background image

Section 6:  Using an NS Series HMI with a CP1W-ETN01-US 

To use an NS series HMI with a CP1W-ETN01-US, it is necessary to limit the number of 
functional objects on each screen to effectively limit the size of the FINS Ethernet 
packet that will be sent to read the data from the PLC.  No more than 20 functional 
objects (bit lamps, pushbuttons, numeric / string displays, etc) should be used on any 
screen. 

Smart Active Parts can be used with the CP1W-ETN01-US module, but may result in 
decreased performance.  If Smart Active Parts are required in a application, a CP1H + 
CJ1W-ETN21 should be used. 

When adding the CP1H or CP1L PLC as a Host in CX Designer, specify the Host Type 
as Sysmac-CS1/CJ1, the Network Address as 1, and the Node Address as the last 
octet of the IP address of the CP1W-ETN01-US.  

11

 would be the Node Address if the 

IP address were 192.168.250.

11

.  If you have changed the IP Address of the adapter 

please use the last octet of the new address. 

 

 

Page 8 of 8 

Summary of Contents for CP1L

Page 1: ...CP1H CP1L Ethernet to Serial Adapter CP1W ETN01 US Application and Setup Guide Revision 1 11 2 11 2009...

Page 2: ...adapter is an Ethernet to Serial adapter it will behave with the response characteristics of a serial port and with throughput and frame length limits associated with serial communications protocols...

Page 3: ...CP1H or CP1L PLC The adapter will not support more than 2 simultaneous connections PLC to PLC communications using Ethernet are not possible as the adapter only functions as an Ethernet slave device U...

Page 4: ...e assigned to the PC s Ethernet card for this purpose Simply enter the IP address of the adapter 192 168 250 11 in the web browsers address field to access the configuration page If you would like to...

Page 5: ...ings of CX Programmer on the Serial Port 1 or Serial Port 2 tab To maximize the throughput of the CP1W ETN01 US the amount of time per PLC scan that is allowed for servicing communications ports shoul...

Page 6: ...L M Rename the file in the folder from StaticInfo xml to old_StaticInfo xml If you do not see the file and CX One or CX Programmer Jr is installed then Go to Tools Folder Options View and make sure th...

Page 7: ...s On the Driver tab specify the IP address of the CP1W ETN01 US adapter 192 168 250 11 is the address of the adapter when the unit is shipped and shown as an example If you have changed the IP address...

Page 8: ...d on any screen Smart Active Parts can be used with the CP1W ETN01 US module but may result in decreased performance If Smart Active Parts are required in a application a CP1H CJ1W ETN21 should be use...

Page 9: ...nt or addition to the above warranty See http www omron247 com or contact your Omron representative for pub lished information 14 Limitation on Liability Etc OMRON COMPANIES SHALL NOT BE LIABLE FOR SP...

Page 10: ...ronto ON Canada 416 286 6465 866 986 6766 www omron ca OMRON ELETR NICA DO BRASIL LTDA HEAD OFFICE S o Paulo SP Brasil 55 11 2101 6300 www omron com br OMRON ELECTRONICS MEXICO SA DE CV HEAD OFFICE Ap...

Reviews: