor R.

R: 3 k

 max.

The sensing object must not come into contact with the human body

Non-grounded Object

If the sensing object is the following non-grounded conductor, the 
D5C will operate if the capacitance between the sensing object and 
the ground is 30 pF or more. The larger the surface area of the 
sensing object is, the higher its capacitance will be. The shorter the 
distance between the sensing object and the ground is, the higher 
the capacitance will be. Furthermore, the capacitance greatly 
varies with the ground condition (e.g., dry sand, concrete, or wet 
soil).

Contact with Non-grounded Conductor
The sensing object is equivalently grounded through capacitor C.

C: 30 pF min.

<Conditions of Sensing Object>

The detection of conductors (e.g., iron, stainless steel, aluminum, 
and brass objects) poses no particular problem. A conductor 
coated with paint cannot be detected, however, because there is no 
electrical continuity between the antenna and the conductor.

Non-conductive objects (e.g., plastic, ceramic, glass, and cloth 
objects) can be detected by grounding them indirectly.
(Refer to 

Application Examples

 on page 1.)

Antenna

<Shape and Extension>

If a metal plate is used as an antenna by connecting it to the built-in 
or separated antenna of the D5C, the surface area of the metal plate 
must be 200 cm

2

 maximum (Fig. 1). The antenna can be extended, 

provided that the total length of the antenna is 1 m maximum (Fig. 2) 
and that the bottom of the antenna is at least 10 cm (Fig. 3) away from 
the ground. Refer to the illustrations below
The D5C may be damaged if the antenna is excessively large or 
heavy or if the antenna is used in locations with excessive vibration or 
shock. Be sure to check the locations before use.

<Parallel Arrangement>

If there are multiple D5Cs are located in parallel, make sure that the 
distance between adjacent antennas is at least 3 cm.

Maintenance

Make sure that the portion of the antenna that comes into contact 
with sensing objects is free of oil, dirt, or rust, or any other insulator. 
Otherwise, the D5C will not operate.

The degree of protection of the D5C is IP67. The D5C cannot be, 
however, used in the water or oil.

Locations with Sprayed Water or Oil
The D5C may malfunction in locations where the D5C is frequently 
exposed to sprayed water or oil. Especially, the D5C may 
malfunction more frequently if it is exposed to sprayed water-
soluble cutting oil. In such locations, be sure to take appropriate 
measures to protect the D5C from oil and water.

Wiring and Connections

Be sure to wire the D5C correctly according to the color of each 
cord. Incorrect wiring may damage the internal components of the 
D5C or the D5C may malfunction.

A maximum of two models can be connected in series provided that 
100 to 240 V is supplied. DC models cannot be connected in series.

Be sure to supply power to the D5C via the load. If power is supplied 
to the D5C directly, the fuse will blow.

If there are wire power lines or high-tension lines close to the cable 
of the D5C, be sure to wire the cable of the D5C away from power 
lines or high-tension lines or lay the cable in an exclusive, shielded 
conduit.

Remove the caution label on the end of the cable before wiring the 
cable.

 CAUTIONS

Precautions for Correct Use 

18.5

+0.5

 

-0

    

dia.

Mounting Hole Dimension

Grounded
         conductor

D5C

3 k

 max.

R

Generally, the conductor will
be detectable if the ambient
humidity is 60% to 70%RH and
the surface area of the conductor
is approximately 300 

×

 500 mm.

Non-grounded

conductor

30 pF min.

C

Metal plate

200cm

2

max.

Fig. 1

D5C

Fig. 2

D5C

1

+ --- 

6

1 m

3

1

2

6

4

5

Fig. 3

D5C

10 cm min.

1 m max.

Ground

D5C

3 cm min.

D5C

D5C

D5C

3 cm min.

D5C

D5C

Load

100 to 240 VAC

Power
source

Summary of Contents for D5C Series

Page 1: ...ting Free attachment to enable changing the antenna shape according to the application Malfunction may occur if used in locations subject to water or oil Be sure to read Safety Precautions on page 6 t...

Page 2: ...0 Hz Sensitivity setting range 30 to 100 pF Current consumption 17 mA max Leakage current Circuit 2 mA max Antenna 1 mA max 1 mA max Response time 2 ms max 8 ms max Output current 200 mA max resistive...

Page 3: ...ity Temperature C Sensitivity pF 10 20 30 200 150 100 50 0 With sensitivity adjuster set to minimum sensitivity With sensitivity adjuster set to maximum sensitivity Voltage V Sensitivity pF 200 300 10...

Page 4: ...ction However limit the overtravel to within 20 mm from the free position The force that pushes the actuator must not exceed 1 96 N 2 Vinyl insulated round cable oil and shock resistant type 4 dia thr...

Page 5: ...6 N 2 Vinyl insulated round cable oil and shock resistant type 4 dia three conductors 0 3 mm2 3 Use after removing the caution label Coil Spring D5C 1AS0 2 1 LED Operation indicator M18 1 Two internal...

Page 6: ...nded provided that the total length of the antenna is 1 m maximum Fig 2 and that the bottom of the antenna is at least 10 cm Fig 3 away from the ground Refer to the illustrations below The D5C may be...

Page 7: ...er supply of the PC Programmable Controller is not available to the D5C 1D 0 The negative line of the service power supply of the PC is not grounded Therefore the D5C may not operate Furthermore if th...

Page 8: ...products Outdoor use uses involving potential chemical contamination or electrical interference or conditions or uses not described in this catalog Nuclear energy control systems combustion systems r...

Reviews: