![Omron C200HE-CPU11 Installation Manual Download Page 178](http://html1.mh-extra.com/html/omron/c200he-cpu11/c200he-cpu11_installation-manual_742480178.webp)
Appendix B
Specifications
166
Transistor Output Unit C200H-OD21B (32 Points)
(Load Short-circuit Protection Provided)
Max. Switching Current
0.5 A 24 VDC
+10%
/
–15%
(5 A/Unit)
Min. Switching Current
None
Leakage Current
0.1 mA max.
Residual Voltage
0.8 V max.
ON Response Time
0.1 ms max.
OFF Response Time
0.3 ms max.
No. of Circuits
32 (32 points/common)
Internal Current Consumption
180 mA 5 VDC max.
Fuses
One 7 A fuse (1 fuse/common)
The fuses are not user-replacable.
Power for External Supply
160 mA 24 VDC
+10%
/
–15%
min.
(5 mA
×
number of ON pts)
Weight
180 g max.
Alarm Indicator
Lamp F lights (unless fuse is broken).
Load Short-circuit Prevention
(see note 1)
Detection current: 0.7 to 2.5 A
Automatic restart after error clearance.
Dimensions
C-shape
Note
When the short-circuit/overload protection is activated for a contact point, the output for that point is turned
OFF. At the same time, lamp “F” lights up, and the alarm from AR0205 to AR0214 corresponding to the I/O
number turns ON. After the cause of the error has been removed, the alarm will be cleared automatically
when the internal temperature of the element drops.
Circuit Configuration
Output LED
indicator
Internal circuit
Alarm
LED
indi-
cator
Output LED
indicator
to
to
to
to
0 V
0 V
0 V
0 V
Short-circuit
protection
circuit
Short-circuit
protection
circuit