background image

6

7

Item

Descriptions

Item

Descriptions

Product name

Model

Applicable PLC-series

Applicable Unit

CX-Process Monitor Plus

WS02-LCMC1-EV2

CS/CJ-series

•Loop Control Unit Ver. 2.0 or higher
•Loop Control Board
•Process-control CPU Unit
•Loop-control CPU Unit

Applicable computer

Personal computer

CPU

OS

Memory

Hard disk drive

Monitor

CD-ROM drive

Mouse

Printer

Sound board

Min. required: 128 Mbytes, Recommended: 256 Mbytes or more

Min. required: 650 Mbytes of free space, Recommended: 800 Mbytes or more of free space

Min. required: XGA, Recommended: XGA or higher, min. 1024 x 768 dots, 256 colors

At least one

Recommended: Microsoft mouse or compatible pointing device

Any printer supported by Microsoft Windows

1 board

FinsGateway (One of the following must be installed according to the communications method with the PLC.)
•Serial Unit driver (Host Link)
•Controller Link driver (Controller Link)
•CLK (PCI) driver (Controller Link, PCI bus)
•ETN_UNIT driver (Ethernet)

CSV tags and tags for Monitor Plus (CSV monitor tags) are set using the CX-Process Tool. 
These tags are used to specify Loop Control Unit/Board data.

Data collected 
(logger function)

Realtime trend

Data display

Horizontal (time) axis: 2, 4, 8, 12 and 24-hour time units can be scrolled
Vertical (8-point common) axis: Graduation can be enlarged by a factor or 1, 2, 5 and 10.
Data is displayed from the time when the specified display start time is reached.
Display color: Red, yellow, green, blue, magenta, purple, cyan, or white

IBM PC/AT or compatible

Min. required: Pentium MMX233 MHz or faster, Recommended: Celeron 400 MHz or faster

Microsoft Windows NT 4.0 (Service Pack 6a or higher), Windows 2000 Professional (Service Pack 4 or higher), 
Windows XP Professional (Operation is not supported on Windows 95, 98, or ME.)

Software that must be installed at the same time

Connecting method

Connection with CPU 
Unit (or Serial 
Communications 
Board/Unit)

Using FinsGateway 
Serial Unit version

Loop Control Unit/Board data specification method

Prepare user configuration screens for use in the online operation screen.

Offline operation functions

Place buttons for progressing on the Control Screen, Trend Screen, and other screens. Four columns and 
eight lines are displayed on each screen (32 screens max.).  Alarm status for each loop is displayed on 
the button on Control Screens.

Online 
operation 
functions

Using FinsGateway 
CLK (PCI) Driver

Connect the computer to the CPU Unit's peripheral port, RS-232C port, 
or the RS-232C port of a Serial Communications Unit.
•Connecting Cable:
 When connecting to the CPU Unit peripheral ports: Model CS1W-CN

 (2 m, 6 m)

 When connecting to the CPU Unit's RS-232C port: Model XW2Z-

-

 (2 m, 5 m)

 For details on the Connecting Cables, refer to CX-Process Monitor Plus Operation 
 Manual (Cat.  No. W428).
•Communications protocol with PLC: Host Link (not supported on Peripheral bus)

Install the driver in a computer equipped with a Controller Link Support Board 
(PCI slot) to support communications between the computer and PLCs equipped 
with a Controller Link Unit.

Using FinsGateway 
Controller Link 
driver

Install the driver in a computer equipped with a Controller Link Support Board 
(ISA slot) to support communications between the computer and PLCs equipped 
with a Controller Link Unit.

Using FinsGateway 
ETN_UNIT driver

Install the FinsGateway ETN_UNIT driver on the computer on which an Ethernet 
board is mounted to enable communications with the PLC on which the Ethernet 
Unit is mounted.

Connection via Controller Link

Connection via Ethernet

User 
Configuration 
Screen

Online 
operation 
functions

User 
Configuration 
Screen

Overview Screen

Control Screen

Tuning Screen

The analog signals output from tag ITEMs for each function block can be collected at fixed intervals and 
saved to a file. If necessary, up to 8 analog signals can be displayed on one screen in the form of 
a multi-dot recorder. 

Trend Screen

Stores 10, 20, 50, 100, or 300 
hours of data for up to 480 
tags sampled at 1, 2, 5, 10, or 
30-second intervals.

Historical trend

Stores 30, 150, 300, 900, or 
1,800 days of data for up to 
960 tags sampled at 1, 5, 10, 
30, or 60-minute intervals.

Data can be saved in CSV format 
either using button commands, 
or automatically at a set interval 
(every 1, 2, 3, 4, 6, 8, 10, 12, 18, 
20, 24, 48, 72, 96, 120, or 240 
hours).

Displays the PV trend for the settings in Segment Program 2 (Block Model 157). 
Segments can be set in table format while observing a time axis graph.

Segment Program 
2 Screen

This screen displays changes in the plant status using graphic elements representing plant devices pasted 
to the screen from the graphic elements library. The maximum number of screens is 200.
Graphics/graphic parts: Text, straight lines, rectangles, rectangles with rounded corners, ellipses, 
polygons, images
Functional Objects Provided in Library
•Fixed graphic elements provided in library: Text, instruments, thermometers, transmitters, orifices
•Variable graphic elements provided in library:
 Analog display: Bar graph display, numeric indication, tanks
 Analog settings: Numeric settings
 Contact display: Pumps, valves, pipes
 Contact operation: Switches
•Screen-displaying elements: Jump (screen jump) elements and FP switch (faceplate pop-up) elements
•Individual Graphic Screens can be imported/exported as files.
•Multiple graphic elements can be grouped and imported/exported as files.

