6-1
Error Messages and Troubleshooting
Error
Possible Cause
Correction
Indicators do not light
PC power is OFF
Apply power to PC
Unit is not mounted securely
Mount Unit and tighten mounting
screws
Indicator 4 lights during PROGRAM or
MONITOR when SW 3 is set to 0
(GPC/FIT/LSS connection error)
GPC/FIT/LSS power is OFF
Apply power to the GPC/FIT/LSS
Cable to GPC/FIT/LSS is
disconnected
Reconnect the cable properly and
secure with screws
Broken cable or poor contact to
GPC/FIT/LSS
Repair or replace the cable
Indicator 4 lights during RUN or
MONITOR mode when SW 3 is set to
0 (operation continues)
JMP(04) and JME(05) are not used in
pairs
Rewrite the program to use JMP(04)
and JME(05) in pairs
Clock data read error
Reset clock data in PROGRAM mode
Fatal Errors
If an error occurs that stops the Unit, the indicator indicated in the following table
will flash regardless of the setting of SW 3. Possible errors vary depending on
which indicator flashes.
Indicator
Error
Possible Cause
Correction
0
Incorrect RAM (verified when
power is connected or at reset
time)
Failed RAM
Replace Unit
Incorrect EEPROM write
Unable to write program to Unit
Replace Unit
Pin 1, 6, 7, or 8 set incorrectly
Pin 1, 6, 7, or 8 set to ON
Turn OFF pins 1, 6, 7, and 8
1
Program error
Program within Unit has been
corrupted
Rewrite program. If error persists,
replace Unit. Transfer data to the
entire user program area. If
transmission is interrupted after
sending END(01), the write will be
invalid; always write completely to
end of program memory area.
2
No END instruction
END(01) is missing in program
Insert END(01) and retransfer the
program
3
Clock data write error
Incorrect clock data written to
DM 60 DM to 63
Write correct clock data
4
Program conversion error
Program contains an instruction
which cannot be used in the Unit
Review program
Program is too long and cannot
be written to the Unit
5
Too many jumps
Program contains 10 or more
JMP(04) instructions
Reduce jumps to 9 or less
6
Too many DIFU(13)/DIFD(14)s
Program contains 17 or more
DIFU(13)/DIFD(14)s
Reduce DIFU(13)/DIFD(14)s to
16 or less
7
CPU error
Watchdog timer error has
occurred
Review and correct program to
limit scan time to 100 ms
maximum
* ( ).
Section 6-1
Summary of Contents for C500-LDP01-V1
Page 1: ...C500 LDP01 V1 Ladder Program I O Unit Operation Manual Revised January 1992...
Page 2: ......
Page 4: ......
Page 5: ...0 1 1 1 2 1 2 1 3 2 2 2 4 12 2 1 56 7 02 5 1 8 1 1 7 5 2...
Page 7: ...02 4 8 02 3 3 3 8 8 3 4 3 3 4...
Page 11: ...8 9 4 8 8...
Page 18: ...8 3 8 02 5 02 5 8 02 2 2 3 0 5 0 1 1...
Page 29: ...8 4 6 6 02 8 2 4 12 2 1 56 7 02 02...
Page 37: ...3 8 4 8 4 3 5 1 8 1...
Page 56: ...1 6 0 0 1 7 8 8 02 1 7 8 1 02 3 0 5 02 02 02 2 02 2 02 5 02 02 6 7 12 2...