Section 5:  Using CX Programmer with the CP1W-ETN01-US 

To use CX Programmer with a CP1H or CP1L PLC Ethernet Adapter, you must have  
CX-Programmer Version 8.0 or later installed. (CX-One Version 3.0 includes CX-
Programmer 8.0).  Select Ethernet as the Network Type.  If Ethernet is not available 
from the Network Type follow the instructions below**

 

 

**Please go to the folder on your PC: 

C:\Program Files\OMRON\CX-Server\StaticData\StaticRoot\Devices\Ocplc\Cs1\CP1L\M 

Rename the file in the folder from: StaticInfo.xml to old_StaticInfo.xml 

(If you do not see the file and CX-One or CX-Programmer/Jr is installed, then Go to 
Tools, Folder Options, View and make sure the file type is Shown and Not Hidden) 

Please copy new file

*

: StaticInfo.xml to the following folder on your PC 

C:\Program Files\OMRON\CX-Server\StaticData\StaticRoot\Devices\Ocplc\Cs1\CP1L\M 

*File located at: Omron247.com under Document Search:  

CP1ETN.ZIP  

(both CP1 

Ethernet Setup Guide and StaticInfo.xml included in zip file)  

Restart the CX-Programmer program, and the Ethernet should now be visible up from 
the Network Type pull down selection. 

 

 

Page 6 of 8 

Summary of Contents for CP1L

Page 1: ...CP1H CP1L Ethernet to Serial Adapter CP1W ETN01 US Application and Setup Guide Revision 1 11 2 11 2009...

Page 2: ...adapter is an Ethernet to Serial adapter it will behave with the response characteristics of a serial port and with throughput and frame length limits associated with serial communications protocols...

Page 3: ...CP1H or CP1L PLC The adapter will not support more than 2 simultaneous connections PLC to PLC communications using Ethernet are not possible as the adapter only functions as an Ethernet slave device U...

Page 4: ...e assigned to the PC s Ethernet card for this purpose Simply enter the IP address of the adapter 192 168 250 11 in the web browsers address field to access the configuration page If you would like to...

Page 5: ...ings of CX Programmer on the Serial Port 1 or Serial Port 2 tab To maximize the throughput of the CP1W ETN01 US the amount of time per PLC scan that is allowed for servicing communications ports shoul...

Page 6: ...L M Rename the file in the folder from StaticInfo xml to old_StaticInfo xml If you do not see the file and CX One or CX Programmer Jr is installed then Go to Tools Folder Options View and make sure th...

Page 7: ...s On the Driver tab specify the IP address of the CP1W ETN01 US adapter 192 168 250 11 is the address of the adapter when the unit is shipped and shown as an example If you have changed the IP address...

Page 8: ...d on any screen Smart Active Parts can be used with the CP1W ETN01 US module but may result in decreased performance If Smart Active Parts are required in a application a CP1H CJ1W ETN21 should be use...

Page 9: ...nt or addition to the above warranty See http www omron247 com or contact your Omron representative for pub lished information 14 Limitation on Liability Etc OMRON COMPANIES SHALL NOT BE LIABLE FOR SP...

Page 10: ...ronto ON Canada 416 286 6465 866 986 6766 www omron ca OMRON ELETR NICA DO BRASIL LTDA HEAD OFFICE S o Paulo SP Brasil 55 11 2101 6300 www omron com br OMRON ELECTRONICS MEXICO SA DE CV HEAD OFFICE Ap...

Reviews: