3 Check and start operation
3-2 Checking the operation
BU150R
40
3-2 Checking the operation
When you finish connecting the unit, check that the Battery Mode is performed normally
according to the following procedure.
Pull out the "AC input" plug during operation and create the same situation as the
occurrence of a power failure to check the operation.
1.
Press the unit's "Power" switch to turn ON the power.
When the power turns on, the beeper sounds and self diagnosis starts
automatically.
*
If the battery voltage is low, the self-diagnostic test is not performed.
2.
When the self-diagnosis test finishes normally, the unit's operation switches to
commercial power and the status indication below is displayed.
Status
indicator
Description
"Power" switch "ON"
Operating normally
When the battery capacity is lower than the setting, the following display appears
on 7 segment LED.
( indicates blinking)
Status
indicator
Description
Battery charge is low, so the unit is waiting to start up.