Graphic Screen

This screen notifies the operator of alarms or errors that occur by changing the display color and emitting 
sound. A message with two lines of 16 characters each is displayed on the screen at the same time. 
A total of 16 screen elements (4 columns x 4 lines) can be displayed on each screen. The maximum number 
of screens is 5.

Annunciator Screen

This screen displays the Loop Control Unit/Board system error information.

System Monitor Screen

This screen displays logs of the run/stop history and a history of execution errors that occur on the Loop 
Control Unit/Board together with the date and time of occurrence.
Output possible in CSV format.

System Monitor Log 
Screen

This screen displays a pre-registered message with two lines of 64 characters each 
together with the date of occurrence when the specified internal switch is set to ON.
Max. number of registerable messages: 1,000, Number of display colors: 16
Up to 1,000 messages are displayed in a single screen.
Output possible in CSV format.

Operation Guide 
Message Screen

A record of alarms (time of error occurrence, tag name, PV or MV current value at occurrence, alarm type, 
etc.) that occur and that are input from the Control and Alarm blocks is saved and displayed as a list later.
Up to 1,000 alarm messages are displayed in a single screen.
Output possible in CSV format.

Alarm Log Screen

Operation logs of data elements and switches in Graphic Screens and a record of changes (date and time 
of operation, tag name, original ITEM data setting, new ITEM data setting, etc.) made to ITEM data on the 
Loop Control Unit/Board in the Control or Tuning Screen are saved and displayed as lists later.
Up to 1,000 operation messages are displayed in a single screen.
Output possible in CSV format.

Operation Log 
Screen

System Fixed 
Screen

Data display

Horizontal (time) axis: The time axis can be scrolled in 2, 4, 8, 12, 24, or 72-hour time units.
Vertical axis: Scale can be enlarged by a factor or 1, 2, 5 and 10.
Data is displayed from the time when the specified display start time is reached.
Display color: Yellow, blue, green, or violet

Data collection

Stores 3, 30, or 180 days of data sampled at 1, 
10, or 60-second intervals.

Data can be saved manually in 
CSV format by pressing a button, 
or it can be saved automatically 
in CSV format each time a batch is 
completed. Past data is saved 
automatically as binary data.

Data display

Horizontal (time) axis: The time axis can be scrolled in the following time units. 
                                      1, 2, 4, 6, 8, 12, 24, 36, 48, or 72 hours 
                                       7 or 10 days
Vertical (8-point common) axis: Scale can be enlarged by a factor or 1, 2, 5 or 10.
Data is displayed from the time when the specified display start time is reached.
Display color: Red, yellow, green, blue, magenta, purple, cyan, or white

CX-Process Monitor Plus Specifications

CX-Process Monitor Plus Specifications

The analog signals output from each function block's tag ITEMs can be collected at fixed intervals and 
stored automatically when a specified tag data condition is met. Past data can be superimposed on the chart.

Batch Trend Screen

Data collection

Stores 10 days or 4 hours of data for up to 960
 tags sampled at 1-minute or 1-second intervals.

Data can be saved manually in 
CSV format by pressing a button, 
or it can be saved automatically 
in CSV format each time a batch is 
completed. Past data is saved 
automatically as binary data.

Control blocks such as the PID blocks and Indication blocks, and some Operation blocks are displayed for up 
to 8 loops in a single screen in the form of a field device. The maximum number of screens is 400.
This screen displays the SP, PV, and MV numeric values, displays a PV as a bar graph that can be scaled, 
and can be used for changing the SP, MAN, and other setting values. When an alarm occurs, the color of the 
bar graphs changes. You can progress to the Tuning Screen from the Control Screen.

This screen is for setting P, I, and D parameters in control blocks such as the PID blocks. The PV, SP, and MV 
can be monitored while tuning the parameters. The maximum number of screens is 400 x 8 = 3,200.
When an alarm occurs, the color of the bar graphs changes.
Fine-tuning according to the degree specified by the user is possible for PID constants.

Summary of Contents for CX-PROCESS

Page 1: ...WS02 LCMC1 EV2 The CX Process Monitor Plus can improve cost performance for monitoring and controlling equipment storing operating data and checking the alarm status CX Process Monitor Plus Ver 2 0...

Page 2: ...rade Version 2 0 upgrade Version 2 0 upgrade Monitor and control the operating status of function blocks in the Loop Controller 1 Function Monitor the alarm status of function blocks in the Loop Contr...

Page 3: ...ator Screens can display up to 16 alarm displays per screen Operation Guide Message Screens can display messages that were registered in advance by the user Alarm Log Screens The Alarm Log can be disp...

Page 4: ...50 Value 80 Move to selected screen Screen selection dialog box SP Segment Program 2 settings PV Click Display Hide switch With the Upgraded Graphic Functions It Is Easy to Configure the Monitoring S...

Page 5: ...mmunications Unit Connecting Cable When connecting to the CPU Unit peripheral ports Model CS1W CN 2 m 6 m When connecting to the CPU Unit s RS 232C port Model XW2Z 2 m 5 m For details on the Connectin...

Page 6: ...screen Output possible in CSV format Operation Guide Message Screen A record of alarms time of error occurrence tag name PV or MV current value at occurrence alarm type etc that occur and that are in...

Page 7: ...that the system as a whole has been designed to address the risks and that the OMRON products are properly rated and installed for the intended use within the overall equipment or system Warranty and...