Section 3-7
+%
Output Pulse Duration
A Digital Output that is configured to have an Output Pulse Duration turns ON
immediately and will stay ON for the specified Pulse Duration. After the Pulse
Duration has elapsed the Digital Output turns OFF.
Note
The status of the Outputs is reflected in CIO (words n+14, n+15). If a Digital Out-
put is configured to have Programmable Output Pulse functionality, the actual
physical status of the Output (Turn ON Delay and/or Pulse Duration included) is
reflected in the corresponding bit in CIO.
Configuring Programmable
Output Pulses
Note
1. A Digital Output to which an Output ON-Delay or Output Pulse is applied will
turn OFF immediately after the corresponding Output (0-3) of the Output Pat-
tern has turned OFF. An Output Pulse ON-Delay or Output Pulse Duration in
progress will be reset immediately and the Digital Output is turned OFF or stays
OFF.
2. If an Output is switched ON manually (refer to 3-5-3
)
and Programmable Output Pulse functionality has been assigned to that Out-
put, then this functionality will not be applied to the Output. Instead, the Output
is switched ON immediately.
3 Once the output has turned OFF after the specified pulse duration, the status
in CIO n+14/n+15 may differ from the internal UNIT OUTPUT PATTERN (refer
to 3-5 "Output Control") where the output may still be ON.
Referring to 3-5-1-1 "Range Mode Overview" this implies that the output will
stay OFF while the counter value is still inside the range that activated the out-
put or, before leaving the current range, enters a new range that activate the
output because the output is already ON in the internal UNIT OUTPUT PAT-
TERN. If you want the output to generate an output pulse again, the counter
value first needs to exit all ranges that set this output. Only this way the output
is turned OFF in the UNIT OUTPUT PATTERN.
Referring to 3-5-2-1 "Comparison Mode Overview" this implies that the output
will not turn ON if a comparison value (e.g. the same comparison value that
caused the output to turn ON) is crossed that would set this output because the
output is already ON in the internal UNIT OUTPUT PATTERN. If you want the
output to generate an output pulse again, the counter value first needs a new
event (e.g. cross a comparison value) that resets this output. Only this way the
output is turned OFF in the UNIT OUTPUT PATTERN.
O0:
O1:
O2:
O3:
m+9
m+11
m+13
m+15
Output Pulse ON-Delay:
0000
(BCD)
= Normal Functionality
0001-9999
(BCD)
= Output Pulse ON-Delay in milliseconds
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
O0:
O1:
O2:
O3:
m+10
m+12
m+14
m+16
Output Pulse Duration:
0000
(BCD)
= Normal Functionality
0001-9999
(BCD)
= Output Pulse Duration in milliseconds
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
W902-E2-03.book Seite 82 Donnerstag, 7. Oktober 2004 2:06 14
Summary of Contents for CS1W-CT021
Page 1: ...OPERATION MANUAL High speed Counter Units CS1W CT021 CS1W CT041 Cat No W902 E2 03...
Page 3: ...W902 E2 03 book Seite iv Donnerstag 7 Oktober 2004 2 06 14...
Page 5: ...W902 E2 03 book Seite vi Donnerstag 7 Oktober 2004 2 06 14...
Page 39: ...W902 E2 03 book Seite 24 Donnerstag 7 Oktober 2004 2 06 14...
Page 59: ...A 2 Section 2 3 W902 E2 03 book Seite 44 Donnerstag 7 Oktober 2004 2 06 14...
Page 155: ...4 Section 4 6 W902 E2 03 book Seite 140 Donnerstag 7 Oktober 2004 2 06 14...
Page 199: ...G W902 E2 03 book Seite 184 Donnerstag 7 Oktober 2004 2 06 14...