![Omron C200HE-CPU11 Installation Manual Download Page 34](http://html1.mh-extra.com/html/omron/c200he-cpu11/c200he-cpu11_installation-manual_742480034.webp)
22
4.
GR
Ground the GR terminal to 100
Ω
or less to protect against possible electri-
cal shock.
5.
24 VDC Output
(C200HW-PA204S Only)
The 24 VDC output terminals can be used to supply power to DC Input Units.
The combined power consumption for both 5 V and 24 V must be 30 W or
less.
6.
DC Input
(C200HW-PD024 Only)
Supply 24 VDC to the DC input terminals.
7.
RUN Output
(C200HW-PA204R/PA209R Only)
The internal contact will turn ON when the CPU Unit is operating in RUN or
MONITOR mode. These terminals are available only on the C200HW-
PA204R.
Units