3
Perform replacement on a stable and flat surface.
●
Handle the battery carefully so that you do not drop it.
●
Dropping the battery may result in injury or burns due to leakage (acid).
Use a specified battery for replacement.
●
Using a battery other than that which is specified may cause a fire.
●
Product models: BUB100RE: 2 required
Do not replace the battery in a place where there is flammable gas.
●
A spark may occur when connecting the battery, which may cause an explosion or fire.
If fluid (dilute sulfuric acid) leaks from the battery, do not touch it.
●
Doing so may cause blindness or burns.
●
If it touches your eyes or skin, wash it out with lots of clean water and consult your doctor.
Do not try to disassemble or modify the product.
●
Doing so may cause the battery to leak dilute sulfuric acid, which may cause blindness or burns.
Do not drop the battery or expose it to strong impact.
●
Doing so may cause the battery to leak dilute sulfuric acid.
Do not short the battery with metal objects.
●
Doing so may cause an electric shock, fire or burn.
●
Some electrical energy remains inside the spent battery.
Do not put the battery into fire, and do not break it.
●
The battery may explode or leak dilute sulfuric acid.
Do not use a new battery and an old battery at the same time.
●
Doing so may cause the battery to leak dilute sulfuric acid.
Caution
(battery replacement)
Notes
Charge the battery immediately after purchase.
●
If you do not use the unit for a long time after purchase, the battery performance may deteriorate and it may be-
come unusable.
●
The battery can be charged by connecting the AC input plug of the UPS to commercial power.
When storing the UPS, charge the battery thoroughly and turn OFF the power switch. Recharge the battery
within 6 months when storage temperature is 25℃ or less, or within 2 months when storage temperature is
40℃ or less.
●
The battery discharges even when it not being used, and it goes into over discharge state if it is left for a long
period of time.
The backup time may become shorter or the battery may become unusable.
●
The battery charge time is 36 hours when 1 additional battery unit is connected, 60 hours when 2 units
connected, or 84 hours when 3 units connected.
Do not install or store the unit in a place exposed to direct sunlight.
●
A rise in temperature may cause the built-in battery to deteriorate rapidly and become unusable.
This unit uses a lead acid battery.
●
Lead acid batteries are a valuable recyclable resource. Please recycle.
For information about recycling, please contact our peripheral device repair center.
Pb